| Plan Review Stops For Permit 07040835 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
11 |
Status |
P |
Date |
2008-05-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-05-28 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-05-28 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2008-05-28 11:34:54 | REVISED A3, A3.1, A3.2, D1, D2, S1, S2, S3, S3.1, S3.2, | | | S4, S5, S6 | | | DATED 5/7/8 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
P |
Date |
2008-05-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-05-12 |
Time |
17:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-05-12 |
Time |
17:47 |
Sent To |
|
|
| Notes |
| 2008-05-12 17:47:54 | REVISION, DOME CEILING FRAMING DETAIL DATED 4/2/8 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
F |
Date |
2008-03-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-12 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-03-21 |
Time |
12:52 |
Sent To |
|
|
| Notes |
| 2008-03-21 13:19:40 | ****CORRECTIONS**** | | | ****REVISION**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.REVISED SHEETS SHOULD REPLACE THE SHEET WITH THE | | | SAME NAME.THE SCOPE OF WORK IS NOT CLEAR; SEE OTHER | | | COMMENTS. | | | | | | 2.IN THE RECORD SET, SHEET S1 DATED 9/20/07 SHOWS A | | | "RAISED NEW PLATFORM".THIS DOES NOT APPEAR ON THE NEW | | | S1 SUBMITTED DATED 3/11/08, AND THIS AREA IS NOT | | | CLOUDED AS A CHANGE TO THE PLAN.IF THIS IS TO BE | | | INCLUDED IN THE SCOPE OF WORK, S1 SHOULD SHOW THE | | | PLATFORM.IF YOU ARE REMOVING THIS RAISED PLATFORM | | | FROM THE SCOPE OF WORK THIS AREA SHOULD BE CLOUDED AND | | | OTHER AFFECTED SHEETS ARE TO BE REVISED. | | | | | | 3.SHEET 2 IN THE PERMIT SET DOES NOT BEAR ANY | | | RESEMBLANCE TO THE REVISED S2 SUBMITTED. IF THIS IS A | | | NEW SHEET WITH NEW DETAILS, IT SHOULD HAVE A NEW | | | (UNIQUE) PAGE NUMBER AND WILL THEN BE ADDED TO THE SET, | | | RATHER THAN REPLACING THE OLD S2. | | | | | | 4.SHEET S2, OTHER PLACES, PLEASE SEE FBC603 REGARDING | | | USE OF COMBUSTIBLE MATERIALS IN TYPE I & II BUILDINGS. | | | PLEASE CLARIFY UNDER WHICH EXCEPTION PLYWOOD SHEATHING | | | IS PERMITTED, IF ANY. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2008-03-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-03-12 |
Time |
09:37 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-03-12 |
Time |
09:36 |
Sent To |
PC |
|
| Notes |
| 2008-03-12 09:37:39 | REVISIONS FIRE STOPPING DETAILS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2008-02-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-02-27 |
Time |
12:09 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-02-27 |
Time |
12:09 |
Sent To |
PC |
|
| Notes |
| 2008-02-27 12:12:13 | REVISIONDATED 2/21/08 STOREFRONT 81/2 X 11 2SHEETS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
|
Date |
2008-02-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-02-21 |
Time |
15:06 |
Rev Time |
0.88 |
| Received By |
jwitmer |
Date |
2008-02-21 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2008-02-25 15:07:54 | REVISION PRODUCT APPROVALS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2008-01-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-01-31 |
Time |
16:59 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-01-31 |
Time |
16:59 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-10-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-10-23 |
Time |
14:15 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2007-10-23 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2007-10-23 14:16:41 | PROVISO: CONTRACTOR TO SUBMIT THE ORIGINAL PERMIT | | | APPLICATION AND LETTER OF TRARNSFER FROM THE ORIGINAL | | | CONTRACTOR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-10-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-10-01 |
Time |
12:52 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2007-10-01 |
Time |
12:52 |
Sent To |
|
|
| Notes |
| 2007-10-01 13:34:55 | TAVERNA OPA 2ND REVIEW | | | 700 S. ROSEMARY | | | BUILDING PLAN REVIEW | | | PERMIT: 07040835 | | | ADD: 700 S ROSEMARY # 232 | | | CONT: L. DAVIS CONSTRUCTION | | | TEL: (561)718-8161 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RDREVIEW ? BUILDING8-25-07 | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUNDWILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3-7) COMPLIED. | | | | | | 8) RED LINE ACI-318-02 UPDATE | | | ACI 531-79 NOT EVEN LISTED | | | ACI 530.1-05 THERE IS THIS NUMBER FOR | | | MASONRY REQUIREMENTS | | | 9-19) COMPLIED. | | | | | | 20) COMPLIED. | | | | | | 21-23) COMPLIED. | | | | | | 24) CHANGE IN OCCUPANCY,BEFORE A PERMIT TO | | | CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY | | | OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE INFORMATION. | | | | | | 25) NEW COMMENT, SHEET S3 DETAIL # 1, SEE NOTES FOR | | | STRUCTURAL MULLIONS,NOTES 8,9 & 10 INDICATE THE | | | MULLIONS ARE VERTICAL WHEN THEY ARE HORIZONTAL. | | | | | | 26) NEW COMMENT, CHANGE OF CONTRACTOR PLEASE NOTE THE | | | PERMIT APPLICATION SUBMITTED INDICATES 700 S ROSEMARY | | | SUITE 100, WHERE ASTHE RESUB SHEET AND ORIGINAL | | | CONTRACTOR PERMIT APPLICATION INDICATES SUITE # 232 | | | AAAS WELL AS THE PLANS. PLEASE CORRECT. | | | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE | | | APPLICABLE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | | | | | | | | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-08-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-08-25 |
Time |
12:15 |
Rev Time |
3.77 |
| Received By |
jwitmer |
Date |
2007-08-25 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2007-08-25 12:26:26 | TAVERNA OPA 2ND REVIEW | | | 700 S. ROSEMARY | | | BUILDING PLAN REVIEW | | | PERMIT: 07040835 | | | ADD: 700 S ROSEMARY # 232 | | | CONT: L. DAVIS CONSTRUCTION | | | TEL: (561)718-8161 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2NDREVIEW ? BUILDING8-25-07 | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUNDWILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) 2ND REQUEST,COVERSHEET BLDG DESIGN DATA PLEASE | | | CORRECT NUMBER OF STORIES, NOTE THE PARKING GARAGE AND | | | B BLOCK RETAIL ARE CONSIDERED ONE BUILDING, NOT TWO. | | | NOTE RESPONSE INDICATES A TYPE I BUILDING PROVIDE IF | | | DESIGNED AS A IA OR IB? | | | | | | 4-7) COMPLIED. | | | | | | | | | | | | 8) PLEASE CLOUD DELTA TO INDICATE CHANGES MADE AS | | | REQUESTED IN COMMENT NUMBER1. SHEET A-1 GENERAL NOTE# | | | 15 PLEASE CORRECT THE EDITION THESTANDARDS REFERENCE | | | INTHE 2006 FBC-BUILDING CHAPTER 35. | | | UPDATE 8A) ASTM C-83 | | | 8B) ACI 318-83 | | | 8C) ACI 301-84 | | | 8D) ACI 531-79 (REVISE THE STANDARD | | | NUMBER AND EDITION) | | | | | | 9A) 2ND REQUEST,PLEASE PROVIDE A LIFE SAFETY PLAN | | | INDICATING THE EGRESS PATTERNS, PROVIDE WIDTH OF THE | | | AISLE AND OCCUPANT LOADS THROUGH TO THE EXIT | | | DISCHARGE. | | | SEMI-COMPLIED PLEASE PROVIDE 44? ACCESS AISLES. | | | 1024.9.1.1THE MINIMUM WIDTH OF AISLES SERVING SEATING | | | AT TABLES SHALL BE 44 INCHES (1118 MM). | | | EXCEPTION: THIRTY-SIX INCHES (914 MM) WHERE SERVING AN | | | OCCUPANT LOAD OF NOT MORE THAN 50. | | | | | | 9B) PRIVATE ELEVATOR COMPLIED. | | | | | | 10-11) COMPLIED. | | | | | | 12) 2ND REQUEST, SHEET S-2 INDICATES THE VARIOUS TYPES | | | OF MATERIALS TO BE USED IN CONSTRUCTING THE RAISED | | | PLATFORMS PLEASE SEE SECTION:410.4 PLATFORM | | | CONSTRUCTION.PERMANENT PLATFORMS SHALL BE CONSTRUCTED | | | OF MATERIALS AS REQUIRED FOR THE TYPE OF CONSTRUCTION | | | OF THE BUILDING IN WHICH THE PERMANENT PLATFORMS IS | | | LOCATED. PERMANENT PLATFORMS ARE PERMITTED TO BE | | | CONSTRUCTED OF FIRE-RETARDANT-TREATED WOOD FOR TYPE I, | | | II, AND IV CONSTRUCTION WHERE THE PLATFORMS ARE NOT | | | MORE THAN 30 INCHES (762 MM) ABOVE THE MAIN FLOOR, AND | | | NOT MORE THAN ONE-THIRD OF THE ROOM FLOOR AREA AND NOT | | | MORE THAN 3,000 SQUARE FEET (279 M2) IN AREA. THE | | | RAISED PLATFORM MEETS THE QUALIFICATIONS ABOVE SHEET | | | S-2 DOESN?T INDICATE THAT THE WOOD IS REQUIRED TO BE | | | FIRE RETARDANT TREATED WOOD. | | | | | | 13) 2ND REQUEST, PROVIDE PRODUCT APPROVALS GLAZED | | | OPENING WILL NEED TO COMPLY WITH: 1609.1.4 PROTECTION | | | OF OPENINGS. IN WIND-BORNE DEBRIS REGIONS, EXTERIOR | | | GLAZING THAT RECEIVES POSITIVE PRESSURE IN THE LOWER 60 | | | FEET (18.3 M) IN BUILDINGS SHALL BE ASSUMED TO BE | | | OPENINGS AND THE BALANCE OF GLAZED OPENINGS IN THE REST | | | OF THE BUILDING SHALL BE ASSUMED TO BE ZERO UNLESS SUCH | | | GLAZING THAT RECEIVES POSITIVE PRESSURE IS IMPACT | | | RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT | | | COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E | | | 1886 AND ASTM E 1996, ANSI/DASMA 115 (FOR GARAGE DOORS | | | AND ROLLING DOORS) OR MIAMI-DADE TAS 201, 202 AND 203 | | | OR AAMA 506 REFERENCED THEREIN AS FOLLOWS: 1. GLAZED | | | OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE SHALL | | | MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. | | | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) | | | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL | | | MISSILE TEST. | | | | | | 13A) 2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES (3 IF THRESHOLD OR RESIDENT | | | INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS | | | ARE AS FOLLOWS: | | | A) WINDOWS FIXED | | | B) SLIDERS | | | C) GLAZED SLIDING GLASS DOORS | | | D) GLAZED EXTERIOR SWING DOORS | | | E) OVERHEAD DOOR, DOOR SCHEDULE STILL INDICATES | | | SUCH DOOR TO BE USED! | | | F) MULLIONS-HORIZONTAL FRAMING | | | G) PRE-ENGINEERED A/C STANDS | | | | | | 13B) 2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED | | | TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE | | | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER | | | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, | | | SUBMIT AN APPLICATION FOR LOCAL PRODUCTAPPROVAL OR | | | SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. | | | WWW.FLORIDABUILDING.ORG | | | | | | 13C) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA | | | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY | | | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | | | | 14)COMPLIED. | | | | | | 15) PLEASE PROVIDE COMPLIANCE WITH: 11-5.1 GENERAL. | | | EXCEPT AS SPECIFIED OR MODIFIED IN THIS SECTION, | | | RESTAURANTS AND CAFETERIAS SHALL COMPLY WITH THE | | | REQUIREMENTS OF SECTION 11-4.1 TO SECTION 11-4.35 . | | | WHERE FIXED TABLES (OR DINING COUNTERS WHERE FOOD IS | | | CONSUMED BUT THERE IS NO SERVICE) ARE PROVIDED, | | | AT LEAST 5 PERCENT, 206X.05= 11 SPACES BUT NOT LESS | | | THAN ONE, OF THE FIXED TABLES (OR A PORTION OF THE | | | DINING COUNTER) SHALL BE ACCESSIBLE AND SHALL COMPLY | | | WITH SECTION 11-4.32 AS REQUIRED IN SECTION 11-4.1.3 | | | (18). | | | | | | 16-19) COMPLIED. | | | | | | | | | 20A) 2ND REQUEST,THE PLANS ALSO LACK FIRE SPRINKLER | | | PLANS THIS IS A FIRE SPRINKLED BUILDING PLEASE PROVIDE | | | THE FIRE SPRINKLER PLAN. THE ORIGINAL DESIGN TOOK THE | | | AREA INCREASES FOR A FIRE SPRINKLED BUILDING. SINCE THE | | | AREA INCREASES WERE GIVEN UNDER 504.2 ALL TENANT | | | IMPROVEMENTS ALSO NEED TO COMPLY WITH THE FIRE | | | SPRINKLER REQUIREMENTS. | | | | | | 20B) 2ND REQUEST,NOTE: 2604.1.2(4) BE PROTECTED BY | | | AN AUTOMATIC SPRINKLER SYSTEM. WHERE THE COOLER OR | | | FREEZER IS WITHIN A BUILDING, BOTH THE COOLER OR | | | FREEZER AND THAT PART OF THE BUILDING IN WHICH IT IS | | | LOCATED SHALL BE SPRINKLED. | | | | | | 21) ENERGY CALCULATIONS:(1) ARE NOT SIGNED NOR SEALED | | | BY THE DESIGNER, | | | (2)UNDER THE DOOR HEADING THE LINES ARE BLANK! PLEASE | | | FILL IN THE DOOR INFORMATION. | | | | | | | | | 22)PLEASE CORRECT THE PERMIT APPLICATION THE CORRECT | | | PCN (PROPERTY CONTROL NUMBER) IS LISTED ON THE PERMIT | | | APPLICATION BUT THE WRONG ADDRESS. 701 S. ROSEMARY IS | | | LOCATED ON THE WEST SIDE OF THE STREET. THE EAST SIDE | | | IS 700 S. ROSEMARY. | | | | | | 23) ANEW COMMENT, THE PLANS SHEET A-3 DOESN?T INDICATE | | | WHAT TYPE OF TENANT IS LOCATED IN THE NEXT TENANT | | | SPACE, IF A A-2 ASSEMBLY IS THE NEXT TENANT A 1 HR WALL | | | IS OK BUT IF A BUSINESS OR MERCANTILE A 2HR OCCUPANCY | | | SEPARATION WALL WILL BE REQUIRED, SEE TABLE 302.3.2. | | | | | | 24) CHANGE IN OCCUPANCY:BEFORE A PERMIT TO CONSTRUCT, | | | MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH | | | COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED | | | BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED | | | TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025 | | | FOR MORE INFORMATION. | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS | | | A RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | BUILDING PLAN REVIEW II | | | JIM WITMER C. B. O. | | | | | | | | | | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | TAVERNA OPA 2NDT REVIEW.DOC |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-06-07 |
Time |
15:27 |
Rev Time |
6.00 |
| Received By |
jwitmer |
Date |
2007-06-07 |
Time |
15:27 |
Sent To |
|
|
| Notes |
| 2007-06-07 15:28:55 | BUILDING PLAN REVIEW | | | PERMIT: 07040835 | | | ADD: 701 S ROSEMARY # 232 | | | CONT: L. DAVIS CONSTRUCTION | | | TEL: (561)718-8161 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) COVERSHEET BLDG DESIGN DATA PLEASE CORRECT NUMBER OF | | | STORIES, NOTE THE PARKING GARAGE AND B BLOCK RETAIL ARE | | | CONSIDERED ONE BUILDING, NOT TWO. | | | | | | 4) COVERSHEET CODE SUMMARY, 2.1 OCCUPANCY GROUP PLEASE | | | CORRECT SEE | | | SECTION 303 OF THE FBC- BUILDING. | | | | | | 5) COVERSHEET FAILS TO MENTION IN THE CODE SUMMARY THE | | | 2006 EXISTING BUILDING CODE AND THE LEVEL OF ALTERATION | | | TO BE COMPLETED UNDER THIS PERMIT. | | | | | | 6) SHEET A-1 IN THE GENERAL NOTES# 1 PLANS INDICATE | | | THAT CONSTRUCTION SHALL FOLLOW THE ?FLORIDA RESIDENTIAL | | | CODE? PLEASE CORRECT. | | | | | | 7) SHEET A-1 GENERAL NOTE# 10 INDICATES COMPLIANCE WITH | | | THE STATES | | | ENERGY SECTION 5024? PLEASE PROVIDE ADDITIONAL | | | INFORMATION 106.1.2*. | | | | | | 8) SHEET A-1 GENERAL NOTE# 15 PLEASE CORRECT THE | | | EDITION THESTANDARDS REFERENCEINTHE 2006 | | | FBC-BUILDING CHAPTER 35. | | | UPDATE 8A) ASTM C-83 | | | 8B) ACI 318-83 | | | 8C) ACI 301-84 | | | 8D) ACI 531-79 (REVISE THE STANDARD | | | NUMBER AND EDITION) | | | | | | 9) PLEASE PROVIDE A LIFE SAFETY PLAN INDICATING THE | | | EGRESS PATTERNS, PROVIDE WIDTH OF THE AISLE AND | | | OCCUPANT LOADS THROUGH TO THE EXIT DISCHARGE. PLANS | | | ALSO INCLUDE AN ELEVATOR TO THE FIRST FLOOR, PLEASE | | | PROVIDE ADDITIONAL INFORMATION ON THE FIRST FLOOR | | | LEVEL, IS THE ELEVATOR USED BY ANY OTHER TENANT? | | | DOES THE ELEVATOR COMMUNICATE WITH THE EXTERIOR, AND IF | | | SO HOW/ | | | PLEASE INCORPORATE : | | | 11-5.3 ACCESS AISLES. ALL ACCESSIBLE FIXED TABLES SHALL | | | BE ACCESSIBLE BY MEANS OF AN ACCESS AISLE AT LEAST 36 | | | INCHES (915 MM) CLEAR BETWEEN PARALLEL EDGES OF TABLES | | | OR BETWEEN A WALL AND THE TABLE EDGES. | | | 1013.4.2 SEATING AT TABLES. | | | 1013.4.2.2 TABLE AND SEATING ACCESSWAY WIDTH. | | | 1013.4.2.3 TABLE AND SEATING AISLE ACCESSWAY LENGTH. | | | | | | 10) SHEET A-3 INDICATES THE USE OF A SINGLE STAIR ON TO | | | TIERED PLATFORMS SEE SECTION: 1003.5.2 WHERE CHANGE IN | | | ELEVATION OF 12 INCHES (305 MM) OR LESS OCCURS IN EXIT | | | ACCESS CORRIDORS, EXITS AND EXIT DISCHARGE, RAMPS | | | COMPLYING WITH SECTION 1010 SHALL BE PROVIDED. | | | | | | 11) 1003.5.1 WHERE A CHANGE IN LEVEL MEANS OF EGRESS | | | NOT EXCEEDING 21 INCHES (533 MM) IS ACHIEVED BY A | | | STAIR, THE MINIMUM TREAD DEPTH OF SUCH STAIR SHALL BE | | | 13 INCHES (330 MM) AND THE PRESENCE AND LOCATION OF | | | EACH STEP SHALL BE READILY APPARENT. | | | | | | 12)SHEET S-2 INDICATES THE VARIOUS TYPES OF MATERIALS | | | TO BE USED IN CONSTRUCTING THE RAISED PLATFORMS PLEASE | | | SEE SECTION:410.4 PLATFORM CONSTRUCTION.PERMANENT | | | PLATFORMS SHALL BE CONSTRUCTED OF MATERIALS AS REQUIRED | | | FOR THE TYPE OF CONSTRUCTION OF THE BUILDING IN WHICH | | | THE PERMANENT PLATFORMS IS LOCATED. PERMANENT PLATFORMS | | | ARE PERMITTED TO BE CONSTRUCTED OF | | | FIRE-RETARDANT-TREATED WOOD FOR TYPE I, II, AND IV | | | CONSTRUCTION WHERE THE PLATFORMS ARE NOT MORE THAN 30 | | | INCHES (762 MM) ABOVE THE MAIN FLOOR, AND NOT MORE THAN | | | ONE-THIRD OF THE ROOM FLOOR AREA AND NOT MORE THAN | | | 3,000 SQUARE FEET (279 M2) IN AREA. WHERE THE SPACE | | | BENEATH THE PERMANENT PLATFORM IS USED FOR STORAGE OR | | | ANY OTHER PURPOSE OTHER THAN EQUIPMENT, WIRING OR | | | PLUMBING, THE FLOOR CONSTRUCTION SHALL NOT BE LESS THAN | | | 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. WHERE THE | | | SPACE BENEATH THE PERMANENT PLATFORM IS USED ONLY FOR | | | EQUIPMENT, WIRING OR PLUMBING, THE UNDERSIDE OF THE | | | PERMANENT PLATFORM NEED NOT BE PROTECTED. | | | | | | 13) GLAZED OPENING WILL NEED TO COMPLY WITH: 1609.1.4 | | | PROTECTION OF OPENINGS. IN WIND-BORNE DEBRIS REGIONS, | | | EXTERIOR GLAZING THAT RECEIVES POSITIVE PRESSURE IN THE | | | LOWER 60 FEET (18.3 M) IN BUILDINGS SHALL BE ASSUMED TO | | | BE OPENINGS AND THE BALANCE OF GLAZED OPENINGS IN THE | | | REST OF THE BUILDING SHALL BE ASSUMED TO BE ZERO UNLESS | | | SUCH GLAZING THAT RECEIVES POSITIVE PRESSURE IS IMPACT | | | RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT | | | COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E | | | 1886 AND ASTM E 1996, ANSI/DASMA 115 (FOR GARAGE DOORS | | | AND ROLLING DOORS) OR MIAMI-DADE TAS 201, 202 AND 203 | | | OR AAMA 506 REFERENCED THEREIN AS FOLLOWS: | | | 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF | | | GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE | | | TEST. | | | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) | | | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL | | | MISSILE TEST. | | | | | | 13A) FL BLD CODE 1609.1.4: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES (3 IF THRESHOLD OR RESIDENT | | | INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS | | | ARE AS FOLLOWS: | | | A) WINDOWS FIXED | | | B) SLIDERS | | | C) GLAZED SLIDING GLASS DOORS | | | D) GLAZED EXTERIOR SWING DOORS | | | E) GLAZED SWING EXTERIOR DOORS | | | F) OVERHEAD DOORS | | | G) MULLIONS-HORIZONTAL FRAMING | | | H) PRE-ENGINEERED A/C STANDS | | | | | | 13B) PRODUCT APPROVALS SUBMITTED WITH PERMIT | | | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO | | | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE | | | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER | | | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, | | | SUBMIT AN APPLICATION FOR LOCAL PRODUCTAPPROVAL OR | | | SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. | | | WWW.FLORIDABUILDING.ORG | | | | | | 13C) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 14)2006 FL. BLD CODE 1603.1.4 THE FOLLOWING | | | INFORMATION RELATED TO WIND | | | SHALL BE SHOWN ON THE CONSTRUCTION DRAWINGS, | | | 1)- BASIC WIND SPEED, MPH | | | 2)- WIND IMPORTANCE FACTOR, & BUILDING CATEGORY | | | 3)- WIND EXPOSURE | | | 4)- INTERNAL PRESSURE COEFFICIENT, | | | 5)- COMPONENTS & CLADDING, THE DESIGN WIND PRESSURES IN | | | TERMS OF PSF. | | | NOTE 5 STORY BUILDING POS/ NEG PRESSURE! | | | | | | 15) PLEASE PROVIDE COMPLIANCE WITH : | | | 15A) 11-5.2 COUNTERS AND BARS. | | | WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34 | | | INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS | | | SEATED ON STOOLS OR STANDING AT THE COUNTER, A PORTION | | | OF THE MAIN COUNTER WHICH IS 60 INCHES (1525 MM) IN | | | LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE WITH | | | SECTION 11-4.32 OR SERVICE SHALL BE AVAILABLE AT | | | ACCESSIBLE TABLES WITHIN THE SAME AREA. | | | 15B) 11-5.4 DINING AREAS. | | | IN NEW CONSTRUCTION, ALL DINING AREAS, INCLUDING RAISED | | | OR SUNKEN DINING AREAS, LOGGIAS, AND OUTDOOR SEATING | | | AREAS, SHALL BE ACCESSIBLE. IN ALTERATIONS, | | | ACCESSIBILITY TO RAISED OR SUNKEN DINING AREAS, OR TO | | | ALL PARTS OF OUTDOOR SEATING AREAS IS NOT REQUIRED | | | PROVIDED THAT THE SAME SERVICES AND DECOR ARE PROVIDED | | | IN AN ACCESSIBLE SPACE USABLE BY THE GENERAL PUBLIC AND | | | ARE NOT RESTRICTED TO USE BY PEOPLE WITH DISABILITIES. | | | | | | 15C) 11-4.32 FIXED OR BUILT-IN SEATING AND TABLES. | | | 11-4.32.1 MINIMUM NUMBER. | | | FIXED OR BUILT-IN SEATING OR TABLES REQUIRED TO BE | | | ACCESSIBLE BY SECTION 11-4.1 SHALL COMPLY WITH SECTION | | | 11-4.32. | | | | | | 15D) 11-4.32.2 SEATING. | | | IF SEATING SPACES FOR PEOPLE IN WHEELCHAIRS ARE | | | PROVIDED AT FIXED TABLES OR COUNTERS, CLEAR FLOOR SPACE | | | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED. SUCH | | | CLEAR FLOOR SPACE SHALL NOT OVERLAP KNEE SPACE BY MORE | | | THAN 19 INCHES (485 MM) (SEE FIGURE 45). | | | ALL FIXED SEATING IN PUBLIC FOOD SERVICE | | | ESTABLISHMENTS, IN ESTABLISHMENTS LICENSED UNDER THE | | | BEVERAGE LAW FOR CONSUMPTION ON THE PREMISES, AND IN | | | ALL OTHER FACILITIES GOVERNED BY REFERENCE SECTION | | | 11-4.1 SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE | | | WITH THE FOLLOWING REQUIREMENTS: | | | (1) ALL AISLES ADJACENT TO FIXED SEATING SHALL PROVIDE | | | CLEAR FLOOR SPACE FOR WHEELCHAIRS. | | | (2) WHERE THERE ARE OPEN POSITIONS ALONG BOTH SIDES OF | | | SUCH AISLES, THE AISLES SHALL BE NOT LESS THAN 52 | | | INCHES (1321 MM) WIDE. | | | 11-4.32.3 KNEE CLEARANCES. | | | IF SEATING FOR PEOPLE IN WHEELCHAIRS IS PROVIDED AT | | | TABLES OR COUNTERS, KNEE SPACES AT LEAST 27 INCHES (685 | | | MM) HIGH, 30 INCHES (760 MM) WIDE, AND 19 INCHES (485 | | | MM) DEEP SHALL BE PROVIDED (SEE FIGURE 45). | | | 11-4.32.4 HEIGHT OF TABLES OR COUNTERS. | | | THE TOPS OF ACCESSIBLE TABLES AND COUNTERS SHALL BE | | | FROM 28 INCHES TO 34 INCHES (710 MM TO 865 MM) ABOVE | | | THE FINISH FLOOR OR GROUND. | | | | | | 16) THE RAISED PLATFORMS HAVE AN OCCUPANT LOAD GREATER | | | THAN 50, THAT WILL REQUIRE 2 MEANS OF EGRESS BUT THERE | | | IS ONLY ONE ACCESSIBLE RAMP. SEE TABLE 1018.2. | | | 11-4.3.10 EGRESS. | | | ACCESSIBLE ROUTES SERVING ANY ACCESSIBLE SPACE OR | | | ELEMENT SHALL ALSO SERVE AS A MEANS OF EGRESS FOR | | | EMERGENCIES OR CONNECT TO AN ACCESSIBLE AREA OF RESCUE | | | ASSISTANCE. | | | | | | 17) SHEET E2.01 INDICATES AN EXIT LIGHT AT THE BACK OF | | | THE PRIVATE MEETING ROOM ,1013.2 EGRESS THROUGH | | | INTERVENING SPACES.EGRESS FROM A ROOM OR SPACE SHALL | | | NOT PASS THROUGH ADJOINING OR INTERVENING ROOMS OR | | | AREAS, EXCEPT WHERE SUCH ADJOINING ROOMS OR AREAS ARE | | | ACCESSORY TO THE AREA SERVED; ARE NOT A HIGH-HAZARD | | | OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS | | | TRAVEL TO AN EXIT. EGRESS SHALL NOT PASS THROUGH | | | KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED FOR | | | SIMILAR PURPOSES. PLEASE CORRECT. | | | | | | 18) PLANS DO NOT PROVIDE ANY INFORMATION FOR DOOR | | | HARDWARE OR PANIC HARDWARE, SEE 1008.1.9. | | | | | | 19)SHEETS A7-8 SHOW A CUT SECTION THROUGH THE | | | RESTAURANT BUT THERE IS NO INFORMATION AS TO WALL AND | | | CEILING FINISHES, PLEASE PROVIDE INFORMATION COMPLYING | | | WITH: 803.1 GENERAL. | | | INTERIOR WALL AND CEILING FINISHES SHALL BE CLASSIFIED | | | IN ACCORDANCE WITH ASTM E 84. SUCH INTERIOR FINISH | | | MATERIALS SHALL BE GROUPED IN THE FOLLOWING CLASSES IN | | | ACCORDANCE WITH THEIR FLAME SPREAD AND SMOKE-DEVELOPED | | | INDEX. | | | CLASS A: | | | FLAME SPREAD INDEX 0-25; SMOKE-DEVELOPED INDEX 0-450. | | | CLASS B: | | | FLAME SPREAD INDEX 26-75; SMOKE-DEVELOPED INDEX 0-450. | | | CLASS C: | | | FLAME SPREAD INDEX 76-200; SMOKE-DEVELOPED INDEX | | | 0-450. | | | EXCEPTION: MATERIALS, OTHER THAN TEXTILES, TESTED IN | | | ACCORDANCE WITH SECTION 803.2. | | | 803.2INTERIOR WALL OR CEILING FINISHES OTHER THAN | | | TEXTILES. | | | INTERIOR WALL OR CEILING FINISHES, OTHER THAN TEXTILES, | | | SHALL BE PERMITTED TO BE TESTED IN ACCORDANCE WITH NFPA | | | 286. FINISHES TESTED IN ACCORDANCE WITH NFPA 286 SHALL | | | COMPLY WITH SECTION 803.2.1. | | | | | | 20) THE PLANS ALSO LACK FIRE SPRINKLER PLANS THIS IS A | | | FIRE SPRINKLED BUILDING PLEASE PROVIDE THE FIRE | | | SPRINKLER PLAN. NOTE: 2604.1.2(4) BE PROTECTED BY AN | | | AUTOMATIC SPRINKLER SYSTEM. WHERE THE COOLER OR FREEZER | | | IS WITHIN A BUILDING, BOTH THE COOLER OR FREEZER AND | | | THAT PART OF THE BUILDING IN WHICH IT IS LOCATED SHALL | | | BE SPRINKLED. | | | | | | 21) IT ALSO APPEARS THAT THE ENERGY CALCULATIONS SEE | | | CHAPTER 13 OF THE FBC BUILDING. | | | | | | 22) SEE ELECTRICAL COMMENTS ABOUT ARCHITECTURAL AND | | | ENGINEERING DEFICIENCIES, SIGNATURES, DELINQUENCIES, | | | CERTIFICATE OF AUTHORIZATION, ETC. | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS | | | A RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | BUILDING PLAN REVIEW II | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | TAVERNA OPA 1ST REVIEW.DOC |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
12 |
Status |
P |
Date |
2008-10-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-10-29 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-10-29 |
Time |
15:29 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
11 |
Status |
F |
Date |
2008-10-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-10-10 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-10-10 |
Time |
17:05 |
Sent To |
PC |
|
| Notes |
| 2008-10-10 17:06:06 | | | | ** DENIED REVIEW** | | | | | | | | | 1) NOTE: PLEASE BE SURE ALL CIRCUITING ON PLANS | | | COORDINATE. | | | SOME EXAMPLES: | | | L-76, L-51, L2-39, 37,ETC | | | | | | THERE ARE OTHERS. ALL PANEL SCHEDULE ON RECORD PLANS | | | NEED TO COORDINATE. SPOKE WITH DESIGNER AND IS AWARE OF | | | THE ITEMS. WILL NEED TO GET REVISED PANEL SCHEDULES | | | FROM ELECTRICAL CONTRACTOR FOR WHAT WAS ACTUALLY DONE | | | ON-SITE SO REVISED PLANS AND PANEL SCHEDULES CAN BE | | | ACCURATE FOR RECORD PLANS. | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
10 |
Status |
F |
Date |
2008-10-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-10-08 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-10-08 |
Time |
11:13 |
Sent To |
PC |
|
| Notes |
| 2008-10-08 11:13:23 | ** DENIED ** | | | | | | 1) NOTE: ALL REVISIONS AND CHANGES TO PLANS NEED TO BE | | | IDENTIFIED BY CLOUDS, TRIANGLES ETC. THE PLANS DO NOT | | | CONTAIN ANY INDICATION OF REVISIONS MADE TO THE MOST | | | RECENT PLANS ON FILE. | | | FOR EXAMPLE: REVISED CIRCUITING FROM THE LAST REVISED | | | PLAN ON FILE WOULD BE INDICATED HOWEVER ONLY FOR THOSE | | | CIRCUITS. AS SHOWN THERE ARE NO REVISIONS. PLEASE CALL | | | TO GO OVER. | | | FOR EXAMPLE: AS THE LATEST PLANS ON FILE SUPPOSEDLY | | | CONTAIN THE LATEST REVISED CIRCUITING, WE WOULD ONLY | | | NEED THE REVISED PANEL SCHEDULE. | | | | | | | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
P |
Date |
2008-09-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-09-10 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-09-10 |
Time |
11:48 |
Sent To |
PC |
|
| Notes |
| 2008-09-10 11:48:58 | ** REDLINED/PROVISO ** | | | | | | 1) NOTE: STILL NEED TO SUBMIT REVISED PANEL SCHEDULES | | | TO COORDINATE WITH THE REVISED CIRCUITING ON POWER | | | PLANS. | | | 408.4 | | | FBC 106.1.1,106.3.5.1.2 | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
P |
Date |
2008-05-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-05-06 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-05-06 |
Time |
11:12 |
Sent To |
PC |
|
| Notes |
| 2008-05-06 11:13:05 | REV FOR PROJECT FOR FINAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
F |
Date |
2008-04-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-04-07 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-04-07 |
Time |
13:02 |
Sent To |
PC |
|
| Notes |
| 2008-04-07 13:02:50 | ** DENIED** | | | | | | 1) NOTE: PLEASE SEE THE SUBMITTED LIGHTING SUBMITTALS | | | ARE NOT REQUIRED FOR ELECTRICAL REVIEW. ANY CHANGES TO | | | LIGHTING CONTROLS OR TO ORIGINAL PROPOSED LIGHTING | | | WHICH WAS ON PERMITTED SET OF PLANS WOULD REQUIRE | | | REVISED ELECTRICAL PLANS. | | | FOR INFORMATIONAL PURPOSE: THE LIGHTING SUBMITTALS | | | SUBMITTED DID NOT CONTAIN SHOP DRAWING REVIEW STAMP | | | FROM ENGINEER OF RECORD. | | | ** AS NOTED ABOVE, ANY CHANGES IN LIGHTING CONTROLS OR | | | LIGHTING FROM THE ORIGINAL PLANS NEEDS TO HAVE REVISED | | | ELECTRICAL PLANS. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
