| Plan Review Stops For Permit 07040875 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2007-11-12 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2007-11-12 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2007-11-12 |
Time |
15:27 |
Sent To |
|
|
| Notes |
| 2007-11-12 15:35:10 | SEE PROVISO FROM 8/31/07.GARAGE DOOR PRODUCT APPROVAL | | | IS STILL REQUIRED. | | | | | | ENGINEER'S LETTER AND CALCULATION RECEIVED STATING THAT | | | THE DESIGN PRESSURES ARE +64.1 PSF AND -64.1 PSF, BASED | | | ON AN EXPOSURE CATEGORY OF 'C".NOTE THAT THE | | | ENGINEER'S LETTER DOES GIVE JUSTIFICATION THAT WOULD | | | PERMIT THE USE OF EXPOSURE CATEGORY 'B' AND HENCE LOWER | | | DESIGN WIND PRESSURES SHOULD THE ENGINEER CHOOSE TO | | | SUBMIT A CALCULATION BASED ON EXPOSURE CATEGORY 'B'. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2007-10-09 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2007-10-09 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2007-10-09 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2007-10-09 14:02:09 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6652 | | | E-MAIL: [email protected] | | | | | | | | | REVISION SUBMITTED ON 9/17/07 FOR ENGINEER'S STATEMENT | | | ADDRESSING THE PROVISO REQUIRING SUBMITTTAL OF A GARAGE | | | DOOR PRODUCT APPROVAL. | | | | | | FBC = FLORIDA BUILDING CODE 2004 WITH 2005 AND 2006 | | | AMENDMENTS | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | 1)FBC 1609.2THE MEMO DATED 9/11/07 FROM ROBERT | | | BOTKIN, P.E. STATES THAT THE PARKING GARAGE DOES NOT | | | MEET THE DEFINITION OF "PARTIALLY ENCLOSED" BECAUSE AO | | | < 1.10 AOI.THAT ARGUMENT HAS BEEN USED TO JUSTIFY | | | CONSIDERATION OF THE PARKING GARAGE AS "ENCLOSED", AND | | | TREATMENT OF THE PROPOSED GARAGE DOOR AS INTERIOR. | | | PLEASE NOTE THE FOLLOWING FLORIDA BUILDING CODE | | | DEFINITIONS FOR THE TERMS AO AND AOI: | | | AO IS "TOTAL AREA OF OPENINGS IN A WALL THAT RECEIVES | | | POSITIVE EXTERNAL PRESSURE, IN SQUARE FEET" | | | AOI IS "THE SUM OF THE AREAS OF OPENINGS IN THE | | | BUILDING ENVELOPE (WALLS AND ROOF) NOT INCLUDING AO, IN | | | SQUARE FEET" | | | IN THIS CASE AO IS THE AREA OF THE GARAGE ENTRIES IN | | | ONE EXTERIOR WALL (I.E. WILL RECEIVE POSITIVE PRESSURE | | | AT THE SAME TIME), AND AOI IS THE SUM OF THE AREAS OF | | | THE OPENINGS IN THE OTHER EXTERIOR WALLS OF THE GARAGE. | | | THOSE OPENINGS DO NOT INCLUDE ANY THAT ARE FITTED WITH | | | DOORS, WINDOWS OR OTHER CLOSURE DEVICES.THE | | | ENGINEER'S MEMO DOES NOT STATE THE ACTUAL NUMBER OF | | | SQUARE FEET REPRESENTED BY AOI. | | | THE PARKING GARAGE MUST BE CONSIDERED AS PARTIALLY | | | ENCLOSED UNLESS YOU CAN SHOW THAT AO < AOI.TO DO THIS | | | YOU MUST SPECIFY THE SQUARE FOOTAGE OF AOI AND STATE | | | WHICH "OTHER" OPENINGS HAVE BEEN TAKEN TO CONTRIBUTE TO | | | THE SQUARE FOOTAGE OF AOI.EITHER PROVIDE THIS | | | JUSTIFICATION OR SUBMIT A PRODUCT APPROVAL FOR A GARAGE | | | DOOR PRODUCT THAT IWILL WITHSTAND THE APPROPRIATE | | | COMPONENTS AND CLADDING PRESSURES. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | | (561) 805 6652ROBERT BROWN | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2007-08-31 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-08-31 |
Time |
12:24 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-08-31 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2007-08-31 12:26:34 | **PROVISO** | | | SUBMIT GARAGE DOOR PRODUCT APPROVAL AS A REVISION | | | REVISE EXPOSURE CATEGORY TO "C"FBC 1609 | | | AT RISK PERMIT SUBJECT TO ENGINEER'S REVISIONS | | | PROVIDE CONDO ASSOCIATION APPROVAL |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2007-08-31 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-08-31 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-08-31 |
