Plan Review Details - Permit 07040976
Plan Review Stops For Permit 07040976
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-06-11 Cont ID  
Sent By mjacobs Date 2007-06-11 Time 10:24 Rev Time 0.00
Received By mjacobs Date 2007-06-06 Time 16:24 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-05-09 Cont ID  
Sent By mjacobs Date 2007-05-09 Time 14:49 Rev Time 0.00
Received By mjacobs Date 2007-05-09 Time 12:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-05-08 Cont ID  
Sent By dpalmer Date 2007-05-08 Time 15:31 Rev Time 0.00
Received By dpalmer Date 2007-05-08 Time 15:12 Sent To  
Notes
2007-05-08 15:32:11REVIEWED FOR NEW RECEPT BRANCH CIRCUIT ONLY.
 EXISTING SERVICE RISER NOT INLCUDED IN SCOPE OF WORK.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-06-08 Cont ID  
Sent By mawillia Date 2007-06-08 Time 17:38 Rev Time 0.00
Received By mawillia Date 2007-06-08 Time 17:21 Sent To  
Notes
2007-06-08 17:38:22*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEETS A-6.1, E-1, AND FP-1 WERE
 STAMPED, INITIALED, AND DATED.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-05-14 Cont ID  
Sent By mawillia Date 2007-05-14 Time 11:46 Rev Time 0.00
Received By mawillia Date 2007-05-14 Time 11:26 Sent To  
Notes
2007-05-14 11:46:09*****DENIED*****
  
  
 1.THE 2003 EDITION OF NFPA 101 - LIFE SAFETY CODE -
 SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 4.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING MATERIALS & SUPPLIES SHALL NOT INTERFERE
 OR HINDER ACCESS TO OR EGRESS FROM THE SAID FLOOR OR
 THE BUILING.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-22 Cont ID  
Sent By adarroug Date 2007-05-22 Time 11:23 Rev Time 0.00
Received By adarroug Date 2007-05-22 Time 11:22 Sent To  
Notes
2007-06-01 08:47:00TO "BOB"#9
2007-05-22 11:23:13WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-14 Cont ID  
Sent By mawillia Date 2007-05-14 Time 11:26 Rev Time 0.00
Received By mawillia Date 2007-05-02 Time 15:40 Sent To  
Notes
2007-05-02 15:43:23TO "BOB"#13

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-06-01 Cont ID  
Sent By tgordon Date 2007-06-01 Time 11:59 Rev Time 0.30
Received By tgordon Date 2007-06-01 Time 11:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-03 Cont ID  
Sent By tgordon Date 2007-05-03 Time 09:06 Rev Time 0.30
Received By tgordon Date 2007-05-03 Time 09:06 Sent To  
Notes
2007-05-03 09:10:28*** DENIED ***
 1) MECHANICAL PLANS SHOW EXISTING OPEN OFFICE #803 HAS
 1,200 CFM'S. OF SUPPLY AIR AND ONLY 600 CFM'S. OF
 RETURN AIR, SEE 2004 FBC/M 601.4 BALANCED RETURN AIR,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.