N |
Date |
2008-03-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-03-04 |
Time |
12:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-03-04 |
Time |
12:35 |
Sent To |
P |
|
| Notes |
| 2008-03-04 12:36:14 | **SWITCH GEAR SUBMITTALS NOT NEEDED. | | | EQUIPMENT AND LISTINGS TO BE VIF, 110.3, 90.7 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2008-01-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-28 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-28 |
Time |
16:52 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-10-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-23 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-23 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2007-10-23 10:53:57 | ***PROVISO/REVISION NEEDED *** | | | | | | 1) NOTE: PLEASE SEE THE LIGHTING IN THE KITCHEN BACK | | | HALLWAY AREA NEEDS TO MEET BOTH THE LIFE SAFETY ASPECT | | | OF THE CODE IN NFPA-101 7.8/ALONG WITH FBC AND CHAPTER | | | 13 FOR LIGHTING CONTROLS. | | | AS SHOWN ON PLANS WHEN THE SCHEDULED LIGHTING SYSTEM | | | TURNS OFF THERE IS NO DEVICE OR LIGHTING PROVIDED FOR | | | THE PATH TO THE OVER RIDE DEVICES. | | | THERE IS ALSO NO *NIGHT-LIGHTS* SHOWN IN THESE SAME | | | AREAS. THIS WAS GONE OVER IN MEETING AND AGREED THESE | | | LIGHTING FIXTURES OR OCCUPANCY SENSORS WILL BE | | | PROVIDED. | | | PLEASE CALL IF THERE ARE ANY QUESTIONS. | | | | | | 2) NOTE: REDLINED METHOD OF LIGHTING CALCULATIONS FROM | | | METHOD *A* TO METHOD *C* AS GONE OVER IN MEETING. | | | | | | ** PLEASE REVISE THE ABOVE ALONG WITH ANY OTHER | | | REVISIONS BEFORE ROUGH ELECTRICAL INSPECTION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-09-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-27 |
Time |
18:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-27 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2007-09-27 18:48:48 | ** DENIED** | | | | | | *** PLEASE SEE THE FOLLOWING COMMENTS BELOW. | | | THERE HAVE BEEN SEVERAL ON PLANS WITH RESPECT TO | | | LIGHTING CONTROLS AND NEW COMMENTS BELOW WHICH MAY NOT | | | BE WORD FOR WORD THE SAME FROM PREVIOUS REVIEW STILL | | | HAVE TO DO WITH CHAPTER 13 COMPLIANCE. AS SOME NEW | | | METHODS/CHANGES IN CONTROLS HAVE BEEN REVISED THIS HAS | | | CREATED A COUPLE OF NEW COMMENTS ON PLANS. | | | ** PLEASE KNOW IF ALL OTHER REVIEWS PASS WITHOUT ANY | | | COMMENTS, THE FOLLOWING MAY BE SET UP AS A PROVISO | | | HOWEVER WOULD NEED TO BE REVISED WITH THE GIVEN TIME. | | | THIS IS ONLY IF ALL OTHER TRADES ARE OK WITH PLANS AND | | | PROJECT IS READY TO ISSUE FOR PERMIT. | | | THE ELECTRICAL DESIGNER HAS BEEN CONTACTED. | | | | | | 1) NOTE:PLEASE THE LOCATIONS OF LIGHTING CONTROLS | | | NEED TO MEET 13-415.1.ABC.1.1. PLEASE SEE FOR EXAMPLE | | | THE REAR DOOR ENTRANCE WHICH DOES NOT CONTAIN ANY OVER | | | RIDE. THERE ARE SEVERAL LOCATIONS WHICH SHOW STANDARD | | | 3-WAY AND 4-WAY SWITCHES HOWEVER WITH OUT AN OVER RIDE | | | DEVICE OF SYSTEM, THESE SWITCHES WOULD BE INOPERABLE. | | | PLEASE SEE THE BATHROOMS WHICH INDICATE A STANDARD | | | SWITCH FOR CONTROL OF LIGHTING ALONG WITH AN OCCUPANCY | | | DEVICE. IF AN OCCUPANT LEAVES THE BATHROOM AND TURNS | | | THIS SWITCH OFF THEN ANY REMAINING OCCUPANTS WOULD HAVE | | | NO LIGHTING TO MAKE WAY TO THE SWITCH TO TURN LIGHTING | | | BACK ON. THIS SCENARIO WAS GONE OVER WITH DESIGNER AND | | | ADJUSTMENTS TO TYPE OF FIXTURES AND POSSIBLE NIGHTS | | | WILL BE REVISED ON PLANS. | | | | | | 2) NOTE: PLEASE SEE LIFE SAFETY CODE NFPA-101 7.8 AND | | | 7.9 WITH RESPECT TO EGRESS LIGHTING UNDER NORMAL AND | | | EMERGENCY CONDITIONS. THE LIGHTING WHICH IS BEING | | | CONTROLLED FROM SYSTEM WHEN BEING SHUT DOWN LEAVES | | | SEVERAL AREAS IN TOTAL DARKNESS WITHOUT LENDING ANY | | | LIGHTING FOR EGRESS TO AREAS FOR THE OVER RIDE | | | CONTROLS. THIS IS ALSO TO COORDINATE WITH THE COMMENT | | | #1 ABOVE WITH RESPECT TO RESTROOMS AND HALLWAY AREAS. | | | THESE LOCATIONS WERESPECIFICALLY GONE OVER WITH THE | | | DESIGNER AND ADJUSTMENTS ARE BEING MADE TO LIGHTING | | | FIXTURE TYPES AND/OR CONTROLS. | | | | | | 3) NOTE: PLEASE SEE THE RISER IS STILL IN QUESTION AS | | | SHOWN. THIS REVISED RISER HAS COMPLETELY CHANGED FROM | | | THE PREVIOUS REVIEWED PLANS. PLEASE SEE THE RISER SHOWS | | | THIS SERVICE BEING TAPPED FROM A GUTTER WHICH IS TAPPED | | | FROM THE LOAD SIDE GUTTER WHICH IS FED FROM METERS AND | | | DISCONNECTS. THIS IS UNCLEAR HOW THIS GUTTER BEING | | | SHOWN ON THE LOAD SIDE OF THE METERS AND TENANT MAINS | | | FEED THIS SECONDARY GUTTER? | | | AS SHOWN THIS DOES NOT SEEM POSSIBLE. THIS REVIEW WILL | | | PLACE CALL TO LAND-LORD AND REQUEST A MEETING ON-SITE | | | FBC 106.1.2/106.3.5.1.2, NEC 215.5, 230.70 ETC | | | THIS IS COORDINATION OF PLANS AND RISER. | | | | | | 4) NOTE: PLEASE SEE COMMENTS FROM FIRE REVIEWER AND | | | POSSIBLE BUILDING AS THE FIRE ALARMS PLANS FP-1 SHEET | | | WAS NOT SIGNED, DATED OR SEALED BY THE ENGINEER OF | | | RECORD. THIS IS REQUIRED FOR BASE BUILDING PLANS EVEN | | | THOUGH THIS IS UNDER A SEPARATE PERMIT. AS MENTIONED ON | | | PREVIOUS REVIEW THIS IS STILL REQUIRED UNDER BASE BUILD | | | OUT PLANS. | | | PLEASE ALSO SEE THE FIRE SPRINKLER SHEET FP3.1 AS THIS | | | SHEET ONLY CONTAINS A PRINTED SEAL OF SOME SORT ON | | | TITLE BLOCKS. PLEASE SEE THE SEAL AS SHOWN WOULD NOT | | | MEET FAC 61G15-23.002. | | | PLEASE BE SURE THIS IS ADDRESS EVEN IF COMMENTS ARE NOT | | | FROM OTHER REVIEWS. IF THESE ITEMS ARE THE ONLY ITEMS | | | ON THESE SHEETS FOR COMPLIANCE, THEN THESE DESIGN | | | PROFESSIONALS MAY COME INTO THIS OFFICE AND SIGN, DATE | | | AND SEAL PLANS. | | | | | | 5) NOTE: PLEASE DO NOT ATTACH PRODUCT APPROVALS AND | | | SUPPORTING DOCUMENTS DOWN THE LEFT HAND SIDE OF PLANS. | | | THESE HAVE BEEN REMOVED BY THIS REVIEWER ON BOTH SETS. | | | THESE DOCUMENTS SHOULD BE PLACED INTO TWO SEPARATE | | | PACKAGES. | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-08-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-25 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-24 |
Time |
19:17 |
Sent To |
|
|
| Notes |
| 2007-08-25 09:50:47 | | | | 2007-08-25 09:50:47 | | | | | | *** DENIED2ND REVIEW *** | | | | | | *** PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW | | | ARE STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW | | | COMMENTS BASED ON SOME INFORMATION ON REVISED PLANS. | | | SOME INFORMATION IS ONLY NOW BEING SUBMITTED FOR | | | REVIEW. | | | | | | 1) NOTE: PLEASE SEE THE RESPONSE LETTER FROM THE DESIGN | | | TEAM QUOTES THIS REVIEWER'S COMMENTS AND THEN CONTAINS | | | A RESPONSE BELOW. PLEASE SEE THERE ARE NUMEROUS | | | INSTANCES WHERE THE TYPEWRITTEN NOTES OF THIS | | | REVIEWER'S COMMENTS ARE NOT WHAT WERE TYPED IN THE | | | PREVIOUS REVIEW. | | | SOME ARE TYPED AS STATING THE REVIEWER HAS REQUIRED | | | CERTAIN ITEMS WHICH ARE NOT THE CASE. PLEASE SEE THE | | | FOLLOWING FOR EXAMPLE. | | | **RESPONSE TO COMMENT #2 FROM PREVIOUS REVIEW IN | | | LETTER. | | | PART OF THE REVIEW COMMENT MENTIONS: *PLANS ONLY SHOW | | | STANDARD SWITCHES* AND THE RESPONSE LETTER TYPES | | | *PLEASE ONLY SHOW STANDARD SWITCHES*. | | | THIS WOULD COMPLETELY CHANGE THE CODE REQUIRED ITEM. IF | | | THE RESPONSE LETTER IS GOING TO *QUOTE* REVIEWER'S | | | COMMENTS PLEASE BE SURE TO ACCURATELY PLACE ACTUAL | | | NOTES. | | | | | | 2) NOTE: PLEASE SEE COMMENT #2 FROM PREVIOUS REVIEW | | | WHICH REQUESTED COMPLIANCE WITH THE FBC CHAPTER 13. | | | THIS IS THE FIRST REVIEW FOR SOME INFORMATION SUBMITTED | | | FOR CHAPTER 13. | | | PLEASE SEE THERE ARE MANY ITEMS WHICH STILL NEED TO BE | | | ADDRESSED: | | | PLEASE SEE NOTE #3 BELOW WITH RESPECT TO THE ENERGY | | | CALCULATIONS. | | | | | | 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED | | | DO NOT REFLECT THE SAME INFORMATION AS SHOWN ON PLANS. | | | THE INPUT DATA REPORT CONTAINS INPUT OF LIGHTING | | | LUMINARIES WHICH ARE NOT ON PLANS AND ALSO THE PLANS | | | CONTAIN LIGHTING FIXTURES WHICH ARE NOT INPUTTED INTO | | | THE REPORT. | | | PLEASE SEE SHEET 2 OF THE IDR WHICH CONTAINS ONLY SEVEN | | | LUMINARIES, HOW IS THIS POSSIBLE WHEN THE PLANS | | | INDICATE A SUBSTANTIALLY HIGHER AMOUNT OF FIXTURES? | | | PLEASE SEE THE WATTAGE OF THESE DO NOT CORRELATE WITH | | | THE FIXTURE LEGEND AND FIXTURES ON PLANS. | | | PLEASE SEE THE LIGHTING POWER DENSITIES CALCULATIONS | | | INDICATE DIFFERENT WATTAGES THAN ON PLANS AND WHAT IS | | | SHOWN ON CALCULATIONS. 