Time |
12:22 |
Sent To |
|
|
| Notes |
| 2007-08-31 12:24:08 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | | | | 1.)ENGINEER HAS SPECIFIED DESIGN PRESSURE OF -52.7, | | | BUT THE DOOR HAS A DESIGN PRESSURE LIMITATION OF -44.4 | | | FOR THE DOOR CIRCLED BY THE ENGINEER.NOTE THAT THE | | | HIGHER PRESSURE OF -65.6 IS THE TEST PRESSURE; DESIGN | | | PRESSURE HAS A FACTOR OF SAFETY. | | | | | | 2.)THIS BUILDING IS IN EXPOSURE C.REVISE WIND | | | DESIGN CRITERIA. | | | | | | OTHER ITEMS OK PER NMK | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-07-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-07-10 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-07-10 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2007-07-10 11:43:32 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)PROVIDE FIRE RESISTANCE INFORMATION FOR THIS WALL | | | AND OPENING.SEE ALSO FBC 708.1, EXCEPTION.NOT | | | ENOUGH INFORMATION WAS PROVIDED TO DETERMINE CODE | | | COMPLIANCE. | | | | | | 3RD REVIEW - NOT ADDRESSED.TENANT SEPARATION IS | | | REQUIRED FBC708.1(5).THIS IS A SEPARATION BETWEEN A | | | PRIVATE, OR "TENANT" SPACE, AND THE COMMON AREA. | | | | | | 2.)THE INFORMATION IN REGARDS TO THE EXISTING | | | BUILDING WAS PROVIDED ON A REDUCED PLAN AND IS NOT | | | LEGIBLE.ALL INFORMATION REQUIRED TO SHOW CODE | | | COMPLIANCE, INCLUDING A BASIC CODE SUMMARY, IS TO BE | | | INCLUDED IN A PLAN SIGNED, SEALED, AND DATED BY THE | | | DESIGN PROFESSIONAL. | | | | | | 2ND & 3RD REVIEW - PROVIDE THE CODE SUMMARY AS | | | REQUESTED; OCCUPANCY CLASSIFICATION FBC3, BUILDING TYPE | | | FBC6, SPRINKLER INFORMATION.THIS WAS ADDRESSED IN THE | | | RESPONSE LETTER BUT THE RESPONSE LETTER IS NOT A PART | | | OF THE PERMIT PACKAGE.PLEASE INCORPORATE INTO THE | | | PLAN. | | | | | | 3.)ADDRESSED. | | | | | | 4.)ADDRESSED. | | | | | | 5.)PLANS STATE "RELOCATE FIRE SPRINKLER HEAD". | | | PROVIDE A PLAN.THE FIRE SPRINKLER PLAN IS REQUIRED AS | | | A PART OF THIS PERMIT PACKAGE FS553.79(2), | | | FBC*106.3.5.1.1(5). | | | | | | 6.-7.)ADDRESSED. | | | | | | 8.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER | | | OF RECORD, FBC*106.3.3. | | | | | | 9.)PROVIDE FIRE RATING INFORMATION FOR THE GARAGE | | | DOOR.FIRE RATING REQUIREMENTS ARE NOT CLEAR DUE TO | | | INSUFFICIENT INFORMATION, SEE ITEM 1. | | | | | | NEW COMMENT: | | | | | | 10.)THE ENGINEER STATES THAT PRODUCT APPROVALS ARE | | | NOT REQUIRED AND STATES THAT THE DESIGN PRESSURE FOR | | | THIS OPEING IS +-5 PSF.THIS OPENING, ALTHOUGH NOT ON | | | AN EXTERIOR WALL, IS NEAR THE GARAGE ENTRY, A LARGE | | | OPENING, AND IS SUBJECT TO WIND PRESSURES.PLEASE | | | DECLARE WIND DESIGN CRITERIA FBC 1603.1.4.WIND TUNNEL | | | TEST REPORT MAY BE AVAILABLE; APRIL PICCIRILLO, | | | 561-805-6658. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-06-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-06-18 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-06-18 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2007-06-18 14:00:40 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)PROVIDE FIRE RESISTANCE INFORMATION FOR THIS WALL | | | AND OPENING.SEE ALSO FBC 708.1, EXCEPTION.NOT | | | ENOUGH INFORMATION WAS PROVIDED TO DETERMINE CODE | | | COMPLIANCE. | | | | | | 2ND REVIEW - NOT ADDRESSED.TENANT SEPARATION IS | | | REQUIRED FBC708.1(5); REQUESTED INFORMATION WAS NOT | | | PROVIDED. | | | | | | 2.)THE INFORMATION IN REGARDS TO THE EXISTING | | | BUILDING WAS PROVIDED ON A REDUCED PLAN AND IS NOT | | | LEGIBLE.ALL INFORMATION REQUIRED TO