Plan Review Details - Permit 07041017
Plan Review Stops For Permit 07041017
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-06-13 Cont ID  
Sent By shill Date 2007-06-13 Time 15:29 Rev Time 0.00
Received By shill Date 2007-06-13 Time 15:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-05-21 Cont ID  
Sent By btrobaug Date 2007-05-21 Time 10:36 Rev Time 0.33
Received By btrobaug Date 2007-05-21 Time 10:29 Sent To G
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-09-14 Cont ID  
Sent By mperson Date 2007-09-14 Time 08:24 Rev Time 0.00
Received By mperson Date 2007-09-14 Time 08:24 Sent To PC
Notes
2007-09-14 08:30:38REVISION: LAYOUT CHANGED AND REMOVED ALL EXISTING
 GALVANIZED PIPE FROM UNDERGROUND. DELETED ALL GAS
 APPLIANCES FROM HOUSE. ONLY GENERATOR ON EXISTING LP
 TANK.
  
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-07-02 Cont ID  
Sent By mperson Date 2007-07-02 Time 15:01 Rev Time 0.45
Received By mperson Date 2007-07-02 Time 15:01 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-05-24 Cont ID  
Sent By mperson Date 2007-05-24 Time 10:23 Rev Time 0.45
Received By mperson Date 2007-05-24 Time 10:23 Sent To B
Notes
2007-05-24 11:13:22DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE CORRESPONDING
 LENGTH INDICATED ON THE DRAWING. THIS INCLUDES ABOVE
 GROUND, UNDERGROUND AND EXISTING PIPING.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: PLEASE INDICATE THE ABOVE GROUND PIPING
 MATERIAL.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: NEED TO INDICATE THE EXISTING HOUSE BTU LOAD AS
 WELL AS THE PROPOSED GENERATOR.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: NEED TO INDICATE THE EXISTING PIPING
 CORRESPONDING LENGTHS TO VERIFY THIS.
  
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 LP GAS SPECIFY 10 PSI, 2 PSI, OR 11 INCH WC.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: PLEASE SUBMIT MANUFACTURER SHEETS OF SECOND STAGE
 REGULATOR TO THE PROPOSED GENERATOR INDICATING NAME OF
 MANUFACTURER, REGULATOR CAPACITY (LARGEST AMOUNT OF
 BTU'S SERVED BY REGULATOR), AND SHOW A LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL). SUBMIT
 MANUFACTURER INSTALLATION INSTRUCTIONS TO VERIFY SET
 BACKS TO STRUCTURES.
  
 7. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 NOTE: THIS INCLUDES EXISTING AS WELL AS PROPOSED
 TANKS.
  
 8. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 NOTE: THIS INCLUDES EXISTING AS WELL AS PROPOSED
 TANKS.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-28 Cont ID  
Sent By adarroug Date 2007-08-28 Time 13:32 Rev Time 0.00
Received By adarroug Date 2007-08-28 Time 13:32 Sent To G
Notes
2007-08-28 13:32:52TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-21 Cont ID  
Sent By adarroug Date 2007-06-21 Time 09:30 Rev Time 0.00
Received By adarroug Date 2007-06-21 Time 09:30 Sent To Z
Notes
2007-06-21 09:31:26TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-04 Cont ID  
Sent By adarroug Date 2007-05-04 Time 15:15 Rev Time 0.00
Received By adarroug Date 2007-05-04 Time 15:15 Sent To E
Notes
2007-05-04 15:15:54TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-13 Cont ID  
Sent By adarroug Date 2007-06-13 Time 09:29 Rev Time 0.00
Received By adarroug Date 2007-05-02 Time 13:33 Sent To  
Notes
2007-05-02 13:33:27TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-06-22 Cont ID  
Sent By tgordon Date 2007-06-22 Time 08:10 Rev Time 0.30
Received By tgordon Date 2007-06-22 Time 08:09 Sent To G
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-08 Cont ID  
Sent By tgordon Date 2007-05-08 Time 08:24 Rev Time 0.25
Received By tgordon Date 2007-05-08 Time 08:24 Sent To E
Notes
2007-05-08 08:35:50*** DENIED ***
 1) MANUFACTURER'S SPECIFICATION'S WERE SUBMITTED,
 PLEASE ALSO SUBMIT MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  
 2) PLEASE SHOW ON SURVEY, LOCATION OF GENERATOR, AND
 DISTANCE TO HOUSE, WINDOWS AND OTHER BUILDING OPENINGS
 WITHIN FIVE FEET.
  
 *** INFORMATIONAL: PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED EQUIPMENT POWERED BY
 INTERNAL COMBUSTION ENGINES SHALL BE INSTALLED IN
 ACCORDANCE WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES: 4.1.4ENGINES (GENERATORS)
 LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT FROM OPENINGS
 IN WALLS & AT LEAST 5 FT FROM STRUCTURES HAVING
 COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT REQUIRED
 WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE
 RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS
 CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE ENCLOSURE WILL
 NOT IGNITE COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS SHOULD NOT
 TERMINATE UNDER STRUCTURES OR WHERE THE EXHAUST MIGHT
 BE DRAWN INTO THE VENTILATION INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE
 TERMINATION POINT SHALL BE LOCATED AT LEAST 3 FT FROM
 THE ROOF STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL
 EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK,
 GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE, BUILDING, WINDOWS,
 DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES AROUND
 EQUIPMENT FOR SERVICING,AND PROVIDE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AT THE JOB-SITE FOR THE FIELD
 INSPECTOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-06-21 Cont ID  
Sent By choops Date 2007-06-21 Time 15:49 Rev Time 0.00
Received By choops Date 2007-06-21 Time 15:49 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-03 Cont ID  
Sent By choops Date 2007-05-03 Time 16:24 Rev Time 0.00
Received By choops Date 2007-05-03 Time 16:24 Sent To I
Notes
2007-05-03 16:26:42***FAILED***
  
  
 1) PLEASE INDICATE SCOPE OF WORK ON BOTH COPIES OF THE
 SURVEY: WITH DIMENSIONS OF WORK AND SETBACK DIMENSIONS
 FROM PROPERTY LINES.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720