Plan Review Details - Permit 07040967
Plan Review Stops For Permit 07040967
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-06-26 Cont ID  
Sent By mjacobs Date 2007-06-26 Time 08:54 Rev Time 0.00
Received By mjacobs Date 2007-06-26 Time 08:35 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-06-22 Cont ID  
Sent By mjacobs Date 2007-06-22 Time 14:59 Rev Time 0.00
Received By mjacobs Date 2007-06-22 Time 14:01 Sent To  
Notes
2007-06-22 14:52:23PROVISOR:
  
 FBC. 11-4.24.5A CLEAR FLOOR SPACE AT LEAST 30 INCHES
 BY 48 INCHES COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD APPROACH.
 THE CLEAR FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE
 AND SHALL EXTEND A MAXIMUM OF 19 INCHES UNDERNEATH TO
 SINK. (SEE FIGURE 32)

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-10 Cont ID  
Sent By mjacobs Date 2007-05-10 Time 10:36 Rev Time 0.00
Received By mjacobs Date 2007-05-10 Time 06:53 Sent To PC
Notes
2007-05-10 10:36:50BUILDING PLAN REVIEW
 PERMIT: 07040967
 ADD: 330 CLEMATIS STREET
 CONT: MJS CONSTRUCTION INC.
 TEL: (561)615-9348
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 4)THE CODE SECTIONS ABOUT TERMITE PROTECTION IS FROM
 THE 2001 FBC. SEE THE 2004 FBC FOR THE NEW CODE
 SECTIONS AND CHANGE ACCORDINGLY.
  
 5)DEMOLITION PLAN NOTES ON PAGE A200 HAVE TWO #6 WITH
 DIFFERENT INFORMATION.THE DRAWINGS SHOWS A #7 SYMBOL,
 BUT THERE IS NO 7 IN THE DEMOLITION NOTES.
  
 6)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW.FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*.
  
 7)SEE FBC. CHAPTER 22 FOR STEEL AND METAL
 REQUIREMENTS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-20 Cont ID  
Sent By dpalmer Date 2007-06-20 Time 14:32 Rev Time 0.00
Received By dpalmer Date 2007-06-20 Time 14:25 Sent To  
Notes
2007-06-20 14:33:01MAX TIME ON OS REDLINED 30MINS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-01 Cont ID  
Sent By dpalmer Date 2007-05-01 Time 09:36 Rev Time 0.00
Received By dpalmer Date 2007-05-01 Time 09:35 Sent To  
Notes
2007-05-01 09:37:28** UNSAT **
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
  
 2) NOTE: PLEASE SEE 2004 FBC CHAPTER 13 W/ 2006
 REVISIONS.
 PLEASE SEE MISSING LIGHTING CONTROLS PER
 13-415.1.ABC.1.1, .1.2.FOR NEW LIGHTING CONTROL
 LOCATIONS.
 PLEASE SEE MISSING INFORMATION FOR NEW LIGHTING
 FIXTURES TO BE INSTALLED.
 PLEASE SEE 13-415.1.ABC.3
 PLEASE SEE 13-415.2 FOR LIMITS OF LIGHTING IN
 SPACE(S).
  
 3) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 AS REQUIRED PER FAC 61G1-16.004.
 PLEASE SEE THE MISSING PRINTED NAME AND PRINTED LICENSE
 NUMBER FOR THE ARCHITECT OF RECORD.
 ** PLEASE BE SURE ALL RAISED SEALS ARE CLEAR AND
 VISIBLE WITH ALL INFORMATION ON SAID SEALS. MANY SEALS
 ARE VERY FAINT AND NOT CLEARLY READABLE.
 FS 481.221
  
 4) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS FOR
 NEW AND CORRELATE WITH A PANEL SCHEDULE TO BE
 SUBMITTED. PLEASE INDICATE ANY INCREASE OF LOADS DUE TO
 THE NUMBER OF ADDED LIGHTS OR RECEPTACLE LOADS PER
 220.12,220.14,220.42, 220.44 ETC.
 PLEASE SEE 408.4 WHICH REQUIRES THE CIRCUITING TO BE
 SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY FEED.
 PLEASE KNOW THESE CAN BE DONE BY THE ROOM NAME OR
 NUMERICAL DESIGNATION.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN FROM THE
 CODE.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 5) NOTE: PLEASE CLARIFY TWO NOTES #6 ON SHEET A200.
 THIS APPEARS TO BE A MISPRINT FOR NOTE #7.
 FBC 106.1.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-06-22 Cont ID  
Sent By mawillia Date 2007-06-22 Time 16:05 Rev Time 0.00
Received By mawillia Date 2007-06-22 Time 15:49 Sent To  
Notes
2007-06-22 16:03:01*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED;PLAN SHEETS A500 AND A700 WERE STAMPED,
 INITIALED, AND DATED.
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-05-14 Cont ID  
Sent By mawillia Date 2007-05-14 Time 12:16 Rev Time 0.00
Received By mawillia Date 2007-05-14 Time 11:56 Sent To  
Notes
2007-05-14 12:16:13*****DENIED*****
  
  
 1.THE COMPLETE/CORRECT ADDRESS OF WHERE THE SCOPE OF
 WORK IS TO BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF
 EACH SUBMITTED PLAN SHEET.EXPLAIN THE DIFFERENCE
 BETWEEN SUITE 201 AND THAT OF 2-A-A.
  
 2.THE 2003 EDITION OF NFPA 101 - LIFE SAFETY CODE -
 SHALL BE REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.PLEASE BE ADVISED THAT INTERIOR WALL AND CEILING
 FINISH MATERIAL SHALL BE CLASS A OR CLASS B IN EXITS
 AND IN EXIT ACCESS CORRIDORS.CLASS C IS INDICATED ON
 SHEET A500.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-18 Cont ID  
Sent By adarroug Date 2007-06-18 Time 11:47 Rev Time 0.00
Received By adarroug Date 2007-06-18 Time 11:47 Sent To  
Notes
2007-06-18 11:49:23TO "BOB"#9

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-14 Cont ID  
Sent By mawillia Date 2007-05-14 Time 11:56 Rev Time 0.00
Received By mawillia Date 2007-04-27 Time 11:27 Sent To  
Notes
2007-04-27 11:29:13TO "BOB"#6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-06-21 Cont ID  
Sent By tgordon Date 2007-06-21 Time 09:26 Rev Time 0.25
Received By tgordon Date 2007-06-21 Time 09:26 Sent To  
Notes
***NONE***