Plan Review Details - Permit 07041039
Plan Review Stops For Permit 07041039
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-19 Cont ID  
Sent By amorse Date 2007-05-19 Time 21:37 Rev Time 0.00
Received By amorse Date 2007-05-19 Time 21:37 Sent To PC
Notes
2007-05-19 21:49:24 
  
 DENIED
  
 1)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE.
 THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.
 WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED
  
 2)PER 106.1.3 FBC* THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR
 PLANS AND SPECIFICATIONS "NO WHITE OUT, PENCIL OR INK"
  
 3)PER 1609.6.1 THE SIMPLIFIED CALCULATION METHOD FOR
 WIND LOADS SHALL NOT BE USED TO DETERMINE WIND
 PRESSURES FOR BUILDINGS OVER 60 FT IN HEIGHT. PLEASE
 SUBMIT ENGINEERED CALCULATIONS. PROVIDE BUILDING
 HEIGHT, EXPOSURE CATEGORY C, AND ZONES THAT DOORS ARE
 LOCATED IN AND THEIR DESIGN PRESSURES.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716