| 2007-08-15 11:50:58 | BUILDING PLAN REVIEW |
| | PERMIT: 07040994 |
| | ADD: 4300 NFLAGLER DR |
| | CONT: MECHANICAL INDUSTRIAL SERVICES |
| | TEL: (813)247-2868 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATETHE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT.NOTE: 713.13(2) IF THE WORK DESCRIBED IN |
| | THE NOTICE OF COMMENCEMENT IS NOT ACTUALLYCOMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING THEREOF, |
| | SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)THE |
| | POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) COMPLIED. |
| | |
| | 4) 2ND REQUEST,DIGITAL DESIGN AND DRAFTING IS ACTING |
| | AS AN ENGINEER AND ARE NOT CERTIFIED OR LICENSED AS AN |
| | ENGINEER OR ENGINEERING BUSINESS IN ACCORDANCE WITH |
| | CHAPTER 471, |
| | FLORIDA STATUTE. PLEASE SEE DBPR CASENO. 03-0489. IT |
| | APPEARS THAT DIGITAL DESIGN IS PRACTICING ENGINEERING, |
| | IF THE FIRM WERE DIRECTLY ENGAGED BY THE ENGINEER THEY |
| | WOULD NOT NEED TO HAVE THEIR NAME ON THE HEADER STRIP, |
| | IT APPEARS THAT THEY ARE ADVERTISING THEMSELVES AS |
| | ENGINEERS. THIS WILL BE TURNED OVER TO THE STATE TO |
| | INVESTIGATE AS PER CONVERSATION WITH STATE INVESTIGATOR |
| | MR. JACK BEMESS. |
| | |
| | 5) 2ND REQUEST,LS & SS SERVIDES INC,IS ACTING AS AN |
| | ENGINEER AND ARE NOT CERTIFIED OR LICENSED AS AN |
| | ENGINEER OR ENGINEERING BUSINESS IN ACCORDANCE WITH |
| | CHAPTER 471,FLORIDA STATUTE. PLEASE SEE DBPR NO |
| | 03-0489 . ALL RESPONSE SHEET COMMENTS DO NOT INDICATE |
| | THAT THEY ARE THE DESIGN ENGIEENERS BUT LYLE |
| | SCHARENBURG OF LS & SS SERVICES INC. BOTH THE |
| | MECHANICAL AND BUILDING REVIEWER HAVE HAD |
| | MULTIPLE TELEPHONE CALLS WITH MR SCHARENBURG WHERE HE |
| | IMPLIED THAT THIS IS HIS DESIGN AND SEALED BY ENGINEER |
| | J. F. SHANNON. THE RESPONSE TO BUILDINGS COMMENT NUMBER |
| | (5 |
| | ) DOESN'T INDICATE THE PLANS WERE DESIGNED BUT SEALED |
| | BY THE ENGINEER OF RECORD. |
| | |
| | 6A)SEMI- COMPLIED, 106.1.2 ADDITIONAL INFORMATION IS |
| | REQUIRED TO BE ABLE TO DO AN ADEQUATE REVIEW,PLEASE |
| | PROVIDE:110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PROJECT WAS DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | |
| | 6B) THE DESIGN PROFESSIONAL HAS NOT COMMENTED ON THIS |
| | ISSUE, AGAIN LYLE SCHARENBERG OF LS & SS SERVES INC |
| | MAKES THE REBUTTAL NOT THE DESIGNER OF RECORD!!!!! THE |
| | REMAINDER OF THE REVIEW WILL USE THE FOLLOWING |
| | ASSUMPTIONS: |
| | NOTE: THIS REVIEW WILL BE COMPLETED WITH THE FOLLOWING |
| | ASSUMPTION, THE WOOD WORKING SHOP WILL BE CONSIDERED |
| | FACTORY-INDUSTRIAL F1 SINCE SECTION 306 OF THE BUILDING |
| | CODE DOES LIST MILLWORK (SASH & DOOR) AS AN F1 |