SHOW CODE | | | COMPLIANCE, INCLUDING A BASIC CODE SUMMARY, IS TO BE | | | INCLUDED IN A PLAN SIGNED, SEALED, AND DATED BY THE | | | DESIGN PROFESSIONAL. | | | | | | 2ND REVIEW - PROVIDE THE CODE SUMMARY AS REQUESTED; | | | OCCUPANCY CLASSIFICATION FBC3, BUILDING TYPE FBC6, | | | SPRINKLER INFORMATION. | | | | | | 3.)ADDRESSED. | | | | | | 4.)ADDRESSED. | | | | | | NEW COMMENTS: | | | | | | 5.)PLANS STATE "RELOCATE FIRE SPRINKLER HEAD". | | | PROVIDE A PLAN.THE FIRE SPRINKLER PLAN IS REQUIRED AS | | | A PART OF THIS PERMIT PACKAGE FS553.79(2), | | | FBC*106.3.5.1.1(5). | | | | | | 6.)ALL INFORMATION REQUIRED BY FAC61G15-23.002 | | | (ENGINEER) IS TO BE ON EACH SHEET. | | | | | | 7.)TWO SETS OF ALL DOCUMENTS REQUIRED.ONLY ONE | | | PRODUCT APPROVAL WAS SUBMITTED. | | | | | | 8.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER | | | OF RECORD, FBC*106.3.3. | | | | | | 9.)PROVIDE FIRE RATING INFORMATION FOR THE GARAGE | | | DOOR.FIRE RATING REQUIREMENTS ARE NOT CLEAR DUE TO | | | INSUFFICIENT INFORMATION, SEE ITEM 1. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-05-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-05-07 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-05-07 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2007-05-07 17:50:28 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)PROVIDE FIRE RESISTANCE INFORMATION FOR THIS WALL | | | AND OPENING.SEE ALSO FBC 708.1, EXCEPTION.NOT | | | ENOUGH INFORMATION WAS PROVIDED TO DETERMINE CODE | | | COMPLIANCE. | | | | | | 2.)THE INFORMATION IN REGARDS TO THE EXISTING | | | BUILDING WAS PROVIDED ON A REDUCED PLAN AND IS NOT | | | LEGIBLE.ALL INFORMATION REQUIRED TO SHOW CODE | | | COMPLIANCE, INCLUDING A BASIC CODE SUMMARY, IS TO BE | | | INCLUDED IN A PLAN SIGNED, SEALED, AND DATED BY THE | | | DESIGN PROFESSIONAL. | | | | | | 3.)ALL INFORMATION PREPARED BY AN ARCHITECT AND | | | SUBMITTED FOR PUBLIC RECORD IS TO BE SIGNED, SEALED, | | | DATED ORIGINALS FS417. | | | | | | 4.)A DETAIL WAS PROVIDED SHOWING THAT THE DOOR WILL | | | BE ENLARGED.WILL A NEW DOOR BE INSTALLED?INCLUDE | | | THE DOOR INFORMATION IN THE PLAN. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-10-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-17 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-17 |
Time |
10:57 |
Sent To |
B |
|
| Notes |
| 2007-10-17 10:57:32 | TO "SHILL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-09-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-17 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-17 |
Time |
16:07 |
Sent To |
B |
|
| Notes |
| 2007-09-17 16:07:44 | TO "SHILL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-08-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-29 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-29 |
Time |
16:02 |
Sent To |
B |
|
| Notes |
| 2007-08-29 16:02:51 | TO "SHILL' DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-07-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-03 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-03 |
Time |
09:49 |
Sent To |
B |
|
| Notes |
| 2007-07-03 09:49:45 | TO "SHILL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-05-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-05-21 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-05-21 |
Time |
16:26 |
Sent To |
B |
|
| Notes |
| 2007-05-21 16:26:29 | TO "SHILL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-05-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-05-07 |
Time |
17:50 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-04-25 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2007-04-25 13:11:11 | TO "MISC" BOX#1 |
|
|