13-415.1.A, 13-415.2 | | | PLEASE SEE NO EXTERIOR LIGHTING WAS ENTERED YET PLANS | | | CONTAIN THESE LIGHTING FIXTURES 13-415.2.ABC.1.3. THE | | | CALCULATIONS AS SUBMITTED ARE UNDER METHOD A. THE PLANS | | | ARE INDICATING THE TABLE 13-415.2.C.1 | | | PLEASE EXPLAIN AND COORDINATE. | | | | | | 4) NOTE:PLEASE SEE NO INFORMATION IS SHOWN FOR THE | | | MINIMUM LOADS FOR TRACK LIGHTING AS REQUIRED AND STATED | | | IN THE PREVIOUS REVIEW. THIS SECTION OF THE CODE WAS | | | SPECIFICALLY QUOTED ON THE PREVIOUS REVIEW AS TRACK | | | LIGHTING INPUT IS OFTEN NOT CORRECT IN | | | DESIGNS.13-415.2.ABC.1.2. | | | | | | 5) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED | | | INFORMATION AND DESIGNS FOR 13-415.1.ABC.1.1, .1.2 AND | | | .1.3. | | | PLEASE SEE ONLY SOME INFORMATION WAS SUBMITTED AND | | | SHOWN ON PLANS. | | | PLEASE SEE THE PLANS STATE THERE IS GOING TO THE A | | | LIGHTING CONTROL PANEL HOWEVER NO INFORMATION WAS SHOWN | | | FOR SCHEDULING , ALL OVER RIDE LOCATIONS, AND MAXIMUM | | | TIMES ON OVER RIDES AND DEVICES FOR LIGHTING CONTROLS. | | | PLANS INDICATE SEVERAL OS TYPE DEVICES, HOWEVER NO | | | MAXIMUM TIMES ON THESE DEVICES. | | | PLEASE SEE THE LOCATIONS REQUIRED FOR OVER RIDES WERE | | | NOT CLEAR AT ALL OF THE LOCATIONS REQUIRED. | | | COULD NOT LOCATE CONTROLS FOR DISPLAY OR ACCENT | | | LIGHTING WHICH IS SHOWN ON PLANS. | | | PLEASE SEE THERE ARE SEVERAL LOCATIONS ON PLANS WHICH | | | STILL ONLY CONTAIN STANDARD CONTROL SWITCHES. (SOME OF | | | THESE LOCATIONS ARE REDLINED) | | | PLEASE INCLUDE INFORMATION FOR ZONES AND SQ FT AS | | | REQUIRED PER 13-415.1.ABC.1.2 | | | PLEASE SEE THE LIGHTING PLANS INDICATE A NOTE #2 ON THE | | | COOLER LIGHTS WHICH MENTIONS TO WIRE THROUGH LIGHTING | | | CONTROL PANEL. HOW IS THIS POSSIBLE WHEN THE LIGHTING | | | CONTROL PANEL IS 120/208V AND THE CIRCUIT NOTED IS | | | 277/480V? PLEASE COORDINATE ALL.(KITCHEN LIGHTING NOTED | | | ON THIS SAME CIRCUIT ON PANEL SCHEDULE) | | | PLEASE COMPLETE THE FIXTURE LEGEND WITH ALL INFORMATION | | | AT THIS TIME. SOME ARE NOTED TO BE *SELECTED BY OWNER* | | | HOWEVER THE MINIMUM ARE REQUIRED AT THIS TIME. THESE | | | CAN ALWAYS BE REVISED AT A LATER DATE IF NEEDED.( | | | PREVIOUS NOTE #18) | | | PLEASE SEE ALL OF CHAPTER 13, THERE ARE MANY ITEMS | | | WHICH CAN NOT BE REVIEWED AT THIS TIME. | | | FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION. | | | | | | 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED | | | IN FACT CONTAIN A PHOTO-COPIED SIGNATURE ON THE | | | CERTIFICATION SHEETS WHEN THESE ARE REQUIRED TO BE | | | SIGNED, SEALED AND DATED PER FLORIDA STATUTES 471.025, | | | 481.221. | | | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND | | | FBC 13-103.1.1.1 | | | PLEASE ALSO SEE THE OWNER AGENT IS NOT SIGNED ON | | | SHEETS. | | | | | | 7) NOTE:PLEASE SHOW ALL DEVICE LOCATIONS AND LEVELS | | | FOR ADA COMPLIANCE FOR HORN, STROBES. PER FBC | | | 11.4-28.1, .2 AND .3(4). | | | ** PLEASE KNOW EVEN AS THE FIRE ALARM PERMIT WILL BE | | | SEPARATE ALONG WITH FIRE SPRINKLER, THE BASE BUILDING | | | PLANS MUST SHOW THE MINIMUM REQUIRED INTENDED SYSTEM. | | | FBC 106.3.5.1.1 | | | THIS NOTE WAS NOTE #9 ON THE PREVIOUS REVIEW AND | | | REMAINS. THE RESPONSE FROM THE ENGINEERING FIRM STATES | | | *NOT PROVIDED* BY FIRM. | | | THE RESPONSE FROM THE ARCHITECT MENTIONS TO SEE A3.2 | | | HOWEVER PLEASE SEE THE DEVICES AS SHOWN ON THIS SHEET | | | DO NOT MEET THE LOCATIONS AS REQUIRED. PLEASE ALSO SEE | | | THE SYMBOL BEING USED FOR HORNS, STROBES OR | | | HORN/STROBES IS NOT THAT OF THE STANDARD USE IN THE | | | INDUSTRY AND ON PLANS. | | | PLEASE SUBMIT COMPLETED INFORMATION FOR MINIMUM DESIGN | | | FOR BASE FIRE ALARM DEVICES ON BASE BUILD OUT PLANS AS | | | REQUIRED PER FS 633 AND 106.3.5.1.2 OF THE FBC | | | ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF WEST | | | PALM BEACH. | | | | | | 8) NOTE:PLEASE SEE THE PREVIOUS NOTE #13 IS STILL IN | | | NEED OF ADDRESSING. THE ELECTRICAL PLANS AS REQUIRED DO | | | NOT CONTAIN THE REQUIRED AND NEEDED INFORMATION FOR THE | | | TRANSFORMER INSTALLATION AS PREVIOUSLY REQUESTED. A | | | NOTE ON THE ELECTRICAL SHEET MENTIONS TO SEE THE | | | ARCHITECTURAL AND/OR STRUCTURAL SHEETS HOWEVER NO | | | COMPLETED INFORMATION WAS LOCATED ON THESE SHEETS. THIS | | | IS A LIFE SAFETY, FIRE, AND PROPERTY HAZARD ISSUE. | | | SERIOUS INJURY OR DEATH COULD RESULT IN AN INSTALLATION | | | OF EQUIPMENT OF THIS NATURE WHICH IS IMPROPERLY | | | INSTALLED. THIS INFORMATION IS NEEDED ON PLANS FOR THE | | | CODE REQUIRED INSTALLATION AT THIS TIME. PLANS MAY NOT | | | SIMPLY STATE TO SEE OTHER SHEETS. PLEASE KNOW THAT | | | THESE UNITS CREATE A SUBSTANTIAL AMOUNT OF HEAT AND | | | BEING LOCATED NEAR EASILY IGNITABLE MATERIALS AND | | | COMBUSTIBLES IS STRICTLY PROHIBITED. PLEASE SEE 110.26, | | | 240.24A, C AND D, 450.9, 450.13, 450.21-450.27. AS NO | | | INFORMATION SPECIFICALLY IS SHOWN ON THE TRANSFORMER | | | SECTIONS .21-.27 ARE BEING NOTED. PLEASE KNOW THIS | | | PROPOSED LOCATION ABOVE THE AREA AS STATED IS NOT | | | PERMITTED. | | | PLEASE SEE NO STRUCTURAL INFORMATION WAS SUBMITTED FOR | | | SUPPORT AS THE PLANS STATE THIS WILL BE LOCATED OFF THE | | | FLOOR. | | | ** CAREFUL CONSIDERATION IS TO BE GIVEN ON THE | | | LOCATION. | | | | | | *** PREVIOUS REVIEW NOTE**** | | | PLEASE SEE THE PLANS ARE MISSING THE LOCATION FOR THE | | | REQUIRED DISCONNECT AND TRANSFORMER. PLEASE SEE 110.26 | | | AND 450 AS NO REVIEW FOR THIS CAN BE DONE AT THIS | | | TIME. | | | PLEASE SEE 450.9, 450.13 ETC AS THE TRANSFORMER MAY NOT | | | BE ABOVE CEILING. | | | PLEASE ALSO SUBMIT STRUCTURAL ENGINEERED DETAIL AT THIS | | | TIME FOR THE LOCATION AND HOW THIS UNIT WILL BE | | | INSTALLED. | | | ** PLANS CURRENTLY MENTION THE LOCATION OF THE | | | TRANSFORMER IS TO BE DETERMINED BY THE BUILDING | | | ENGINEER, HOWEVER THE NEC DETERMINES LOCATION BASED ON | | | WIRING METHODS, CLEARANCES, ETC. THE STRUCTURAL ELEMENT | | | WILL THEN BE THE CONSIDERATION FOR NEEDED STRUCTURAL | | | SUPPORT ETC. | | | ** SOME ELECTRICAL CODE COMPLIANCE ITEMS CAN NOT BE | | | REVIEWED AT THIS TIME** | | | | | | | | | 9) NOTE: THIS NOTE REMAINS FROM THE PREVIOUS REVIEW. | | | PLEASE SEE THE RESPONSE MENTIONS THERE ARE NO OTHER | | | LOADS ON THIS MAIN. THIS NOTED EXISTING MAIN IS NOT | | | KNOWN BY THIS OFFICE BEING DIRECTLY FROM FPL WITH ITS | | | OWN SERVICE AS BEING SHOWN ON THE REVISED RISER. PLEASE | | | KNOW THAT A FIELD INSPECTION WILL NEED TO BE PERFORMED | | | TO GO OVER THE SERVICES AND EQUIPMENT AT THIS LOCATION. | | | THIS OFFICE WILL NEED TO BE IN CONTACT WITH THE | | | LANDLORDS OFFICE TO OBTAIN ACCESS TO LOCATION. | | | AS REQUESTED FROM PREVIOUS REVIEW: | | | **PLEASE SUBMIT THE COMPLETED LOAD CALCULATIONS ON | | | SERVICE AND THE ADDED LOAD TO THE EXISTING MAIN SERVICE | | | WITH NEW LOAD ADDED. | | | THE PLANS CURRENTLY ONLY SHOW THE LOAD CALCULATIONS ON | | | *L*. | | | 220 (ALL), 215.5, CONTINUOUS LOADS PER 215.3, 230.42 | | | ETC | | | NEC 220 WAS GIVEN IN GENERAL AS THERE ARE TOO MANY | | | SPECIFIC CODE SECTIONS WHICH APPLY FROM 220. (TRACK | | | LTS, LIGHTING, RECEPTACLES) ETC. | | | FBC 106.3.5.1.2, 106.1.2. | | | ** PLEASE BE SURE TO OBTAIN ANY INFORMATION FROM OTHER | | | POSSIBLE BUILD-OUTS FOR NEW TENANTS WHICH *WILL* AFFECT | | | THE LOAD CALCULATIONS ON MAIN SERVICE. | | | | | | 10) NOTE:THE PREVIOUS REVIEW NOTE #20 REQUESTED | | | COORDINATION OF SHUNT TRIP BREAKERS FOR EQUIPMENT. MOST | | | OF THIS SEEMS TO BE DONE HOWEVER PLEASE SEE THE | | | EQUIPMENT SCHEDULES ON E1.02 AND BE SURE ALL | | | COORDINATE. | | | PLEASE KNOW MANY OF THESE ITEMS SEEM TO BE MISPRINTS | | | FOR ACTUAL LOADS ETC. | | | REDLINED SHEETS ON ONE SET. FBC 106.1.2 FOR | | | COORDINATION. | | | MAY CALL TO GO OVER. | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE INDICATE THE REQUIRED SHUNT OF ALL | | | ELECTRICAL UNDER HOODS PER NFPA-96. | | | PLEASE SEE SOME EQUIPMENT IS ALREADY BEING NOTED AS | | | HAVING THE SHUNT TRIP BREAKERS, BUT NOT ALL. | | | | | | 11) NOTE: THIS NOTE REMAINS FROM PREVIOUS REVIEW NOTE # | | | 22. THE ENGINEER'S FIRM RESPONSE MENTIONS *NOT | | | PROVIDED* PER FIRM. | | | THE ARCHITECT'S RESPONSE MENTIONS THIS WAS COMPLETED IN | | | TITLE BLOCKS HOWEVER UPON REVIEW OF SEVERAL SHEETS | | | INCLUDING CHECKING THE TITLE BLOCKS OF OTHER TRADES, | | | THIS WAS NOT COMPLETED AS NEEDED AND AS REQUESTED. | | | PLEASE BE SURE THE TITLE BLOCKS REFLECT THE ADDRESS AND | | | SUITE/UNIT NUMBER FOR NEW BUILD-OUT. FAC 61G15-23.002, | | | 61G1-16.004 | | | | | | 12) NOTE: PLEASE CLARIFY HOW IT IS DIMMERS ARE BEING | | | SHOWN ON LIGHTING WHICH IS LOCATED IN THE EGRESS | | | PATHS. | | | PLEASE SEE LS 101 7.8 AND 7.9. | | | PLEASE PROVIDE THE MINIMUM LEVELS ARE NEEDED ON THESE | | | PATHS. | | | PLEASE SEE FAC 61G15-33.004. | | | FBC 106.1.2 | | | | | | 13) NOTE: PLEASE SEE ATTACHED COPY OF FS 553.80(2)(B) | | | WITH RESPECT TO DESIGN PROFESSIONALS AND REPEAT | | | COMMENTS FOR CODE COMPLIANCE. | | | PLEASE KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME. | | | PLEASE ALSO KNOW THAT ONE SET OF ELECTRICAL PLANS AND | | | ENERGY CALCULATIONS ARE BEING RETAINED BY THIS OFFICE | | | AT THIS TIME. | | | | | | AS STATED ON THE PREVIOUS REVIEW: | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-08-25 07:55:04 | 2007-08-25 07:55:04 | | | | | | REVIEW CONTINUED | | 2007-08-24 21:04:56 | 2007-08-24 21:04:56 | | | | | | PLANS ARE IN ELEC FOR REVIEW. | | | REVIEW TO CONTINUE ON 8/25, NOTES WILL FOLLOW ONCE | | | REVIEW IS COMPLETE. | | | PLANS WILL BE GOING INTO A *F* STATUS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-05-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-05-10 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-05-10 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2007-05-10 15:45:23 | ** UNSAT ** | | | | | | ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA | | | BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED | | | BY THE CITY OF WEST PALM BEACH. | | | | | | 1) NOTE: PLEASE KNOW THAT CODE ADOPTED AS OF DECEMBER | | | 8TH, 2006 IS LISTED AS FOLLOWS. | | | PLEASE SEE THERE ARE PARTS OF THE PLANS WHICH REFLECT A | | | 2004 NEC AND A 2002 NEC. | | | PLEASE KNOW THAT THERE WAS NOT ANY 2004 NEC. PLEASE | | | LIST THE FOLLOWING CODES AT A MINIMUM ON THE ELECTRICAL | | | PAGES AND ARCHITECTURAL SHEETS. SOME CODES ARE ALREADY | | | REFLECTED ON PLANS, HOWEVER WILL BE AS FOLLOWS FOR | | | INFORMATION AS SOME NEED TO BE CHANGED. 2005 NFPA-70 | | | (NEC). | | | 2003 NFPA- 101 | | | 2002 NFPA-72 | | | 2004 FBC W/2006 REVISIONS. | | | AS STATED, SOME OF THESE ARE DONE ALREADY. PLEASE | | | COORDINATE. | | | | | | 2) NOTE: PLEASE SEE FBC CHAPTER 13. | | | PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS/PERFORMANCE | | | CALCULATIONS. 13-415.1.AB.1.1, 13-415.2 | | | PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING LINE OR | | | LOW VOLTAGE. | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR LIGHTING | | | CONTROLS, OVER RIDES, OVER RIDE LOCATION, OVER RIDE | | | TIMES, SCHEDULING ETC. | | | PLANS ONLY INDICATE STANDARD SWITCHES. | | | PLEASE SEE ZONES BASED ON SQ FT. | | | PLEASE SEE ALL OF CHAPTER 13, THERE ARE MANY ITEMS | | | WHICH CAN NOT BE REVIEWED AT THIS TIME. | | | | | | 3) NOTE: PLEASE SEE THE OCCUPANCY STATED ON PLANS IS | | | STATED A *COMMERCIAL*? PLEASE VERIFYAND SEE ANY | | | COMMENTS FROM OTHER TRADES FOR THIS. | | | FBC 106.1.2 | | | | | | 4) NOTE: ** NOT A COMMENT FOR FORMICA AND ASSOC. PLEASE | | | SEE THE CERTIFICATE OF AUTHORIZATION NUMBER LISTED FOR | | | THE STRUCTURALLY ENGINEERING FIRM IS *DELINQUENT* AS OF | | | THIS REVIEW DATE. PLEASE SEE THE ATTACHED PRINT OUT | | | FROM THE DEPARTMENT OF BUSINESS AND PROFESSIONAL | | | REGULATION WHICH SHOWS THIS. | | | PLEASE ALSO SEE THE ADDRESS ON TITLE BLOCKS IS NOT THAT | | | AS LISTED WITH THE STATE OF FLORIDA. | | | ** PLEASE KNOW THE ABOVE IS REQUIRED WHETHER OR NOT | | | COMMENT IS MADE BY ANY OTHER TRADE. | | | | | | 5) NOTE: PLEASE BE SURE ALL RAISED SEALS FOR THE | | | ARCHITECT OF RECORD ARE CLEAR AND VISIBLE WITH ALL | | | INFORMATION ON SAID SEALS AS REQUIRED PER FAC 61G1-16. | | | PLEASE SEE THERE ARE SOME SEALS WHICH ARE NOT | | | CLEAR/VISIBLE WITH SOME INFORMATION. | | | | | | 6) NOTE: PLEASE KNOW THAT ALL LOW VOLTAGE WILL BE | | | REQUIRED TO BE UNDER SEPARATE PERMIT. | | | | | | 7) NOTE: PLEASE SEE THE CODE SECTION FOR GFI PROTECTION | | | FOR ALL RECEPTACLES IN KITCHEN AREAS SHOULD BE 210.8B3. | | | THIS SECTION SEEMS TO BE MISPRINTED ON PLANS. | | | | | | 8) NOTE: PLEASE SEE 408.4 WHICH REQUIRES ALL CIRCUITS | | | TO BE SPECIFIC TO ALL ROOMS, AREAS, LOCATIONS AND | | | CIRCUIT SPECIFIC. PLEASE SEE THE FOLLOWING TEXT FROM | | | THE NEC. | | | **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO | | | REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT | | | SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND | | | CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE | | | CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE | | | MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE, | | | SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN | | | THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS. | | | IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH | | | CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE | | | IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING | | | ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP | | | RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES | | | CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR | | | ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL | | | REQUIRED BY THIS SECTION.* | | | 408.4, 310.16, 240.4 ETC | | | FBC 106.3.5.1.2 | | | | | | 9) NOTE: PLEASE SHOW ALL DEVICE LOCATIONS AND LEVELS | | | FOR ADA COMPLIANCE FOR HORN, STROBES. PER FBC | | | 11.4-28.1, .2 AND .3(4). | | | ** PLEASE KNOW EVEN AS THE FIRE ALARM PERMIT WILL BE | | | SEPARATE ALONG WITH FIRE SPRINKLER, THE BASE BUILDING | | | PLANS MUST SHOW THE MINIMUM REQUIRED INTENDED SYSTEM. | | | FBC 106.3.5.1.1 | | | | | | 10) NOTE: PLEASE SEE THE CIRCUIT L2-36 WHICH APPEARS TO | | | BE IN PLACE FOR THE REQUIRED SIGN CIRCUIT, HOWEVER | | | PLEASE SEE 600.5 AS THE LOAD OF 1200VA PER OUTLET , MAY | | | NOT FEED ANY OTHER OUTLETS. PLEASE ALSO INDICATE IF | | | INDEED THIS IS FOR THE SIGN CIRCUIT(S). | | | | | | 11) NOTE: PLEASE SEE L2-31 WHICH IS SHOWN FEEDING | | | HOUSE/COMMON AREA WHICH MAY NOT BE FED FROM THE TENANT | | | SPACE. THIS WOULD BE SHOWN FROM A HOUSE PANEL CIRCUIT. | | | 210.25, 240.24 | | | | | | 12) NOTE: PLEASE SEE THE MINIMUM CLEARANCES ARE NOT | | | SHOWN FOR THE ELECTRICAL PANELS. IN FACT THERE ARE | | | ITEMS/RACKS OR SOME OTHER NON-ELECTRICAL EQUIPMENT | | | SHOWN ON PLANS WHICH ARE SHOWN IN THE AREA ABOUT | | | ELECTRICAL EQUIPMENT WHICH IS NOT PERMITTED. 110.26 | | | | | | 13) NOTE: PLEASE SEE THE PLANS ARE MISSING THE LOCATION | | | FOR THE REQUIRED DISCONNECT AND TRANSFORMER. PLEASE SEE | | | 110.26 AND 450 AS NO REVIEW FOR THIS CAN BE DONE AT | | | THIS TIME. | | | PLEASE SEE 450.9, 450.13 ETC AS THE TRANSFORMER MAY NOT | | | BE ABOVE CEILING. | | | PLEASE ALSO SUBMIT STRUCTURAL ENGINEERED DETAIL AT THIS | | | TIME FOR THE LOCATION AND HOW THIS UNIT WILL BE | | | INSTALLED. | | | ** PLANS CURRENTLY MENTION THE LOCATION OF THE | | | TRANSFORMER IS TO BE DETERMINED BY THE BUILDING | | | ENGINEER, HOWEVER THE NEC DETERMINES LOCATION BASED ON | | | WIRING METHODS, CLEARANCES, ETC. THE STRUCTURAL ELEMENT | | | WILL THEN BE THE CONSIDERATION FOR NEEDED STRUCTURAL | | | SUPPORT ETC. | | | ** SOME ELECTRICAL CODE COMPLIANCE ITEMS CAN NOT BE | | | REVIEWED AT THIS TIME** | | | | | | 14) NOTE: PLEASE INDICATE IF THE PANEL *L* SECTION 1 | | | CONTAINS FEED-THRU LUGS OR IS THERE OVER CURRENT | | | PROTECTION IN THIS PANEL WHICH FEEDS PANEL *L* SECTION | | | 2? | | | FBC 106.1.2 | | | | | | 15) NOTE: PLEASE SEE THE TAPPED CONDUCTORS ON THE | | | SECONDARY SIDE OF THE TRANSFORMER ARE NOT OF SUFFICIENT | | | SIZE PER 310.16, 240.21C. | | | PLEASE SEE THAT THE TAPPED CONDUCTORS SHALL TERMINATE | | | IN OCP WHICH LIMITS THE LOAD ON THE CONDUCTOR WHICH IT | | | IS RATED. (MAY NOT GO TO NEXT SIZE UP) (600MCM MIN). | | | | | | 16) NOTE: PLEASE COORDINATE THE RISER AND THE PANEL | | | SCHEDULES AS THE PANELS *L* SECTIONS ONE AND TWO ARE | | | BOTH BEING SHOWN AS 225AMP PANELS, YET THE RISER SHOWS | | | 400AMP OVER CURRENT PROTECTION FEEDING THESE PANELS?? | | | PLEASE SEE THE LOADS ON PANEL *L* AFTER DE-RATING | | | EXCEED THAT OF THE RATING OF THESE PANELS. | | | | | | 17) NOTE: PLEASE SEE THE EQUIPMENT GROUNDING CONDUCTORS | | | ON RISER DIFFER FROM THOSE INDICATED ON PANELS *L* ONE | | | AND TWO. | | | PLEASE CORRELATE. | | | FBC 106.1.2 | | | | | | 18) NOTE: PLEASE COMPLETE THE FIXTURE LEGEND WITH ALL | | | INFORMATION ON FIXTURES BEING INSTALLED AND THE NUMBER | | | OF FIXTURES. PLEASE SEE THE COMMENT ABOVE WITH RESPECT | | | TO THE FBC CHAPTER 13. | | | FBC 106.1.2, 106.3.5.1.2 | | | | | | 19) NOTE: PLEASE SUBMIT THE COMPLETED LOAD CALCULATIONS | | | ON SERVICE AND THE ADDED LOAD TO THE EXISTING MAIN | | | SERVICE WITH NEW LOAD ADDED. | | | THE PLANS CURRENTLY ONLY SHOW THE LOAD CALCULATIONS ON | | | *L*. | | | 220 (ALL), 215.5, CONTINUOUS LOADS PER 215.3, 230.42 | | | ETC | | | FBC 106.3.5.1.2, 106.1.2. | | | ** PLEASE BE SURE TO OBTAIN ANY INFORMATION FROM OTHER | | | POSSIBLE BUILD-OUTS FOR NEW TENANTS WHICH *WILL* AFFECT | | | THE LOAD CALCULATIONS ON MAIN SERVICE. | | | | | | 20) NOTE: PLEASE SEE INDICATE THE REQUIRED SHUNT OF ALL | | | ELECTRICAL UNDER HOODS PER NFPA-96. | | | PLEASE SEE SOME EQUIPMENT IS ALREADY BEING NOTED AS | | | HAVING THE SHUNT TRIP BREAKERS, BUT NOT ALL. | | | | | | 21) NOTE: PLEASE SEE 424.3B FOR THE MINIMUM OCP FOR THE | | | AHU/HEAT. THE MINIMUM OCP IS TO BE SIZED AT 125%. | | | | | | 22) NOTE: PLEASE BE SURE THE TITLE BLOCKS REFLECT THE | | | ADDRESS AND SUITE/UNIT NUMBER FOR NEW BUILD-OUT. FAC | | | 61G15-23.002, 61G1-16.004 | | | | | | 23) NOTE: PLEASE SEE THE BASED BUILDING PLANS HAD THE | | | *DEMO PLANS* REMOVED FOR THE INTERIOR DEMO PERMIT, | | | THESE SHEETS NEED TO BE REPLACED IN THIS SET OF PLANS. | | | | | | **PLEASE KNOW THERE MAY BE NEW COMMENTS IN THE FUTURE | | | AS SOME ITEMS CAN NOT BE REVIEWED AT THIS TIME. | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
8 |
Status |
P |
Date |
2008-05-19 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-05-19 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-05-19 |
Time |
10:30 |
Sent To |
B1 |
|
| Notes |
| 2008-05-19 11:10:49 | *****REVISION #6, DATED 4/22/08, APPROVED***** | | | | | | REVISED PLAN SHEETS A-3, A-3.1, A-3.2, D-1, D-2, AND | | | S-1 THRU S-6 WERE REVIEWED;SHEET A-3.2 STAMPED, | | | INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
7 |
Status |
P |
Date |
2008-04-01 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-04-01 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-04-01 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2008-04-01 16:28:13 | *****REVISION #5, DATED 3/10/08, APPROVED***** | | | | | | REVISED PLAN SHEETS A-3, A-7, A-8, AND D-1 WERE | | | REVIEWED;HOWEVER, NO FIRE-STAMPING NEEDED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2008-02-01 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-02-01 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-02-01 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2008-02-01 11:25:11 | REVISION DATED 1/11/08 STAMPED LIFE SAFETY SHEET A-3.2. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2008-01-31 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-01-31 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-01-31 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2008-01-31 15:04:09 | REVISED SHEET FA1.01 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2007-10-23 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-23 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-23 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2007-10-23 15:43:50 | *****APPROVED***** | | | | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED;PLAN SHEETS A-3.2, A-4, E2.01, FA1.01, | | | AND FP-3.1 WERE STAMPED, INITIALED, AND DATED |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2007-10-11 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-10-11 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-10-11 |
Time |
13:03 |
Sent To |
|
|
| Notes |
| 2007-10-11 13:08:21 | ***DENIED*** | | | | | | 02.) OK | | | | | | 08.) OK | | | | | | 09.) OK | | | | | | NEW COMMENT: | | | | | | 1) FIRE PROTECTION AND ALARM SYSTEMS REQUIRE A | | | PROFESSIONAL ENGINEER TO SIGN, SEAL AND DATE ALL PLANS, | | | SPECIFICATIONS ETC TO BE FILED FOR PUBLIC RECORD. FP-1 | | | AND FP-3.1 | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-08-29 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-08-29 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-29 |
Time |
10:17 |
Sent To |
E |
|
| Notes |
| 2007-08-29 10:48:42 | *****UNSAT***** | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 02.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET.NO ADDRESS IN THE TITLE | | | BLOCK FOR THE M, P, AND E PLAN SHEETS | | | | | | 08.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL | | | BE CLASS A, CLASS B, OR CLASS C.IT IS NOTED ON SHEET | | | A-5 THAT THE INTERIOR WALLS FINISH TO BE CLASS "A" , | | | HOWEVER THE CLASSIFICATION OF THE CEILING FINISH IS NOT | | | NOTED | | | | | | 09.WILL THE SCOPE OF WORK HAVE CAUSE FOR FIRE | | | SPRINKLERS TO BE MODIFIED?IF SO SEPARATE PLANS WILL | | | BE REQUIRED.PLEASE ACKNOWLEDGE | | | | | | | | | | | | | | | TO EXPIDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW / WHERE EACH ITEM WAS ADDRESSED. | | | | | | CAPT. MICHAEL WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-06-08 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-06-08 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-06-08 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2007-06-08 11:16:34 | *****DENIED***** | | | | | | | | | 01.THE SITE LOCATION INDICATED ON THE COVER SHEET | | | SHOWS THIS STRUCTURE AT THE SOUTHEAST CORNER OF | | | HIBISCUS STREET AND SOUTH ROSEMARY AVENUE.THE | | | NUMERICAL ADDRESS FOR THIS SITE WOULD BE 700 INSTEAD OF | | | 701.PLEASE VERIFY | | | | | | 02.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET.BE ADVISED THAT THE ZIP | | | CODE FOR THIS AREA IS 33401 NOT 33305(SEE S SHEETS) | | | | | | 03.PLEASE INDICATE IF THIS ASSEMBLY OCCUPANCY IS | | | EXISTING OR NEW. | | | | | | 04.THE REMOVAL AND/OR REPLACEMENT OF BUILDING | | | MATERIALS & SUPPLIES SHALL NOT HINDER OR INTERFERE WITH | | | EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY | | | THEREOF (INCLUDING STREETS, ROADS, FIRE LANES). | | | | | | 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS | | | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT | | | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 06.SHOW/DISPLAY THE SUITE NUMBER ON THE THE | | | APPROPIATE EXTERIOR ELEVATION AS TO BE DISTINGUISHABLE | | | FROM OTHER SUITESOF THIS BUILDING. | | | | | | 07.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN | | | AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS | | | SHALL BE PERMITTED TO BE PROVIDED WITH PANIC HARDWARE | | | OR FIRE EXIT HARDWARE. | | | | | | 08.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL | | | BE CLASS A, CLASS B, OR CLASS C.BE SPECIFIC | | | | | | 09.WILL THE SCOPE OF WORK HAVE CAUSE FOR FIRE | | | SPRINKLERS TO BE MODIFIED?IF SO SEPARATE PLANS WILL | | | BE REQUIRED. | | | | | | 10.SHOW THE LOCATION OF THE 2A:10BC FIRE EXTINGUISHER | | | WHICH SATISFY 75' TRAVEL DISTANCE. | | | | | | | | | TO EXPIDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW / WHERE EACH ITEM WAS ADDRESSED. | | | | | | CAPT. MICHAEL WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
N |
Date |
2007-10-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-10-29 |
Time |
18:04 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-10-29 |
Time |
18:04 |
Sent To |
|
|
| Notes |
| 2007-10-29 18:05:53 | SEPARATE GAS PERMIT REQUIRED. SUBMIT PLANS, MANUF. | | | SPECIFICATION SHEETS AND ALL REQUIRMENTS FROM GAS | | | PERMIT APPLICATION CHECK LIST WITH PERMIT APPLICATION. | | | ITEM 29 NOT APPROVED WITHOUT LISTING, MANUF. | | | INSTALLATION INSTRUCTIONS & CERTIFICATION OF BTU LOAD | | | PER HR. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2007-10-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-10-27 |
Time |
17:17 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-10-27 |
Time |
17:17 |
Sent To |
|
|
| Notes |
| 2007-10-27 17:23:23 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | **********NEW COMMENT********** | | | | | | 1D. NEW ITEM #29 NOT APPROVED. PER SECTION 301.3 | | | APPLIANCES REGULATED BY THIS CODE SHALL BE LISTED AND | | | LABELED. PLEASE PROVIDE LISTING FOR THIS PRODUCT AND | | | SHOW GAS LOAD PER HOUR AS INDICATED BY TESTING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2007-10-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-10-03 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-10-02 |
Time |
12:40 |
Sent To |
|
|
| Notes |
| 2007-10-03 14:12:13 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | | | | 1. SHTS P1.01 & P2.01 SEPARATE GAS PERMIT REQUIRED. THE | | | FOLLOWING INFORMATION IS REQUIRED FOR REVIEW PRIOR TO | | | ISSUING THE GAS PERMIT: | | | | | | A. OK | | | B. OK | | | C. OK | | | D. OK | | | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE NOTED, BUT THE ARCHITECT INDICATED THAT | | | FORMICA WILL RESPOND TO COMMENT. PLEASE COMMUNICATE | | | WITH ARCHITECT. | | | ******RESPONSE NOTED, BUT ITEM 59 (TILT SKILLET), AND | | | THE WATER HEATER MANUF SHEETS HAVE NOT BEEN SUBMITTED. | | | | | | F. N/A | | | G. N/A | | | H. OK | | | 10. OK | | | | | | **********NEW COMMENTS********** | | | | | | 1C. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33).THE MANUF SHEETS SUBMITTED DO NOT REFLECT | | | THE BTU LOADS INDICATED ON THE RISER DIAGRAM FOR ALL | | | BUT ITEM 31. PLEASE MAKE SURE THAT THE GAS RISER | | | DIAGRAM REFLECTS THE MANUF SHEETS FOR THE BTU LOADS. | | | ALSO MAKE SURE THE TOTAL BTU LOAD IS CORRECT. | | | | | | 2C. SHOW THE REGULATORS ON THE GAS RISER DIAGRAM. THE | | | SHUT OFF VALVE SHALL BE UPSTREAM OF THE REGULATORS AND | | | A UNION IS REQUIRED IF THE REGULATOR IS NOT AT THE END | | | OF A RUN. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR | | | THE REGULATOR BEING USED. SECTIONS 106.1.2. &409.4. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY.A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2007-08-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-08-27 |
Time |
18:55 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-08-27 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2007-08-27 18:56:22 | DENIED | | | | | | SEE COMMENTS FROM PLUMBING REVIEW THIS DATE. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2007-06-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-06-07 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-06-07 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2007-06-07 11:24:49 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | 1. SHTS P1.01 & P2.01 SEPARATE GAS PERMIT REQUIRED. THE | | | FOLLOWING INFORMATION IS REQUIRED FOR REVIEW PRIOR TO | | | ISSUING THE GAS PERMIT: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | | | | B. TYPE OF GAS, (LP OR NATURAL). | | | | | | C. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). (TO BE DETERMINED WHEN | | | COMMENT (A) IS ADDRESSED. | | | | | | D. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | F. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | G. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | H. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
24 |
Status |
N |
Date |
2008-10-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-24 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-24 |
Time |
16:44 |
Sent To |
E |
|
| Notes |
| 2008-10-24 16:45:03 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
23 |
Status |
N |
Date |
2008-10-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-10 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-10 |
Time |
14:26 |
Sent To |
E |
|
| Notes |
| 2008-10-10 14:26:28 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
22 |
Status |
N |
Date |
2008-10-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-03 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-03 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2008-10-03 16:34:32 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
