| 2007-05-07 16:04:27 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE MISSING LICENSE INFORMATION |
| | REQUIRED ON TITLE BLOCKS PER FAC 61G1-16.004 AND |
| | FS481.219. |
| | THE LETTER ATTACHED MENTIONS THE ARCHITECT IS A SOLE |
| | PROPRIETOR , HOWEVER ANY USEOR NAME FOR FIRM, |
| | FICTITIOUS NAME MUST CONTAIN A FIRM LICENSE NUMBER |
| | WHICH IS ALSO KNOWN AS A CERTIFICATE OF AUTHORIZATION |
| | NUMBER. IF THERE ARE ANY QUESTIONS ON THIS, PLEASE |
| | CONTACT THE STATE BOARD OF ARCHITECT'S LEGAL COUNSEL |
| | PROSECUTING ATTORNEY MR. DAVID MINACCI AS THIS HAS BEEN |
| | CONFIRMED. |
| | INFORMATION CAN BE FOUND ON THE BOARD OF ARCHITECT'S |
| | WEBSITE OR AT THE FOLLOWING WEBSITE ADDRESS. |
| | HTTP://WWW.STSLAW.COM/HOME.ASP |
| | |
| | 2) NOTE: PLEASE KNOW THAT AN ELECTRICAL PERMIT IS |
| | REQUIRED FOR ELECTRICAL DEMO WORK BEFORE DEMO MAY |
| | BEGIN. ALL ELECTRICAL IS TO BE SAFE FROM LIFE SAFETY |
| | AND PROPERTY HAZARDS. NFPA241, NFPA-70 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |