Plan Review Details - Permit 07040965
Plan Review Stops For Permit 07040965
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-08-28 Cont ID  
Sent By shill Date 2007-08-28 Time 08:56 Rev Time 0.00
Received By shill Date 2007-08-28 Time 08:55 Sent To  
Notes
2007-08-28 08:57:34***INFORMATIONAL ONLY***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PLANS ARE BUILDING CODE COMPLIANT AS DRAWN.
 HOWEVER, WHEN ADDRESSING ZONING COMMENTS, PLEASE SEE
 FBC3202.2, ENCROACHMENTS INTO THE PUBLIC WAY ARE
 PROHIBITED (GATE CANNOT SWING OVER THE PROPERTY LINE).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-06-05 Cont ID  
Sent By shill Date 2007-06-05 Time 14:39 Rev Time 0.00
Received By shill Date 2007-06-05 Time 14:39 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2008-03-07 Cont ID  
Sent By rchokshi Date 2008-03-07 Time 14:05 Rev Time 0.00
Received By rchokshi Date 2008-03-07 Time 14:05 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-08-20 Cont ID  
Sent By rchokshi Date 2007-08-20 Time 11:39 Rev Time 0.00
Received By rchokshi Date 2007-08-20 Time 11:39 Sent To  
Notes
2007-08-20 11:38:46**** FAILED ****
  
 YOU DID NOT RESPOND TO OUR COMMENTS WE MADE IN REV 1,
 OF 05/09/07, THEREFORE WEREPEAT THOSE COMMENTS
 AGAIN.
  
 1. PLEASE SHOW ON DRAWING THE LOCATION WITH THE MINIMUM
 DIMENSIONS OF THE DUMPSTER PAD,APPROVED BY THE CITY
 2. MUST MEET MINIMUM LENGTH,WIDTH, & HEIGHT PER CITY
 STANDARDS.
 ADUMPSTER SKETCH WITH MINIMUM DIMENSION ENCLOSED
 FOR YOUR USE.
 IF YOU CAN NOT MEET MINIMUM DIMENSIONS, NEED A
 LETTER FROM SANITATION DEPT.
 3.DUMPSTER LOCATIONMUST BE ACCESSIBLE TO CITY PICK UP
 TRUCK FOR LOADIN/UNLOADING DUMPSTER.
  
 PLEASE RESPOND ABOVE COMMENTSIN DETAIL TO EXPEDITE
 YOUR PERMIT
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-05-09 Cont ID  
Sent By rchokshi Date 2007-05-09 Time 11:34 Rev Time 0.00
Received By rchokshi Date 2007-05-09 Time 11:31 Sent To  
Notes
2007-05-09 11:34:19PLEASE PROVIDE PLANS SHOWING LOCATION OF THE DUMPSTER,
 DETAILS,ETC
 MUST BE ACCESSIBLE TO CITY'S PICK UP TRUCK,
  
 RASIK CHOKSHI 805-6723

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-03-03 Cont ID  
Sent By adarroug Date 2008-03-03 Time 11:08 Rev Time 0.00
Received By adarroug Date 2008-03-03 Time 11:08 Sent To Z
Notes
2008-03-03 11:08:29TO "Z" BOX/RESUB--NEW SHEETS FOR "BLDG"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-16 Cont ID  
Sent By adarroug Date 2007-08-16 Time 10:30 Rev Time 0.00
Received By adarroug Date 2007-08-16 Time 10:30 Sent To Z
Notes
2007-08-16 10:31:04TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-09 Cont ID  
Sent By adarroug Date 2007-05-09 Time 12:55 Rev Time 0.00
Received By adarroug Date 2007-05-09 Time 12:55 Sent To B
Notes
2007-05-09 12:56:02TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-30 Cont ID  
Sent By adarroug Date 2007-04-30 Time 14:21 Rev Time 0.00
Received By adarroug Date 2007-04-30 Time 14:21 Sent To ENG
Notes
2007-04-30 14:21:36TO "ENG" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-05 Cont ID  
Sent By shill Date 2007-06-05 Time 14:40 Rev Time 0.00
Received By shill Date 2007-04-27 Time 11:30 Sent To  
Notes
2007-04-27 11:31:02TO "Z" BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2008-03-04 Cont ID  
Sent By choops Date 2008-03-04 Time 08:54 Rev Time 0.00
Received By choops Date 2008-03-04 Time 08:54 Sent To ENG
Notes
2008-03-04 08:58:16***APPROVED - RESUB #2***
  
 PROVISO:
 1)MUST BE LOCATED A MINIMUM OF 5' FROM THE PROPERTY
 LINES.
 2)LOCATION AS APPROVED BY THE CITY'S ENGINEERING
 DEPT.
  
  
  
  
 SENT TO "ENG" - RC

Review Stop Z ZONING
Rev No 2 Status F Date 2007-08-17 Cont ID  
Sent By choops Date 2007-08-17 Time 08:16 Rev Time 0.00
Received By choops Date 2007-08-17 Time 08:15 Sent To ENG
Notes
2007-08-17 08:19:05***FAILED******RESUB #1***
  
  
 REPEAT COMMENTS:
  
 1)PLEASE PROVIDE TWO (2) COPIES OF AN UPDATED SURVEY
 (WITHING THE LAST YEAR) SHOWING ALL DIMENSIONS: FROM
 PROPERTY LINES TO PROPOSED DUMPSTER PAD, DIMENSIONS OF
 DUMPSTER PAD, ETC... (WITH A PERMANENT UTENSIL)
  
 2)PUBLIC UTILITIES MUST APPROVE LOCATION OF DUMPSTER
 (561)494-1040
  
 3)LANDSCAPING TO BE SHOWN.MUST PROVIDE APPROPRIATE
 SCREENING AS PER THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS SECTION 94-444(B):
 OUTDOOR STORAGE FOR NONRESIDENTIAL AND MULTIFAMILY
 USES; STORAGE AND DISPOSAL FACILITIES.OUTDOOR
 INCINERATORS, GARBAGE OR TRASH RECEPTACLES, FUEL OIL OR
 PROPANE TANKS, AND STORAGE RACKS SHALL NOT BE PERMITTED
 UNLESS APPROPRIATE SCREENING IS PROVIDED. SCREENING
 SHALL BE CONSTRUCTED OF BRICK, DECORATIVE CONCRETE,
 OTHER DECORATIVE MASONRY, OR COMPARABLY DURABLE WOOD
 AND STEEL. WALLS SHALL BE LANDSCAPED WITH SHRUBS AND
 HEDGES PLANTED AT TWO-FOOT INTERVALS. A FOUR-SIDED
 ENCLOSURE WITH AN OBSCURING GATE MAY BE REQUIRED AS A
 CONDITION FOR SITE PLAN APPROVAL. PLANS FOR THE LAYOUT
 OF TRASH RECEPTACLESSHALL BE IN ACCORDANCE WITH THE
 MINIMUM REQUIREMENTS SET FORTH IN FIGURE XIV-3. THE
 PROVISIONS OF THIS SECTION SHALL NOT APPLY TO LITTER
 CONTAINERS PROVIDED FOR THE CONVENIENCE OF PEDESTRIANS.
 ALL AREAS FOR THE STORAGE AND DISPOSAL OF TRASH AND
 GARBAGE SHALL BE PAVED WITH CONCRETE SURFACE AS
 REQUIRED BY THE CITY DEPARTMENT OF ENGINEERING AND
 PUBLIC WORKS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720
  

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-30 Cont ID  
Sent By choops Date 2007-04-30 Time 13:50 Rev Time 0.00
Received By choops Date 2007-04-30 Time 13:49 Sent To I
Notes
2007-04-30 14:03:45***FAILED***
  
  
 1) PLEASE PROVIDE (2) COPIES OF AN UPDATED SURVEY
 (WITHING THE LAST YEAR) SHOWING ALL DIMENSIONS: FROM
 PROPERTY LINES TO PROPOSED DUMPSTER PAD, DIMENSIONS OF
 DUMPSTER PAD, ETC...
  
 2) PUBLIC UTILITIES MUST APPROVE LOCATION OF DUMPSTER
 (561)494-1040
  
 3) MUST PROVIDE APPROPRIATE SCREENING AS PER THE CITY
 OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS SECTION 94-444(B):OUTDOOR STORAGE FOR
 NONRESIDENTIAL AND MULTIFAMILY USES; STORAGE AND
 DISPOSAL FACILITIES.OUTDOOR INCINERATORS, GARBAGE OR
 TRASH RECEPTACLES, FUEL OIL OR PROPANE TANKS, AND
 STORAGE RACKS SHALL NOT BE PERMITTED UNLESS APPROPRIATE
 SCREENING IS PROVIDED. SCREENING SHALL BE CONSTRUCTED
 OF BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE
 MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL. WALLS
 SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT
 TWO-FOOT INTERVALS. A FOUR-SIDED ENCLOSURE WITH AN
 OBSCURING GATE MAY BE REQUIRED AS A CONDITION FOR SITE
 PLAN APPROVAL. PLANS FOR THE LAYOUT OF TRASH
 RECEPTACLESSHALL BE IN ACCORDANCE WITH THE MINIMUM
 REQUIREMENTS SET FORTH IN FIGURE XIV-3. THE PROVISIONS
 OF THIS SECTION SHALL NOT APPLY TO LITTER CONTAINERS
 PROVIDED FOR THE CONVENIENCE OF PEDESTRIANS. ALL AREAS
 FOR THE STORAGE AND DISPOSAL OF TRASH AND GARBAGE SHALL
 BE PAVED WITH CONCRETE SURFACE AS REQUIRED BY THE CITY
 DEPARTMENT OF ENGINEERING AND PUBLIC WORKS.
  
 4) DUMPSTER MUST NOT TAKE UP REQUIRED PARKING.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720