Plan Review Details - Permit 07050024
Plan Review Stops For Permit 07050024
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-01-29 Cont ID  
Sent By jwitmer Date 2008-01-29 Time 09:05 Rev Time 0.55
Received By jwitmer Date 2008-01-29 Time 09:05 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-01-07 Cont ID  
Sent By jwitmer Date 2008-01-07 Time 13:14 Rev Time 0.55
Received By jwitmer Date 2008-01-07 Time 13:14 Sent To  
Notes
2008-01-07 13:15:40REVISION DATED 12-26-07 ENGINEERING LETTER

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-12-26 Cont ID  
Sent By jwitmer Date 2007-12-26 Time 09:58 Rev Time 0.77
Received By jwitmer Date 2007-12-26 Time 09:58 Sent To PC
Notes
2007-12-26 10:04:51BUILDING PLAN REVIEW
 PERMIT:07050024
 ADD: 208 CLEMATIS ST
 CONT: FINLEY CONSTRUCTION
 TEL: (561)352-5856
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 LETTER OF CLARIFICATION REVIEW
 ACTION: DENIED
  
 THE LETTER FROM ARCHITECT DAVID LAWRENCES' OFFICE
 INDICATES THAT THE STRUCTURAL ENGINEER KUPPUSAMY
 VENKATESAN (42793) MADE A JOBSITE INSPECTION OF THIS
 CONDITION AND CONCURS THIS OPTION WILL BE SATISFACTORY
 BUT NO NEW STRUCTURAL SHEET S1 OR LETTER FROM THE
 ENGINEER HAS OCCUMPANIED THE ARCHITECTS LETTER. PLEASE
 PROVIDE THE ENGINEERING LETTER OR THE NEW S1 SHEET
 INDICATING THE REVISION BEING MADE.
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-09-04 Cont ID  
Sent By lmartine Date 2007-09-04 Time 15:18 Rev Time 0.00
Received By lmartine Date 2007-09-04 Time 15:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-15 Cont ID  
Sent By jwitmer Date 2007-06-15 Time 17:33 Rev Time 1.33
Received By jwitmer Date 2007-06-15 Time 17:33 Sent To  
Notes
2007-06-15 17:47:48BUILDING PLAN REVIEW
 PERMIT: 07050024
 ADD: 208 CLEMATIS ST
 CONT: FINLEY CONSTRUCTION
 TEL: (561) 352-5856
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3A) PLANS INDICATE THAT THEY ARE DESIGNED TO THE 2006
 FBC PLEASE CORRECT TO THE 2004 FBC WITH 2006 AMENMENTS.
 ALSO INCLUDE THE 2004 FBC EXISTING BUILDING CODE WITH
 2006 AMENDMENTS. PROVIDE WHAT LEVEL OF ALTERATION IS
 BEING COMPLETED UNDER THIS PERMIT.
  
 3B) PLEASE SEE EXISTING BUILDING TYPE INDICATES A V,
 SPRINKLERED TABLE 503 WILL NOT ALLOW MERCANTILE NOR R2
 SIX FLOORS HIGH, PLEASE REVIEW TABLE 503 FOR MERCANTILE
 AND R2 RESIDENCE FORTHE MINIMUM BUILDING TYPE!
  
 4) PLEASE PROVIDE WIND DESIGN INFORMATION: 2004 FL.
 BLD CODE 1603.1.4 THE FOLLOWING INFORMATION RELATED TO
 WIND SHALL BE SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
 A)EXTERIOR FIRE RATED DOOR
 B) WALL LOUVER
 C) NEW PRE MANUFACTURED A/C STAND
  
 6)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-08-21 Cont ID  
Sent By dpalmer Date 2007-08-21 Time 11:07 Rev Time 0.00
Received By dpalmer Date 2007-08-21 Time 09:08 Sent To  
Notes
2007-08-21 11:08:55*** REDLINED PLANS.
  
 THE *EXISTING* SERVICE RISER AS SHOWN IS NOT CODE
 COMPLIANT FOR FIRE PUMP MAINS EQUIPMENT ETC.NO WORK
 IS BEING DONE ON EXISTING SERVICE MAINS OR EQUIPMENT.
 NEW WORK RELATED TO ELEVATOR EQUIPMENT ONLY.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-17 Cont ID  
Sent By dpalmer Date 2007-05-17 Time 08:53 Rev Time 0.00
Received By dpalmer Date 2007-05-17 Time 08:28 Sent To  
Notes
2007-05-17 08:54:03** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 * PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE PLANS MUST REFLECT CURRENT CODES IN
 EFFECT AND ADOPTED BY THE STATE IN THE SCOPE OF WORK AS
 SHOWN.
 PLEASE SEE THE PLANS CALL FOR A 2006 FBC WHICH AT THIS
 TIME, THERE IS NO 2006. PLEASE KNOW HOWEVER AT THIS
 TIME AND AS OF DECEMBER 8TH, 2006 THE STATE IS UNDER
 THE 2004 FBC W/2006 REVISIONS. THESE ARE ONLY REVISIONS
 TO THE 2004 FBC.
 PLEASE ALSO SEE THE PLANS INDICATE THE 2002 NEC WHICH
 WENT OUT FOR ALL PERMIT APPLICATIONS AFTER THIS SAME
 DATE. WE ARE UNDER THE 2005 NFPA-70. (NEC).
 PLEASE ALSO LIST THE FOLLOWING.
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY REQUEST TO SHOW HOW EQUIPMENT WILL BE
 INTERFACED WITH ANY EXISTING FIRE ALARM SYSTEM(S).
 PLEASE SEE NEC AND LS CODE WHICH REQUIRES
 DISCONNECTS/SHUNT OF EQUIPMENT IN EVENTS.
 PLEASE SEE 620.51, NFPA-72, ASME A-17.1-2004
  
 3) NOTE: PLEASE SEE PLANS MENTIONS WORK FOR ELEVATOR
 EQUIPMENT BY STATE, HOWEVER MANY OF THE ITEMS WHICH ARE
 NOT COVERED BY THE STATE AND IS PERMITTED BY THE
 ELECTRICAL CONTRACTOR AND THE LOCAL AHJ IS NOT SHOWN.
 PLEASE COMPLETE INFORMATION ON MOTORS/EQUIPMENT LOADS
 BEING INSTALLED.
 PLEASE SEE620.22 AS INFORMATION FOR THESE CIRCUITS
 COULD NOT BE LOCATED.
 PLEASE SEE THE SAME SECTIONS AND INDICATE THE
 FT-CANDLES AS REQUIRED.
 PLANS CALL FOR A 100AMP DISCONNECT FOR THE EQUIPMENT,
 HOWEVER NO INFORMATION WAS SHOWNON ELECTRICAL RISER,
 PANELS ETC FOR THIS.?
 PLEASE COMPLETE.
 215.5, 240.4, 310.16, ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 4) NOTE: PLEASE SEE 700.16,700.12, LS 101 7.8 AND 7.9
 AS AN EMERGENCY BATTERY BACK UP LIGHT OF SOME KIND WILL
 BE REQUIRED FOR THIS ROOM.
  
 5) NOTE: PLEASE SEE13-415.1.ABC.1.1, .1.2 AS LIGHTING
 CONTROL IS REQUIRED FOR ANY NEW INSTALLATIONS OF
 LIGHTING CONTROL.
  
 6) NOTE: PLEASE CLARIFY CIRCUITING ON PLANS FOR A/C
 SYSTEM AS SHOWN ON PANEL SCHEDULE.
 PLEASE ALSO SEE THAT BOTH UNITS DO NOT INDICATE ANY
 DISCONNECTS AS REQUIRED PER 440.11
 PLEASE SEE NO SERVICE GFI SHOWN FOR CU. 210.63, 210.8
  
 7) NOTE: PLEASE SEE THE VLAUE SHALL INCLUDE ALL LABOR,
 MATERIALS AND EQUIPMENT, EVNE IF ANY IS OWNER SUPPLIED.
 FBC 108.3
  