| | OCCUPANCY. |
| | |
| | THE NEXT ISSUE WILL BE HOW TO CLASSIFY THE SAWDUSST |
| | THAT IS CREATED WHEN WORK IS BEING COMPLETED. THE WOOD |
| | BEFORE IT IS CUT IS A MINOR HAZARD BUT WHEN SAWDUST IS |
| | CREATED, THE SAWDUST IS VERY COMBUSTIBLE AND CREATES A |
| | HIGH HAZARD OR H-2 OCCUPANCY. TABLE 307.7(1)IS FOR |
| | THE MAXIMUM ALLOWABLE QUANITIES OF MATERIAL ALLOWED PER |
| | CONTROL AREA, THAT POSES A PHYSICAL HAZARD. WHEN YOU |
| | SCAN THE TABLE THERE IS NO CATEGORY FOR COMBUSTIBLE |
| | DUST, THERE IS FOR COMBUSTIBLE FIBERS NOT COMBUSTIBLE |
| | DUST! PLACING THE COMBUSTIBLE DUST INTO A H-2 CATEGORY. |
| | SEE 415.7 GROUP H-2 |
| | |
| | 415.7.1 COMBUSTIBLE DUSTS, GRAIN PROCESSING AND |
| | STORAGE. |
| | THE PROVISIONS OF SECTIONS 415.7.1.1 THROUGH 415.7.1.5 |
| | SHALL APPLY TO BUILDINGS IN WHICH MATERIALS THAT |
| | PRODUCE COMBUSTIBLE DUSTS ARE STORED OR HANDLED. |
| | BUILDINGS THAT STORE OR HANDLE COMBUSTIBLE DUSTS SHALL |
| | COMPLY WITH THE APPLICABLE PROVISIONS OF NFPA 61, NFPA |
| | 120, NFPA 651, NFPA 654, NFPA 655, NFPA 664 AND NFPA |
| | 85, AND THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | WHEN YOU LOOK AT THE VARIOUS NFPA REQUIREMENTS ABOVE |
| | 664 IS THE STANDARD TO BE USED . NFPA 664 IS THE |
| | STANDARDFOR THE PREVENTION OF FIRE AND EXPLOSIONS IN |
| | WOOD PROCESSING FACILITIES 2007 EDITION. WE BELIEVE |
| | THAT THIS STILL CAN BE CLASSIFIED AS A F-1 FACTORY USE |
| | WITH ONE CONTROLED AREA THE WOOD SHOP AND THE DUST |
| | COLLECTION SYSTEM HAS TO TIED INTO |
| | OPERATION OF ANY EQUIPMENT THAT CREATES SAWDUST. THIS |
| | WOULDMAKE THE COLLECTION SYSTEM AND HOLDING TANK THE |
| | H-2 HAZARD ZONE. |
| | |
| | IN STUDYING 415.7.1 THE NFPA WHICH REFERS TO WOOD AND |
| | OR COMBUSTIBLE SAWDUST IS NFPA 664 AND IS TO BE |
| | FOLLOWED COMPLETELY. |
| | 4.4 DESIGNER AND INSTALLER QUALIFICATIONS. SYSTEMS THAT |
| | HANDLE COMBUSTIBLE PARTICLES SHALL BE DESIGNED BY AND |
| | INSTALLED UNDER THE SUPERVISION OF QUALIFIED ENGINEERS |
| | WHO ARE KNOWLEGABLE OF THESE SYSTEMS AND THEIR |
| | ASSOCIATED HAZARDS. PLEASE NOTE THAT THE ENGINEER OF |
| | RECORD STATES HE HAS DESIGNED THE STRUCTURE |
| | STRUCTURALLY TO THE 2004 FBC NOT THE MECHANICAL |
| | ASSPECTS OF THE SYSTEM. |
| | ATTACHED IS A COPY OF NFPA 664 TO FOLLOW IN THE DESIGN |
| | OF THE SYSTEM PLEASE COMPLY WITH ALL SECTION OF THIS |
| | STANDARD, INCLUSIVE OF CHAPTER 12. |
| | |
| | PLEASE PROVIDE INFORMATION ON THE BULK STORAGE TANK |
| | SIZE IN WIDTH DEPTH AND HEIGTH AS WELL AS CU FT |
| | |
| | PROVIDE THE EMPLOYEE TRAINING PROGRAM IN SECTION IN |
| | 11.1 AND 11.3. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |