Plan Review Details - Permit 07040875
Plan Review Stops For Permit 07040875
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-11-12 Cont ID  
Sent By rbrown Date 2007-11-12 Time 15:27 Rev Time 0.00
Received By rbrown Date 2007-11-12 Time 15:27 Sent To  
Notes
2007-11-12 15:35:10SEE PROVISO FROM 8/31/07.GARAGE DOOR PRODUCT APPROVAL
 IS STILL REQUIRED.
  
 ENGINEER'S LETTER AND CALCULATION RECEIVED STATING THAT
 THE DESIGN PRESSURES ARE +64.1 PSF AND -64.1 PSF, BASED
 ON AN EXPOSURE CATEGORY OF 'C".NOTE THAT THE
 ENGINEER'S LETTER DOES GIVE JUSTIFICATION THAT WOULD
 PERMIT THE USE OF EXPOSURE CATEGORY 'B' AND HENCE LOWER
 DESIGN WIND PRESSURES SHOULD THE ENGINEER CHOOSE TO
 SUBMIT A CALCULATION BASED ON EXPOSURE CATEGORY 'B'.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-10-09 Cont ID  
Sent By rbrown Date 2007-10-09 Time 13:27 Rev Time 0.00
Received By rbrown Date 2007-10-09 Time 13:27 Sent To  
Notes
2007-10-09 14:02:09BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
  
 REVISION SUBMITTED ON 9/17/07 FOR ENGINEER'S STATEMENT
 ADDRESSING THE PROVISO REQUIRING SUBMITTTAL OF A GARAGE
 DOOR PRODUCT APPROVAL.
  
 FBC = FLORIDA BUILDING CODE 2004 WITH 2005 AND 2006
 AMENDMENTS
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1)FBC 1609.2THE MEMO DATED 9/11/07 FROM ROBERT
 BOTKIN, P.E. STATES THAT THE PARKING GARAGE DOES NOT
 MEET THE DEFINITION OF "PARTIALLY ENCLOSED" BECAUSE AO
 < 1.10 AOI.THAT ARGUMENT HAS BEEN USED TO JUSTIFY
 CONSIDERATION OF THE PARKING GARAGE AS "ENCLOSED", AND
 TREATMENT OF THE PROPOSED GARAGE DOOR AS INTERIOR.
 PLEASE NOTE THE FOLLOWING FLORIDA BUILDING CODE
 DEFINITIONS FOR THE TERMS AO AND AOI:
 AO IS "TOTAL AREA OF OPENINGS IN A WALL THAT RECEIVES
 POSITIVE EXTERNAL PRESSURE, IN SQUARE FEET"
 AOI IS "THE SUM OF THE AREAS OF OPENINGS IN THE
 BUILDING ENVELOPE (WALLS AND ROOF) NOT INCLUDING AO, IN
 SQUARE FEET"
 IN THIS CASE AO IS THE AREA OF THE GARAGE ENTRIES IN
 ONE EXTERIOR WALL (I.E. WILL RECEIVE POSITIVE PRESSURE
 AT THE SAME TIME), AND AOI IS THE SUM OF THE AREAS OF
 THE OPENINGS IN THE OTHER EXTERIOR WALLS OF THE GARAGE.
 THOSE OPENINGS DO NOT INCLUDE ANY THAT ARE FITTED WITH
 DOORS, WINDOWS OR OTHER CLOSURE DEVICES.THE
 ENGINEER'S MEMO DOES NOT STATE THE ACTUAL NUMBER OF
 SQUARE FEET REPRESENTED BY AOI.
 THE PARKING GARAGE MUST BE CONSIDERED AS PARTIALLY
 ENCLOSED UNLESS YOU CAN SHOW THAT AO < AOI.TO DO THIS
 YOU MUST SPECIFY THE SQUARE FOOTAGE OF AOI AND STATE
 WHICH "OTHER" OPENINGS HAVE BEEN TAKEN TO CONTRIBUTE TO
 THE SQUARE FOOTAGE OF AOI.EITHER PROVIDE THIS
 JUSTIFICATION OR SUBMIT A PRODUCT APPROVAL FOR A GARAGE
 DOOR PRODUCT THAT IWILL WITHSTAND THE APPROPRIATE
 COMPONENTS AND CLADDING PRESSURES.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-08-31 Cont ID  
Sent By shill Date 2007-08-31 Time 12:24 Rev Time 0.00
Received By shill Date 2007-08-31 Time 12:24 Sent To  
Notes
2007-08-31 12:26:34**PROVISO**
 SUBMIT GARAGE DOOR PRODUCT APPROVAL AS A REVISION
 REVISE EXPOSURE CATEGORY TO "C"FBC 1609
 AT RISK PERMIT SUBJECT TO ENGINEER'S REVISIONS
 PROVIDE CONDO ASSOCIATION APPROVAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-08-31 Cont ID  
Sent By shill Date 2007-08-31 Time 12:22 Rev Time 0.00
Received By shill Date 2007-08-31 Time 12:22 Sent To  
Notes
2007-08-31 12:24:08****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
  
 1.)ENGINEER HAS SPECIFIED DESIGN PRESSURE OF -52.7,
 BUT THE DOOR HAS A DESIGN PRESSURE LIMITATION OF -44.4
 FOR THE DOOR CIRCLED BY THE ENGINEER.NOTE THAT THE
 HIGHER PRESSURE OF -65.6 IS THE TEST PRESSURE; DESIGN
 PRESSURE HAS A FACTOR OF SAFETY.
  
 2.)THIS BUILDING IS IN EXPOSURE C.REVISE WIND
 DESIGN CRITERIA.
  
 OTHER ITEMS OK PER NMK
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-07-10 Cont ID  
Sent By shill Date 2007-07-10 Time 11:25 Rev Time 0.00
Received By shill Date 2007-07-10 Time 11:25 Sent To  
Notes
2007-07-10 11:43:32****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE FIRE RESISTANCE INFORMATION FOR THIS WALL
 AND OPENING.SEE ALSO FBC 708.1, EXCEPTION.NOT
 ENOUGH INFORMATION WAS PROVIDED TO DETERMINE CODE
 COMPLIANCE.
  
 3RD REVIEW - NOT ADDRESSED.TENANT SEPARATION IS
 REQUIRED FBC708.1(5).THIS IS A SEPARATION BETWEEN A
 PRIVATE, OR "TENANT" SPACE, AND THE COMMON AREA.
  
 2.)THE INFORMATION IN REGARDS TO THE EXISTING
 BUILDING WAS PROVIDED ON A REDUCED PLAN AND IS NOT
 LEGIBLE.ALL INFORMATION REQUIRED TO SHOW CODE
 COMPLIANCE, INCLUDING A BASIC CODE SUMMARY, IS TO BE
 INCLUDED IN A PLAN SIGNED, SEALED, AND DATED BY THE
 DESIGN PROFESSIONAL.
  
 2ND & 3RD REVIEW - PROVIDE THE CODE SUMMARY AS
 REQUESTED; OCCUPANCY CLASSIFICATION FBC3, BUILDING TYPE
 FBC6, SPRINKLER INFORMATION.THIS WAS ADDRESSED IN THE
 RESPONSE LETTER BUT THE RESPONSE LETTER IS NOT A PART
 OF THE PERMIT PACKAGE.PLEASE INCORPORATE INTO THE
 PLAN.
  
 3.)ADDRESSED.
  
 4.)ADDRESSED.
  
 5.)PLANS STATE "RELOCATE FIRE SPRINKLER HEAD".
 PROVIDE A PLAN.THE FIRE SPRINKLER PLAN IS REQUIRED AS
 A PART OF THIS PERMIT PACKAGE FS553.79(2),
 FBC*106.3.5.1.1(5).
  
 6.-7.)ADDRESSED.
  
 8.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 9.)PROVIDE FIRE RATING INFORMATION FOR THE GARAGE
 DOOR.FIRE RATING REQUIREMENTS ARE NOT CLEAR DUE TO
 INSUFFICIENT INFORMATION, SEE ITEM 1.
  
 NEW COMMENT:
  
 10.)THE ENGINEER STATES THAT PRODUCT APPROVALS ARE
 NOT REQUIRED AND STATES THAT THE DESIGN PRESSURE FOR
 THIS OPEING IS +-5 PSF.THIS OPENING, ALTHOUGH NOT ON
 AN EXTERIOR WALL, IS NEAR THE GARAGE ENTRY, A LARGE
 OPENING, AND IS SUBJECT TO WIND PRESSURES.PLEASE
 DECLARE WIND DESIGN CRITERIA FBC 1603.1.4.WIND TUNNEL
 TEST REPORT MAY BE AVAILABLE; APRIL PICCIRILLO,
 561-805-6658.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-18 Cont ID  
Sent By shill Date 2007-06-18 Time 13:43 Rev Time 0.00
Received By shill Date 2007-06-18 Time 13:43 Sent To  
Notes
2007-06-18 14:00:40****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE FIRE RESISTANCE INFORMATION FOR THIS WALL
 AND OPENING.SEE ALSO FBC 708.1, EXCEPTION.NOT
 ENOUGH INFORMATION WAS PROVIDED TO DETERMINE CODE
 COMPLIANCE.
  
 2ND REVIEW - NOT ADDRESSED.TENANT SEPARATION IS
 REQUIRED FBC708.1(5); REQUESTED INFORMATION WAS NOT
 PROVIDED.
  
 2.)THE INFORMATION IN REGARDS TO THE EXISTING
 BUILDING WAS PROVIDED ON A REDUCED PLAN AND IS NOT
 LEGIBLE.ALL INFORMATION REQUIRED TO SHOW CODE
 COMPLIANCE, INCLUDING A BASIC CODE SUMMARY, IS TO BE
 INCLUDED IN A PLAN SIGNED, SEALED, AND DATED BY THE
 DESIGN PROFESSIONAL.
  
 2ND REVIEW - PROVIDE THE CODE SUMMARY AS REQUESTED;
 OCCUPANCY CLASSIFICATION FBC3, BUILDING TYPE FBC6,
 SPRINKLER INFORMATION.
  
 3.)ADDRESSED.
  
 4.)ADDRESSED.
  
 NEW COMMENTS:
  
 5.)PLANS STATE "RELOCATE FIRE SPRINKLER HEAD".
 PROVIDE A PLAN.THE FIRE SPRINKLER PLAN IS REQUIRED AS
 A PART OF THIS PERMIT PACKAGE FS553.79(2),
 FBC*106.3.5.1.1(5).
  
 6.)ALL INFORMATION REQUIRED BY FAC61G15-23.002
 (ENGINEER) IS TO BE ON EACH SHEET.
  
 7.)TWO SETS OF ALL DOCUMENTS REQUIRED.ONLY ONE
 PRODUCT APPROVAL WAS SUBMITTED.
  
 8.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 9.)PROVIDE FIRE RATING INFORMATION FOR THE GARAGE
 DOOR.FIRE RATING REQUIREMENTS ARE NOT CLEAR DUE TO
 INSUFFICIENT INFORMATION, SEE ITEM 1.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-07 Cont ID  
Sent By shill Date 2007-05-07 Time 17:27 Rev Time 0.00
Received By shill Date 2007-05-07 Time 17:27 Sent To  
Notes
2007-05-07 17:50:28****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE FIRE RESISTANCE INFORMATION FOR THIS WALL
 AND OPENING.SEE ALSO FBC 708.1, EXCEPTION.NOT
 ENOUGH INFORMATION WAS PROVIDED TO DETERMINE CODE
 COMPLIANCE.
  
 2.)THE INFORMATION IN REGARDS TO THE EXISTING
 BUILDING WAS PROVIDED ON A REDUCED PLAN AND IS NOT
 LEGIBLE.ALL INFORMATION REQUIRED TO SHOW CODE
 COMPLIANCE, INCLUDING A BASIC CODE SUMMARY, IS TO BE
 INCLUDED IN A PLAN SIGNED, SEALED, AND DATED BY THE
 DESIGN PROFESSIONAL.
  
 3.)ALL INFORMATION PREPARED BY AN ARCHITECT AND
 SUBMITTED FOR PUBLIC RECORD IS TO BE SIGNED, SEALED,
 DATED ORIGINALS FS417.
  
 4.)A DETAIL WAS PROVIDED SHOWING THAT THE DOOR WILL
 BE ENLARGED.WILL A NEW DOOR BE INSTALLED?INCLUDE
 THE DOOR INFORMATION IN THE PLAN.
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-10-17 Cont ID  
Sent By adarroug Date 2007-10-17 Time 10:57 Rev Time 0.00
Received By adarroug Date 2007-10-17 Time 10:57 Sent To B
Notes
2007-10-17 10:57:32TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-17 Cont ID  
Sent By adarroug Date 2007-09-17 Time 16:07 Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 16:07 Sent To B
Notes
2007-09-17 16:07:44TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-29 Cont ID  
Sent By adarroug Date 2007-08-29 Time 16:02 Rev Time 0.00
Received By adarroug Date 2007-08-29 Time 16:02 Sent To B
Notes
2007-08-29 16:02:51TO "SHILL' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-03 Cont ID  
Sent By adarroug Date 2007-07-03 Time 09:49 Rev Time 0.00
Received By adarroug Date 2007-07-03 Time 09:49 Sent To B
Notes
2007-07-03 09:49:45TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-21 Cont ID  
Sent By shill Date 2007-05-21 Time 16:26 Rev Time 0.00
Received By shill Date 2007-05-21 Time 16:26 Sent To B
Notes
2007-05-21 16:26:29TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-07 Cont ID  
Sent By shill Date 2007-05-07 Time 17:50 Rev Time 0.00
Received By shill Date 2007-04-25 Time 13:11 Sent To  
Notes
2007-04-25 13:11:11TO "MISC" BOX#1