 ** PLEASE KNOW THAT AS SOME INFORMATION WAS NOT
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW FOR CODE COMPLIANCE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-08-28 Cont ID  
Sent By mawillia Date 2007-08-28 Time 16:50 Rev Time 0.00
Received By mawillia Date 2007-08-28 Time 16:32 Sent To  
Notes
2007-08-28 16:34:43*****APPROVED*****
  
 PLAN SHEET A1.1 STAMPED, INITIALED, AND DATED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-26 Cont ID  
Sent By mawillia Date 2007-06-26 Time 00:48 Rev Time 0.00
Received By mawillia Date 2007-06-25 Time 23:53 Sent To  
Notes
2007-06-26 00:45:00*****DENIED*****
  
  
 1.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.SEE SHEET S1 AND ME1
  
 2.ON SHEET A1.0 UNDER CODE COMPLIANCE, THE 2003
 EDITION OF NFPA 101 SHALL BE REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.THE ACCUMULATION OF COMBUSTIBLE WASTE MATERIALS,
 DUST, AND DEBRIS SHALL BE REMOVED FROM THE SITE AT THE
 END OF EACH SHIFT OR MORE FREQUENTLY AS NECESSARY FOR
 SAFE OPERATION.
  
 5.SPECIFY NEW WALL AND CEILING FINISH MATERIAL IN THE
 ELEVATOR EQUIPMENT ROOM AS CLASS A, CLASS B, OR CLASS
 C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE (ON THE PLANS) EACH ITEM WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-24 Cont ID  
Sent By adarroug Date 2008-01-24 Time 10:35 Rev Time 0.00
Received By adarroug Date 2008-01-24 Time 10:35 Sent To B
Notes
2008-01-24 10:35:48TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-28 Cont ID  
Sent By spalmer Date 2007-12-28 Time 10:42 Rev Time 0.00
Received By spalmer Date 2007-12-28 Time 10:42 Sent To B
Notes
2007-12-28 10:42:58TO JIM WITMERS DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-13 Cont ID  
Sent By adarroug Date 2007-12-13 Time 10:58 Rev Time 0.00
Received By adarroug Date 2007-12-13 Time 10:58 Sent To B
Notes
2007-12-13 10:58:30TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-30 Cont ID  
Sent By adarroug Date 2007-07-30 Time 10:24 Rev Time 0.00
Received By adarroug Date 2007-07-30 Time 10:24 Sent To  
Notes
2007-08-14 14:38:54TO "COMM" BD#7
2007-07-30 10:25:05WAITING FOR "COMM' BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-25 Cont ID  
Sent By mawillia Date 2007-06-25 Time 23:53 Rev Time 0.00
Received By mawillia Date 2007-05-03 Time 13:28 Sent To  
Notes
2007-05-14 14:34:21TO "COMM" BD#11
2007-05-03 13:28:26WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-08-15 Cont ID  
Sent By tgordon Date 2007-08-15 Time 16:06 Rev Time 0.25
Received By tgordon Date 2007-08-15 Time 16:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-21 Cont ID  
Sent By tgordon Date 2007-05-21 Time 13:29 Rev Time 0.25
Received By tgordon Date 2007-05-21 Time 13:29 Sent To  
Notes
2007-05-21 13:33:24*** DENIED ***
 1) THE ENGINEER W. BRUCE MILLER LICENSE EXPIRED
 2-28-07, PLEASE CORRECT.
  
 2) PLEASE SUBMIT PRODUCT APPROVAL FOR PER-ENGINEERED
 CONDENSER STANDS, SEE FS 553.842(1) AND FAC
 9B-72.010(31)(G).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-08-28 Cont ID  
Sent By mflis Date 2007-08-28 Time 09:44 Rev Time 0.00
Received By mflis Date 2007-08-28 Time 09:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2007-05-15 Cont ID  
Sent By mflis Date 2007-05-15 Time 15:48 Rev Time 0.00
Received By mflis Date 2007-05-15 Time 15:47 Sent To  
Notes
2007-05-15 15:48:38ZONING REVIEW: PASSED
  
 - -ELEVATOR MACHINE ROOM RENOVATIONS/REPAIR
  
 MATT FLIS - 822-1445