Plan Review Details - Permit 07040908
Plan Review Stops For Permit 07040908
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-07-21 Cont ID  
Sent By lmartine Date 2008-07-21 Time 09:16 Rev Time 0.00
Received By lmartine Date 2008-07-18 Time 16:57 Sent To  
Notes
2008-07-21 09:21:37#2 FROM PREVIOUS REVIEW, IMPACT FEES ARE STILL
 REQUIRED.
  
 #3, COMPLIED
  
 #4, COMPLIED
  
 #5 COMPLIED
  
 #6 COMPLIED
  
  
  
  
 THANK YOU,
 LUIS MARTINEZ
 561-805-6710
2008-07-18 17:10:22REVISION COMMENTS
  
  
 #1 FROM PREVIOUS REVIEW RESPONCE IS NOT APPROVED.
 PANDULA'S OFFICE SHALL SUBMIT FORMAL NOTORIZED LETTER
 TAKING FULL RESPONSIBILITY FROM PRINCIPLE DESIGN AND
 DEVELOPMENT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-06-09 Cont ID  
Sent By lmartine Date 2008-06-09 Time 12:37 Rev Time 0.00
Received By lmartine Date 2008-06-09 Time 10:13 Sent To Z
Notes
2008-06-09 12:37:03BUILDING REVISION COMMENTS
  
  
  
  
 1)
 PROVIDE CERTIFIED LETTER FROM NEW DESIGNERS (ARCHITECTS
 AND ENGINEERS) TAKING RESPONSIBILITY FOR THE ORIGINAL
 DESIGNERS WORK.
  
 2)
 SUBMIT PLANS TO PALM BEACH COUNTY IMPACT FEE OFFICE
 FOR REVIEW AND PROVIDE COPY OF RECEIPT.
  
 3)
 DOES THIS REVISION INCLUDE THE BREAKFAST ROOM, KITCHEN
 OR BOTH.
  
 4)
 SHEET A-3, EXPLAIN NEW 2-STORY ADDITION, NEW BALUSTERS
 AND RE-BUILDING THE CORNICES NOTES.
  
 5)
 PROVIDE FINISH FLOOR ELEVATION, MINIMUM ELEVATION
 REQUIRED IS 7.5 FOR A-5 FLOOD ZONE.
  
 6)
 IDENTIFY DOOR SCHEDULE PAGE, A__ WHAT ?
  
  
  
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-28 Cont ID  
Sent By lmartine Date 2008-04-28 Time 13:29 Rev Time 0.00
Received By lmartine Date 2008-04-28 Time 13:19 Sent To  
Notes
2008-04-28 13:26:42REVISION FOR ENERGY CALCULATIONS
  
  
  
  
 CANNOT REVIEW FOR ENERGY CALCULATIONS WITHOUT FIRST
 OBTAINING A MECHANICAL PERMIT FOR THE INSTALLATION OF
 YOUR SYSTEM.
  
  
  
  
  
 L.MARTINEZ
 805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-05-17 Cont ID  
Sent By lmartine Date 2007-05-17 Time 14:36 Rev Time 0.00
Received By lmartine Date 2007-05-17 Time 14:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-06-27 Cont ID  
Sent By dpalmer Date 2008-06-27 Time 13:40 Rev Time 0.00
Received By dpalmer Date 2008-06-27 Time 13:40 Sent To M
Notes
2008-06-27 13:40:20** DENIED REVISION **
  
 ** ELECTRICAL RISER HAS NOW BEEN COMPLETELY REVISED
 ONCE AGAIN.
 ** PLANS ARE COMING BACK FOR COMMENTS FROM OTHER
 TRADES.
  
 ** GENERATOR IS NOT PART OF THE ELECTRICAL REVIEW.
 NIC.
  
 1) NOTE: RISER SHOWS NEW ATS ON THE LINE SIDE OF THE
 MDP WHICH IS OK, HOWEVER THE SPECS SUBMITTED ARE NOT
 FOR A SERVICE ENTRANCE RATED TRANSFER SWITCH.
 230.70,230.76,230.76, 110.3, 90.7
 FBC 106.1.1, 106.1.2 FOR COORDINATION, CLARITY AND
 ADDITIONAL INFORMATION.
  
 2) NOTE: PLEASE SEE RISER SHOWS MDP AS MLO (MAIN LUG
 ONLY) YET THEMDP ON PANEL SCHEDULE SHOWS THIS
 CONTAINING A MAIN.
 230.70, 408.4, )225.31-225.39
 FBC 106.1.1, 106.1.2 FOR CLARITY, ADDITIONAL
 INFORMATION AND COORDINATION OF PLANS.
  
 3) NOTE: PLEASE SEE NEW STEAM GENERATOR WHICH IS SHOWN
 AS A 6KW LOAD ON A 1-POLE 20AMP CIRCUIT.
 PLEASE ADJUST.
 310.16, 240.4 ETC
  
 4) NOTE: PLEASE EXPLAIN NEW SHEET E-3.1 WHICH SHOWS
 SEVERAL NEW DETAILS FOR THIS PROJECT. PLEASE KNOW IF
 THESE DETAILS INCLUDING NEW GROUND BAR IS GOING TO BE
 USED THIS WOULD BE DIFFERENT FROM THE RISER GROUNDING
 ELECTRODE SYSTEM.
 THIS WOULD ALSO REQUIRE OTHER GROUNDING ELECTRODE
 METHODS. ARE ALL DETAILS ON THIS SHEET INTENDED?
 PLEASE COORDINATE.
 250.50
 FBC 106.1.1 FOR CLARITY.
  
 ONCE AGAINIF THERE ARE ANY QUESTIONS OR COMMENTS
 PLEASE CALL.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-06-03 Cont ID  
Sent By dpalmer Date 2008-06-03 Time 10:53 Rev Time 0.00
Received By dpalmer Date 2008-06-03 Time 10:53 Sent To B
Notes
2008-06-03 10:54:06** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS ARE
 STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE: AS THE ORIGINAL PERMIT APPLIED AS 06040626 DID
 NOT CONTAIN SUB PERMITS, INSPECTIONS FOR MEP AND DID
 NOT OBTAIN FINAL INSPECTIONS, PLANS MUST GO BACK TO
 ZONING FOR REVIEW AND STAMPING. THERE ARE SOME ITEMS ON
 PLANS CHANGED WHICH WERE NOT ON ORIGINAL PLANS STAMPED
 BY ZONING.
 ALL REVISED PLANS MUST ALSO CONTAIN HISTORIC REVIEW AND
 STAMPS. PLANS WILL BE ROUTED TO ZONING.
  
 2) NOTE: AS STATED ON PREVIOUS REVIEW THE GENERATOR WAS
 NOT INCLUDED ON ORIGINAL PLANS AND NEEDS TO BE DONE
 UNDER A SEPARATE PERMIT. THE ATS MAY BE INCLUDED WITH
 ELECTRICAL SERVICE HOWEVER PLEASE SEE THE ATS MUST MEET
 THE FOLLOWING.
 PLEASE SEE THE SIZE IS STILL SHOWN AS 260AMPS WHICH IS
 NOT A STANDARD RECOGNIZED IN THE NEC 240.6.
 110.3, 90.7.
  
 3) NOTE: PLEASE KNOW DISCONNECTING MEANS PER
 225.31-225.39 SHALL BE INSTALLED. BASED ON PLANS THERE
 IS NO DISCONNECTING MEANS FOR FEEDERS FROM GENERATOR AT
 MAIN HOUSE.
 PLEASE KNOW AS SHOWN THIS DOES NOT APPEAR TO MEET THE
 EXCEPTION IN 702.11.
 THIS ONLY NEEDS TO BE A DISCONNECT RATED FOR LOAD
 SERVED AND NOT A DISCONNECT WITH OVER CURRENT
 PROTECTION.
  
 4) NOTE: PLEASE SEE ALL RECEPTACLES SERVING KITCHEN
 COUNTER SPACE ARE REQUIRED TO BE GFI/GFI PROTECTED PER
 210.8A6. THIS WOULD INCLUDE KITCHEN ISLAND. THIS CAN BE
 REDLINED IF ONLY COMMENT REMAINING OR IF PAGE DOES NOT
 NEED TO BE REVISED FOR ANY OTHER COMMENTS.
  
 5) NOTE: PLEASE SEE ELECTRICAL RISER IS SHOWING AN
 *EQUIPMENT GROUNDING CONDUCTOR* BEFORE THE FIRST MEANS
 OF DISCONNECT AND BEFORE FPL METER WHICH IS NOT
 PERMITTED.
 PLEASE SEE 250.6, 250.24
 ** EQUIPMENT GROUNDING CONDUCTORS ARE ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 6) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.52 AS
 1500VA SHALL BE FIGURE FOR EACH OF THE SMALL APPLIANCE
 CIRCUITS.
 THERE ARE A GREATER NUMBER OF SMALL APPLIANCE CIRCUITS
 ON PANEL SCHEDULES THAN SHOWN ON LOAD CALCULATIONS.
  
 7) NOTE: PLEASE SEE 408.4 AS THE PANEL SCHEDULE SHALL
 BE DETAILED FOR CIRCUITS IN WHICH THEY FEED. THIS WILL
 AFFECT THE NOTE #6 ABOVE AS CIRCUIT #1 IS ACTUALLY A
 REFRIGERATOR.
 PLEASE SEE THE FOLLOWING TEXT EXTRACTED FROM THE NEC.
 SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.
  
 8) NOTE: PLEASE SUBMIT THE LOAD CALCULATIONS ON EACH
 PANEL. PANELS ARE SHOWN AS 400AMP AND NOW SERVICE WHICH
 WAS PREVIOUSLY 400AMPS IS NOW 250AMPS. HOWEVER FEEDERS
 ARE STILL SHOWN FOR 400AMPS?
 EACH PANEL NOTES TO SEE LOAD CALCULATIONS FOR LOADS ON
 PANELS HOWEVER BASED ON THE LOADS SHOWN ON SHEET ONLY
 THE LOAD FOR ENTIRE SERVICE IS SHOWN.
 PLEASE SUBMIT AND COORDINATE.
 220, 215.5, 310.16, 240.4 ETC
 FBC 106.1.2 FOR COORDINATION AND ADDITIONAL
 INFORMATION.
  
 9) NOTE: PLEASE SEE THE PANEL *A* SHOWS A AHU/CU #3,
 HOWEVER SO DOES PANEL *B*.
 PLANS SHOW FOUR SYSTEMS.
 PLEASE SEE PLANS ON E-1.1 AS BOTH THE CU#1 AND CU#4 ARE
 SHOWN ON SAME CIRCUITS A-33/35. THIS IS NOT POSSIBLE.
 PLEASE COORDINATE. 408.4
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE ELEVATOR SHOWS A 10KW LOAD ON A
 30AMP CIRCUIT. THIS CAN NOT BE POSSIBLE AS 10KW EXCEEDS
 THE RATING OF THE 30AMP CIRCUIT.
 310.16, 240.4 ETC
 PLEASE VERIFY LOAD ON ELEVATOR.
  
 11) NOTE: PLEASE SEE 110.26 AS NOT ALL THE CU
 DISCONNECT MEET MINIMUM CLEARANCES.
  
 12) NOTE: PLEASE KNOW *GATES* ARE NOT INCLUDED IN SCOPE
 OF WORK.
  
 13) NOTE: PLEASE SEE AS NOTED ABOVE IN NOTE#9 PLEASE
 COORDINATE ALL CIRCUITING ON PLANS WITH THAT OF THE
 CIRCUITS ON PANEL SCHEDULES.
 FBC 106.3.5.4, 106.1.2, NEC 408.4.
 THE FEW NOTED ABOVE IS NOT AN EXHAUSTED LIST AND ONLY
 REFERENCE A FEW FOR EXAMPLES.
  
 14) NOTE: PLEASE KNOW AS NOTED IN PREVIOUS REVIEW THE
 LOCATIONS OF THE FIXTURES IN CLOSETS DO NOT APPEAR TO
 MEET 410.8 WITH THE MINIMUM SHELVING DISTANCES GIVEN BY
 THE CODE. THE PLANS NOTE ON WALL ABOVE DOOR OR ON
 CEILINGS.THERE MAY BE THE MINIMUM NEEDED PER CODE FOR
 LOCATIONS ABOVE DOOR HOWEVER THE LOCATIONS ON CEILINGS
 FOR SOME OF THESE DO NOT APPEAR THIS WILL MEET CODE.
 THE PLANS ALSO CALL FOR THE FIXTURE TO BE CHOSEN BY
 OWNER/ARCHITECT HOWEVER THE MINIMUM SHALL BE SHOWN ON
 PLANS AT THIS TIME FOR THE TYPE OF FIXTURES TO COMPLY
 WITH MINIMUM SAFETY AND FIRE CONCERNS.
 THIS IS A FIRE/ LIFE SAFETY HAZARD AND ONE REASON MANY
 FIRES ARE STARTED IN CLOSETS AND STORAGE AREAS WHICH
 EASILY IGNITABLE MATERIALS ARE LOCATED.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-04-04 Cont ID  
Sent By dpalmer Date 2008-04-04 Time 17:32 Rev Time 0.00
Received By dpalmer Date 2008-04-04 Time 17:32 Sent To PC
Notes
2008-04-04 17:32:25** DENIED **
  
 1) NOTE: PLEASE SEE THAT COMPLETE PLANS INCLUDING PLANS
 FOR SITE AND SURVEY WILL BE REQUIRED TO BE SUBMITTED.
 NO GENERATOR WAS ON ORIGINAL PLANS WHICH ARE NOW
 CLOSED.
 PLEASE SEE THAT THE SUBMITTED PLANS FOR *STRUCTURAL
 ONLY SCOPE OF WORK* NEEDS TO INCLUDE ALL WORK WHICH DID
 NOT RECEIVE FINALS UNDER ORIGINAL APPLIED PERMIT
 06040626. THIS WILL INCLUDE THE ADDITION TO THE
 EXISTING DWELLING UNDER FIRE DAMAGE REPAIR ETC.
 THE NEW GENERATOR/ATS WAS NEVER PERMITTED OR APPLIED
 FOR.
  
 ** THERE WAS NEVER ANY ROUGH ELECTRICAL INSPECTION ON
 THE PREVIOUS ELECTRICAL PERMIT WHICH HAS EXPIRED.
  
 2) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK WHICH IS NOW BEING INCLUDED TO PREVIOUS APPLIED
 SCOPE OF WORK NOT COMPLETED NEEDS TO BE ADJUSTED.
 THE VALUE FOR ALL LABOR, MATERIALS EQUIPMENT ETC NEEDS
 TO BE INCLUDED. IF THE GENERATOR IS GOING TO BE UNDER
 THE SCOPE OF WORK THEN PLEASE KNOW VALUE SHALL INCLUDE
 THIS AS APPLIED VALUE.
 FBC 108.3
  
 3) NOTE: PLEASE SEE THAT SOME ITEMS WHICH ARE SHOWN AS
 EXISTING ON PLANS NEEDS TO BE SHOWN AS NEW AS THESE
 RECORD SET OF PLANS IS TO COMPLETE SCOPE OF WORK NEVER
 COMPLETED. THE NEW CONTRACTOR AND RECORD PLANS NEEDS TO
 SHOWS THESE.
 FOR EXAMPLE:
 OFFICE, ADDITION, ETC
 FBC 106.3.5.4
  
 4) NOTE: PLEASE SEE THERE ARE SEVERAL LIGHT FIXTURES
 MISSING FOR ROOMS AND OUTDOOR LOCATIONS WHICH NEED
 FIXTURES PER 210.70, LS 101 7.8.
 MOST ARE SHOWN AS J-BOXES.
  
 5) NOTE: PLEASE SEE THE LOAD CALCULATIONS STATE A
 250AMP SERVICE YET RISER SHOWS 400AMPS.
 FBC 106.1.2 FOR COORDINATION.
  
 6) NOTE: PLEASE VERIFY HOW SOME OF THE AHU/CU ON PANEL
 SCHEDULES HAVE NO LOADS SHOWN.
 FOR EXAMPLE:
 UNITS #2 AND 3.
 220
  
 7) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS ON
 GENERATOR AND ATS.
 PLEASE SEE 110.3, 90.7
 SLAB DETAILS NEEDED BY BUILDING.
 PLEASE ALSO KNOW THE HOUSE/LOCATION IS IN A FLOOD ZONE,
 ALL ELECTRICAL EQUIPMENT INCLUDING GENERATOR MUST BE
 6INCHES ABOVE BASE FLOOD ELEVATION.
  
 8) NOTE: PLEASE COMPLETE CIRCUITING FOR SMOKE ALARMS.
 PLEASE ALSO SEE NFPA-72 11.8.3 AS THE SMOKE ALARM IN
 MASTER BEDROOM IS NOT CODE COMPLIANT. NEEDS TO BE
 WITHIN 3FT OFPEAK AND WITHIN 12INCHES OF THE HIGHEST
 POINT.
  
 9) NOTE: PLEASE SEE FBC 13-606.1.ABC.1.2.4 FOR MINIMUM
 TYPES OF RECESSED LIGHTS.
  
 10) NOTE: PLEASE SEE LIGHTS IN SOME CLOSETS DO NOT MEET
 410.8 FOR MINIMUM CLEARANCES.
  
 11) NOTE: PLEASE SEE THE FEEDER SIZE SHOWN FROM THE
 GENERATOR IS SHOWN AS 150MCM. THIS IS NOT A CONDUCTOR
 SIZE PER AWG.
 110.3
  
 12) NOTE: CODES NEED TO BE STATED ON PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 2004 FBC W/ 2007 (RESIDENTIAL CODE)
  
 13) NOTE: PLEASE SEE THE ELECTRICAL AND CONDUITS RUN
 OUTSIDE THE PROPERTY IN THE CITY RIGHT OF WAY ARE NOT
 PERMITTED.
 ALL ELECTRICAL MUST REMAIN WITHIN LOT LINES.
  
 14) NOTE: PLEASE COMPLETE FIXTURE LEGEND, AND SYMBOL
 LEGEND FOR THIS DWELLING. PLEASE SEE SHEET E-0.1 WHICH
 INDICATES MANY ITEMS FROM WHAT WOULD BE A COMMERCIAL
 BUILDING INCLUDING FIXTURES AND CONTROLS.
 FBC 106.3.5.4, 106.1.2
  
  
 ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET
 SUBMITTED FOR REVIEW A FULL REVIEW COULD NOT BE DONE AT
 THIS TIME.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2008-07-01 Cont ID  
Sent By mperson Date 2008-07-01 Time 09:29 Rev Time 0.00
Received By mperson Date 2008-07-01 Time 09:29 Sent To B
Notes
2008-07-01 10:01:47GAS PLAN REVIEW:
 REVISION DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. SHEET P-2.1 NATURAL GAS RISER DIAGRAM:
 SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 NOTE: THE SUBMITTED GAS ISOMETRIC IS NOT INDICATING
 THE CORRESPONG LENGTHS TO ALL CUT SECTIONS OF PIPE.
 REFERENCE THE RED CIRCLED YELLOW HIGH LIGTHED AREAS
 INDICATING THIS AND COMPLY.
  
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: REFERENCE COMMENT #1 AND CORRELATE THE "GAS
 SIZING BASED ON THE FOLLOWING" TABLE TO REFLECT THE
 CORRECT "MAXIMUM DEVELOPED LENGTH". THE ADDED SUM FROM
 THE METER TO THE FARTHEST APPLIANCE IS 101'. THE PLANS
 ARE INDICATING 98' WHICH IS INCORRECT. UNTIL COMMENT #1
 IS ADDRESSED AND PLANS CORRELATED GAS WILL CONTINUE TO
 FAIL PLAN REVIEW. THE UNDERGROUND PE PIPING TO THE
 GENERATOR IS UNDERSIZED. THE FBC- FUEL GAS TABLE
 402.4(20) FOR 1-1/2" PE @ 125' IS ONLY GOOD FOR 550,000
 BTU'S, HOWEVER THE PLANS ARE INDICATING A BTU LOAD
 CAPACITY FOR THE GENERATOR AS BEING 1,012,000 BTU'S.
 THE FBC- FUEL GAS TABLE 402.4(20) @ 125' ONLY GOES UP
 TO 2" PIPE WHICH IS ONLY GOOD FOR 871,000 BTU'S. PLEASE
 REFERENCE THE ATTACHED GAS TABLES INDICATING THIS.
 PLEASE PROVIDE A SIZING TABLE INDICATING COMPLIANCE OR
 CHANGE SYSTEM TO A 2 PSI DELIVERY PRESSURE.
  
 3. SHEET P-1.1 AND P-2.1 PLEASE CORRELATE GENERATOR
 WITH ELECTRICAL SHEETS E-21 AND E-3.1 AND INDICATE THE
 GENERATOR A "FUTURE" APPLIANCE. NOTE: GENERATOR IS
 UNDER A SEPERATE PERMIT.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-05-30 Cont ID  
Sent By mperson Date 2008-05-30 Time 08:19 Rev Time 0.00
Received By mperson Date 2008-05-30 Time 08:19 Sent To E
Notes
2008-05-30 10:02:31GAS PLAN REVIEW:
 DENIED REVISION:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
 NOTE: A GAS PERMIT WILL BE REQUIRED FOR THE PROPOSED
 WORK.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 NOTE: THE SUBMITTED NATURAL GAS RISER DIAGRAM ON SHEET
 P-2.1 IS NOT AN ISOMETRIC AND IT DOES NOT CLEARLY
 INDICATE ALL CUT SECTIONS OF PIPE WITH CORRESPONDING
 LENGTHS.
  
 2. SHEET P-1.1 FIRST FLOOR PLAN INDICATES THE GAS
 WATER HEATER IN A CONFINED SPACE WITH THE DRYER. SUBMIT
 CALCULATIONS FOR COMBUSTION
 AIR AND MAKEUP AIR PER FBC-2004 FUEL GAS CODE SECTION
 304.
  
 3. NOTE: A RESIDENTIAL GENERATOR PERMIT IS REQUIRED
 FOR THE GENERATOR. THE LOCATION OF THE GENERATOR NEEDS
 TO APPROVED BY ZONING BEFORE A GAS PERMIT CAN BE
 ISSUED. SUBMIT TWO COPIES OF A SITE PLAN OR SURVEY
 CLEARLY INDICATING THE GENERATOR'S LOCATION AND
 DIMENSIONS FROM PROPERTY LINES AND DISTANCES FROM
 ADJACENT STRUCTURES.
  
 4. SHEET P-2.1 GAS ISOMETRIC THE BTU'S FOR THE
 GENERATOR ARE WRONG. PER THE SUBMITED MANUFACTURER'S
 SPECIFICATIONS THE GENERATOR @ 100% STANBY RATING IS
 790,000. PLEASE CORRECT BOTH THE BTU'S INDICATED FOR
 THE GENERATOR AND THE TOTAL BTU'S FOR THE SYSTEM TO
 1,160,000.
  
 5. PER (W.P.B. AS AMENDED) SECTION 106.1 SUBMITTAL
 DOCUMENTS. CONSTRUCTION DOCUMENTS, SPECIAL INSPECTION
 AND STRUCTURAL OBSERVATION PROGRAMS, AND OTHER DATA
 SHALL BE SUBMITTED IN TWO OR MORE SETS WITH EACH
 APPLICATION FOR A PERMIT.
 NOTE: ONLY ONE COPY OF THE GENERATOR MANUFACTURER'S
 SPECIFICATIONS WAS SUBMITTED.
  
 6. THE SUBMITTED GENERATOR MANUFACTURER'S
 SPECIFICATIONS FAIL TO INDICATE GENERATOR'S REQUIRED
 SETBACKS FROM STRUCTURES.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-04-02 Cont ID  
Sent By jleech Date 2008-04-02 Time 09:31 Rev Time 0.00
Received By jleech Date 2008-04-02 Time 08:33 Sent To P
Notes
2008-04-02 09:47:15DENIED;
 1. TYPE OF GAS, (LP OR NATURAL)
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 3. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 4. A GEN-RES. AND A ELECTRICAL PERMIT APPLICATION IS
 REQUIRED FOR GENERATOR. PROVIDE MANUFACTURE SPEC.
 SHEETS, ELECTICAL PLAN AND SURVEY.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop HIST HISTORICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-04-26 Cont ID  
Sent By swurafti Date 2007-04-26 Time 10:51 Rev Time 0.00
Received By swurafti Date 2007-04-26 Time 10:51 Sent To  
Notes
2007-04-26 10:51:58HISTORIC APPROVED BY GJUDGE

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-06-23 Cont ID  
Sent By adarroug Date 2008-06-23 Time 10:44 Rev Time 0.00
Received By adarroug Date 2008-06-23 Time 10:44 Sent To Z
Notes
2008-06-23 10:44:51TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-16 Cont ID  
Sent By adarroug Date 2008-05-16 Time 13:47 Rev Time 0.00
Received By adarroug Date 2008-05-16 Time 13:47 Sent To E
Notes
2008-05-16 13:47:57TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-01 Cont ID  
Sent By adarroug Date 2008-04-01 Time 08:46 Rev Time 0.00
Received By adarroug Date 2008-04-01 Time 08:46 Sent To M
Notes
2008-04-01 08:46:27TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-01 Cont ID  
Sent By adarroug Date 2008-04-01 Time 08:38 Rev Time 0.00
Received By adarroug Date 2008-04-01 Time 08:38 Sent To E
Notes
2008-04-01 08:39:17TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-01 Cont ID  
Sent By adarroug Date 2008-04-01 Time 08:20 Rev Time 0.00
Received By adarroug Date 2008-04-01 Time 08:20 Sent To P
Notes
2008-04-01 08:20:57TO "P" BOX/REV--PLEASE REFERENCE PERMIT#06040626

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-17 Cont ID  
Sent By lmartine Date 2007-05-17 Time 14:36 Rev Time 0.00
Received By lmartine Date 2007-05-01 Time 14:47 Sent To  
Notes
2007-05-01 14:48:00TO "LMARTINEZ" DESK--PLEASE REFERENCE PERMIT#06040626

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-06-27 Cont ID  
Sent By tgordon Date 2008-06-27 Time 14:16 Rev Time 0.45
Received By tgordon Date 2008-06-27 Time 14:16 Sent To P
Notes
2008-06-27 14:18:55HIGH VELOCITY SYSTEM
  
 *** PROVISO ***
 1) IF PLASTIC REGISTERS, GRILLES OR DIFFUSERS ARE USED
 THEN PROVIDE UL TESTING REPORT.
 PER 2004 FBC/R M1601.16 DUCT REGISTERS, GRILLES AND
 DIFFUSERS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS, AND SHALL
 HAVE A FLAME SPREAD RATING NOT OVER 25 WITHOUT EVIDENCE
 OF CONTINUED PROGRESSIVE COMBUSTION AND A
 SMOKE-DEVELOPED RATING NOT OVER 50 WHEN TESTED IN
 ACCORDANCE WITH ASTM E 84. BALANCING DAMPERS OR OTHER
 MEANS OF SUPPLY AIR ADJUSTMENT SHALL BE PROVIDED IN THE
 BRANCH DUCTS OR AT EACH INDIVIDUAL DUCT REGISTER,
 GRILLE OR DIFFUSER.
  
 2) HAVE DETAILED MANUFACTURER'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS FOR A/C SYSTEM AND
 PRE-ENGINEERED DUCT SYSTEM ON JOB SITE FOR CITY
 INSPECTORS. PER 2004 FBC/R M1401.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-05-21 Cont ID  
Sent By tgordon Date 2008-05-21 Time 13:47 Rev Time 1.15
Received By tgordon Date 2008-05-21 Time 13:47 Sent To P
Notes
2008-05-21 13:48:49PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 4-1-08 NOTE #1. ENERGY
 CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT ALSO, PER
 2004 FBC 13-103.3.
  
 2) AS NOTED IN LAST REVIEW 4-1-08 NOTE #6. PLEASE
 SUBMIT DETAILED MANUFACTURER'S SPECIFICATION'S THAT
 SHOW THE SUPPLY AIR VENTS COMPLY WITH 2004 FBC M1601.16
 REGISTERS, GRILLES AND DIFFUSERS.DUCT REGISTERS,
 GRILLES AND DIFFUSERS SHALL HAVE A FLAME SPREAD RATING
 NOT OVER 25 WITHOUT EVIDENCE OF CONTINUED PROGRESSIVE
 COMBUSTION AND A SMOKE-DEVELOPED RATING NOT OVER 50
 WHEN TESTED IN ACCORDANCE WITH ASTM E 84. THE RESPONSE
 RECEIVED REFERS TO UL94 HB THAT DEALS WITH FLAME
 RATING, NOT FLAME SPREAD RATING AND SMOKE-DEVELOPED
 RATING. PLEASE PROVIDE DOCUMENTATION SHOWING THE FLAME
 SPREAD RATING AND SMOKE-DEVELOPED RATING.
  
 3) NOT NOTED IN LAST REVIEW, THE GAS TANKLESS WATER
 HEATER IS IN A CONFINED SPACE WITH A CLOTHES DRYER.
 PLEASE PROVIDE FOR COMBUSTION AND MAKE-UP AIR PER 2004
 FBC/R G2407.1, G2407.4, AND G2407.5.1.
  
 4) NOT NOTED IN LAST REVIEW, THE PROPERTY IS IN FLOOD
 ZONE 'A5' PLEASE SHOW HOW THE A/C CONDENSER UNITS AND
 GENERATOR WILL BE MAINTAINED 6" ABOVE THE BASE FLOOD
 ELEVATION, PER W.P.B. CITY ORDINANCE CHAPTER 94,
 ARTICLE XVII SECTION 94-543.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-04-01 Cont ID  
Sent By tgordon Date 2008-04-01 Time 14:02 Rev Time 1.30
Received By tgordon Date 2008-04-01 Time 14:02 Sent To B
Notes
2008-04-01 14:25:38PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 2) COOLING LOAD CALCULATIONS FOR SYSTEM #1 ARE CALLING
 FOR 23,300 TOTAL COOLING BTU'S, MECHANICAL PLANS ARE
 SHOWING A SYSTEM WITH 33,000 TOTAL COOLING BTU'S. THE
 PLANS CAN ONLY CALL FOR 15% MORE THAN THE COOLING LOAD
 CAL'S, PER 2004 FBC 13-607.1.ABC.1.1. A 3 TON SYSTEM IS
 TO LARGE PLEASE CORRECT.
  
 3) COOLING LOAD CALCULATIONS FOR SYSTEM #2 ARE CALLING
 FOR 31,200 TOTAL COOLING BTU'S, MECHANICAL PLANS ARE
 SHOWING A SYSTEM WITH 44,000 TOTAL COOLING BTU'S. THE
 PLANS CAN ONLY CALL FOR 15% MORE THAN THE COOLING LOAD
 CAL'S, PER 2004 FBC 13-607.1.ABC.1.1. A 4 TON SYSTEM IS
 TO LARGE PLEASE CORRECT.
  
 4) COOLING LOAD CALCULATIONS FOR SYSTEM #3 ARE CALLING
 FOR 34,300 TOTAL COOLING BTU'S, MECHANICAL PLANS ARE
 SHOWING A SYSTEM WITH 54,000 TOTAL COOLING BTU'S. THE
 PLANS CAN ONLY CALL FOR 15% MORE THAN THE COOLING LOAD
 CAL'S, PER 2004 FBC 13-607.1.ABC.1.1. A 5 TON SYSTEM IS
 TO LARGE PLEASE CORRECT.
  
 5) PLEASE SUBMIT MANUAL D CALCULATIONS OR EQUIVALENT
 FOR RESIDENTIAL DUCT DESIGN, PER 2004 FBC/R M1601.1 AND
 FBC 13-610.1.ABC.1.
  
 6) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE
 SUPPLY AIR VENTS TO SHOW THEY COMPLY WITH 2004 FBC
 M1601.16 REGISTERS, GRILLES AND DIFFUSERS.DUCT
 REGISTERS, GRILLES AND DIFFUSERS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS, AND SHALL HAVE A FLAME SPREAD RATING NOT
 OVER 25 WITHOUT EVIDENCE OF CONTINUED PROGRESSIVE
 COMBUSTION AND A SMOKE-DEVELOPED RATING NOT OVER 50
 WHEN TESTED IN ACCORDANCE WITH ASTM E 84. BALANCING
 DAMPERS OR OTHER MEANS OF SUPPLY AIR ADJUSTMENT SHALL
 BE PROVIDED IN THE BRANCH DUCTS OR AT EACH INDIVIDUAL
 DUCT REGISTER, GRILLE OR DIFFUSER.
  
 7) THE VALUE ON THE PERMIT MUST BE ADJUSTED TO THE FAIR
 MARKET VALUE (REPLACEMENT VALUE) FOR THE RENOVATION
 WITH ALL MATERIALS AND LABOR. IF THE VALUE IS NOT
 ADJUSTED THEN THE CITY WILL NEED TO ADJUST IT USING THE
 MARSHALL & SWIFT NATIONAL VALUATION SERVICE, PER 2004
 WPB AMEND. 108.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-07-01 Cont ID  
Sent By mperson Date 2008-07-01 Time 08:50 Rev Time 0.00
Received By mperson Date 2008-07-01 Time 08:50 Sent To G
Notes
2008-07-01 09:28:18PLUMBING PLAN REVIEW:
 REVISION DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1. SHEET P-1.1 FIRST FLOOR PLAN DOES NOT REFLECT THE
 FIRST FLOOR PLAN ON SHEET A-1. PLEASE CORRELATE THE
 FOLLOWING ON SHEET P-1.1 WITH SHEET A-1. PER FBC-
 PLUMBING SECTIONS 401.1, 601.1 AND 701.1 SCOPE.
  
 A} THE 15" PREP SINK AND DISHWASHER IS MISSING AS WELL
 AS THE SANITARY AND WATER TO THESE FIXTURES.
  
 B} THE POT FILLER WATER SUPPLY IS MISSING.
  
 C} THE 24" DISHWASHER BY THE 36" SINK IS BEING
 INDICATED ON THE WRONG SIDE OF THE 36" SINK.
  
 2. SHEET P-2.1 SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FIRST FLOOR PLAN ON SHEET A-1. PLEASE CORRELATE THE
 FOLLOWING ON SHEET P-2.1 WITH SHEET A-1. PER FBC-
 PLUMBING SECTIONS 701.1 AND 901.1 SCOPE.
  
 A} THE SANITARY AND VENT FOR THE 15" PREP SINK IS
 MISSING AS WELL AS THE DRAIN FOR THE DISHWASHER.
  
 B} THE DISHWASHER DRAIN FOR THE 36" SINK IS BEING
 INDICATED ON THE WRONG SIDE OF THE SINK.
  
 3. SHEET P-2.1 SANITARY RISER DIAGRAM: DELETE THE SH
 BY THE WC IN THE SECOND FLOOR BATH #3 (THIS IS
 CONFUSING). PER FBC- PLUMBING SECTION 701.1 SCOPE.
  
 4. SHEET P-2.1 DOMESTIC WATER RISER DIAGRAM DOES NOT
 REFLECT THE FIRST FLOOR PLAN ON SHEET A-1. PLEASE
 CORRELATE THE FOLLOWING ON SHEET P-2.1 WITH SHEET A-1.
 PER FBC- PLUMBING SECTION 601.1 SCOPE.
  
 A} THE HOT AND COLD WATER FOR THE 15" PREP SINK AND
 DISHWASHER IS MISSING.
  
 B} THE WATER SUPPLY TO THE POT FILLER IS MISSING.
 (CLEARLY INDICATE IF ITS HOT OR COLD WATER AS SOME POT
 FILLERS HAVE BEEN KNOWN TO BE HOT WATER)
  
 5. SHEET P-2.1 DOMESTIC WATER RISER DIAGRAM: THE
 FOLLOWING FIXTURES NEED WATER-HAMMER ARRESTORS DUE TO
 HAVING QUICK-CLOSING VALVES. PER FBC-PLUMBING SECTION
 604.9.
  
 A} THE HOT WATER SUPPLY TO THE DISHWASHER BY THE 36"
 SINK.
  
 B} THE HOT WATER SUPPLY TO THE DISHWASHER BY THE 15"
 PREP SINK.
  
 C} THE HOT AND COLD WATER TO THE WASHING MACHINE. (ADD
 NOTE BY WASHING MACHINE: REFERENCE DETAIL SHEET
 P-0.1).
  
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-05-30 Cont ID  
Sent By mperson Date 2008-05-30 Time 16:41 Rev Time 0.00
Received By mperson Date 2008-05-29 Time 16:41 Sent To G
Notes
2008-05-29 16:57:08PLUMBING PLAN REVIEW:
 DENIED REVISION:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P-0.1 AUTOMATIC CLOTHES WASHER CONNECTION
 DETAIL: THE DRAINAGE STACK NEED TO BE 3",PER FBC-2004
 PLUMBING SECTION 406.3 WASTE CONNECTION. THE CLEANOUT
 FOR THE WASHING MACHINE NEEDS TO BE 3". PER FBC-2004
 PLUMBING SECTION 708.7 MINIMUM SIZE.
  
 2. SHEET P-2.1 RISER DIAGRAM - SANITARY: THE AUTOMATIC
 CLOTHES WASHER BRANCH DRAIN AND STACK NEED TO BE 3",
 PER FBC-204 PLUMBING SECTION 406.3 WASTE CONNECTION.
 THE CLEANOUT FOR THE WASHING MACHINE NEEDS TO BE 3",
 PER FBC-2004 PLUMBING SECTION 406.3.
  
 3. SHEET P-2.1 POWDER ROOM #109: THE LAV STACK NEEDS A
 CLEANOUT AT THE BASE OF ITS STACK DUE TO THE "PLUMBING
 FIXTURE SCHEDULE" ON SHEET P-0.1 INDICATING 1-1/4"
 TRAPS FOR THE LAVATORIES. PER FBC-2004 PLUMBING SECTION
 708.3.4.
  
 4. ENERGY CALCULATIONS NEED TO BE SIGNED BY
 OWNER/AGENT. PER FBC-2004 13-103.3.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-04-03 Cont ID  
Sent By jleech Date 2008-04-03 Time 08:57 Rev Time 0.00
Received By jleech Date 2008-04-03 Time 08:48 Sent To  
Notes
2008-04-03 09:02:48DENIED;
 1. SEE MECHANICAL PLAN REVIEW NOTE # 7. VALUE $ OF WORK
 AND MATERIALS IS TO LOW.
 2. PLUMBING AND GAS APPLICATIONS ARE REQUIRED.
 3. SHOW ALL PLUMBING AND GAS APPLIANCES ON FLOOR PLANS,
 SHEETS ,A-1 AND A-1.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status F Date 2008-06-24 Cont ID  
Sent By choops Date 2008-06-24 Time 14:17 Rev Time 0.00
Received By choops Date 2008-06-24 Time 14:17 Sent To E
Notes
2008-06-24 14:18:22***FAILED - ZONING 2ND REVIEW***
  
  
 REPEAT COMMENTS:
  
 2)DEMOLITION/ADDITION PLANS SHALL BE STAMPED AND
 APPROVED BY THE CITY'S HISTORIC PRESERVATION
 DEPARTMENT.
  
 5)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDRS.PLEASE SUBMIT A LANDSCAPE PLAN SHOWING
 COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF THE
 ZLDRS.
  
 6)ELECTRICAL SITE PLAN (SHEET ES -1) SHOWS A
 GENERATOR.INDICATE SETBACK DIMENSIONS FROM PROPOSED
 GENERATOR EQUIPMENT TO ALL PROPERTY LINES.AS PER
 SECTION 94-305(B)(4) OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS): MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED
 SETBACK.NOTE: THE GENERATOR MUST MAINTAIN A MINIMUM
 SETBACK OF 11 FEET TO THE REAR (WEST) PROPERTY LINE.
  
  
 NEW COMMENT:
  
 1)THE SIDE SETBACK IS NOT CLEARLY SHOWN FROM THE
 PROPERTY LINE TO THE NEW ADDITION.INDICATE THIS
 SETBACK DIMENSION ON THE SITE PLAN.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
 [email protected]
  
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 1 Status F Date 2008-06-09 Cont ID  
Sent By choops Date 2008-06-09 Time 14:56 Rev Time 0.00
Received By choops Date 2008-06-09 Time 14:56 Sent To  
Notes
2008-06-09 15:14:52***FAILED - ZONING 1ST REVIEW***
  
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S LEGAL DESCRIPTION AND ADDRESS.
  
 2)DEMOLITION/ADDITION PLANS SHALL BE STAMPED AND
 APPROVED BY THE CITY'S HISTORIC PRESERVATION
 DEPARTMENT.
  
 3)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS): MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 4)INDICATE OVERHANG DIMENSIONS OF THE PROPOSED
 ADDITION.AS PER SECTION 94-305(B) OF THE ZLDRS:
 OVERHANGS MAY NOT PROJECT MORE THAN 3' INTO A REQUIRED
 SETACK.
  
 5)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDRS.PLEASE SUBMIT A LANDSCAPE PLAN SHOWING
 COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF THE
 ZLDRS.
  
 6)ELECTRICAL SITE PLAN (SHEET ES -1) SHOWS A
 GENERATOR.INDICATE SETBACK DIMENSIONS FROM PROPOSED
 GENERATOR EQUIPMENT TO ALL PROPERTY LINES.AS PER
 SECTION 94-305(B)(4) OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS): MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED
 SETBACK.NOTE: THE GENERATOR MUST MAINTAIN A MINIMUM
 SETBACK OF 11 FEET TO THE REAR (WEST) PROPERTY LINE.
  
  
 NOTE:THE "FUTURE LIBRARY CONSTRUCTION - TO BE
 PERMITTED SEPARATELY" WILL NOT BE ALLOWED AS SHOWN. IF
 THE PRINCIPAL STRUCTURE IS MADE TO CONNECT TO THE
 EXISTING ACCESSORY STRUCTURE, THE ENTIRE BUILDING WILL
 BE REQUIRED TO MEET THE PRINCIPAL STRUCTURE'S SETBACK
 REQUIREMENTS, WHICH IT DOES NOT.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720