21 |
Status |
N |
Date |
2008-09-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-04 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-04 |
Time |
10:34 |
Sent To |
E |
|
| Notes |
| 2008-09-04 10:34:45 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
20 |
Status |
N |
Date |
2008-05-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-19 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-19 |
Time |
09:41 |
Sent To |
FIRE |
|
| Notes |
| 2008-05-12 11:04:20 | TO "MWILLIAMS" DESK--EXPEDITED-- |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
19 |
Status |
N |
Date |
2008-05-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-12 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-12 |
Time |
11:01 |
Sent To |
P |
|
| Notes |
| 2008-05-12 11:01:51 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
18 |
Status |
N |
Date |
2008-05-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-06 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-06 |
Time |
15:06 |
Sent To |
B |
|
| Notes |
| 2008-05-06 15:06:52 | TO "SHILL" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
17 |
Status |
N |
Date |
2008-04-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-30 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-30 |
Time |
14:03 |
Sent To |
E |
|
| Notes |
| 2008-04-30 14:03:22 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
16 |
Status |
N |
Date |
2008-04-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-30 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-30 |
Time |
11:55 |
Sent To |
M |
|
| Notes |
| 2008-04-30 11:56:10 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
15 |
Status |
N |
Date |
2008-04-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-04 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-04 |
Time |
14:58 |
Sent To |
P |
|
| Notes |
| 2008-04-04 14:59:12 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
14 |
Status |
N |
Date |
2008-04-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-04 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-04 |
Time |
10:34 |
Sent To |
E |
|
| Notes |
| 2008-04-04 10:34:52 | TO "DPALMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2008-03-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-13 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-13 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2008-03-13 11:24:27 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2008-03-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-05 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-05 |
Time |
10:18 |
Sent To |
B |
|
| Notes |
| 2008-03-05 10:18:37 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2008-02-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-28 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-28 |
Time |
10:47 |
Sent To |
E |
|
| Notes |
| 2008-02-28 10:49:34 | TO "E" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2008-02-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-25 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-25 |
Time |
09:04 |
Sent To |
B |
|
| Notes |
| 2008-02-25 09:04:50 | TO "JWITMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2008-02-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-21 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-21 |
Time |
11:32 |
Sent To |
B |
|
| Notes |
| 2008-02-21 11:33:18 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2008-01-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-25 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-01-25 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2008-01-25 16:10:01 | TO "COMM" BD#9--EXPEDITED-- |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2008-01-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-25 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-01-25 |
Time |
15:50 |
Sent To |
P |
|
| Notes |
| 2008-01-25 15:51:04 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2008-01-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-25 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-01-25 |
Time |
15:47 |
Sent To |
FIRE |
|
| Notes |
| 2008-01-25 15:47:34 | TO "F" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-01-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-25 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-01-25 |
Time |
15:33 |
Sent To |
E |
|
| Notes |
| 2008-01-25 15:34:21 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-10-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-10-19 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-10-19 |
Time |
15:49 |
Sent To |
|
|
| Notes |
| 2007-10-23 09:30:09 | TO "COMM" BD#48 | | 2007-10-19 15:50:13 | WAITING FOR "COMM" BD--EXPEDITED-- |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-25 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-25 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2007-09-25 10:29:45 | TO "COMM" BD#45--EXPEDITED-- | | 2007-09-25 10:19:14 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-08-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-07 |
Time |
20:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-07 |
Time |
20:39 |
Sent To |
|
|
| Notes |
| 2007-08-24 14:24:09 | TO "COMM" BD#33--EXPEDITED PERMIT-- | | 2007-08-07 20:39:23 | PLANS WAITING FOR COMM BOARD. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-06-08 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-06-08 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-04-24 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2007-05-04 09:52:50 | TO "COMM" BD#40 | | 2007-04-24 16:01:36 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2008-05-01 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-05-01 |
Time |
14:42 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-05-01 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2008-05-01 14:43:21 | REVISION TO MECH. PLAN PAGE M1.01. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2007-10-24 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-10-24 |
Time |
09:29 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-10-24 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2007-10-24 09:29:56 | ADDITIONAL MECHANICAL PERMITS REQUIRED FOR | | | (A) WALK-IN-COOLER | | | (B) KITCHEN HOOD | | | (C) FIRE SUPPRESSION | | | ** SUBMIT PLANS WITH PERMIT APPLICATION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2007-10-10 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-10-10 |
Time |
10:59 |
Rev Time |
1.30 |
| Received By |
tgordon |
Date |
2007-10-10 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2007-10-10 11:09:06 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | | | *** DENIED *** | | | 1) FIRM LICENSE NUMBER IN THE TITLE BLOCK FOR A.J.O. | | | ARCH. IS INCORRECT SEE RED LINE ON PLANS, PLEASE | | | CORRECT PER FAC 61G1-16.004 TITLE BLOCK. | | | | | | 2) PAGE M2.01 AIR BALANCE SCHEDULE HAS INCORRECT | | | INFORMATION IN IT, BATH EXHAUST SHOWS 500 SHOULD SHOW | | | 550 (EF-1 50CFM'S AND TWO EF-2 AT 250 CFM'S EACH =550 | | | CFM'S). ALSO THE TOTALS FOR O/A, R/A, AND PRESSURE/CFM | | | ARE INCORRECT, PLEASE CORRECT AND COMPLY WITH 2004 FBC | | | 13-409.1.ABC.3.6.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
|
Date |
2007-10-05 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-10-05 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-10-05 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2007-10-05 15:25:01 | PUT BACK ON SHELF FOR TOM GORDON. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-08-28 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-08-28 |
Time |
09:45 |
Rev Time |
2.50 |
| Received By |
tgordon |
Date |
2007-08-28 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2007-08-28 10:03:54 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA | | | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). | | | | | | *** DENIED *** | | | 1) INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT | | | (FIRM LICENSE AND JOB ADDRESS) ON EACH PAGE AS NOTED IN | | | LAST REVIEW 5-10-07 NOTE #7.SEE FAC 61G1-16.004 TITLE | | | BLOCK. | | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | | (2) FIRM LICENSE NUMBER. | | | (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS" | | | SEE CITY WPB AMEND. 106.1.1). | | | (4) DATE PREPARED. | | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | | THE DOCUMENT. | | | | | | 2) ENERGY CALCULATIONS ARE A PHOTO COPY. ENERGY | | | CALCULATIONS NEED TO BE SIGNED AND SEALED BY A | | | ARCHITECT OR ENGINEER, SEE 4004 FBC 13-103.1.1.1. | | | | | | 3) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 4) NEED TO SHOW THE EER OF THE A/C EQUIPMENT IN THE | | | "AIR CONDITIONING UNIT DATA" ON PAGE M2.01, SEE FBC | | | 13-407.1.ABC.3.2.1. | | | | | | 5) PAGE M2.01 AIR BALANCE SCHEDULE SHOWS THE BUILDING | | | AT A POSITIVE PRESSURE OF 2180. PLEASE SHOW COMPLIANCE | | | WITH 2004 FBC 13-409.1.ABC.3.6.1 NONRESIDENTIAL KITCHEN | | | SPACES. | | | NONRESIDENTIAL KITCHEN SPACE AND AREAS IN DINING ROOMS | | | OR OPEN MALLS WHERE A KITCHEN EXHAUST HOOD IS REQUIRED | | | BY NFPA 96 SHALL COMPLY WITH THE FOLLOWING | | | REQUIREMENTS: | | | (1) BE DESIGNED WITH AN EXHAUST AIR AND MAKE UP AIR | | | BALANCE SUCH THAT THE SPACE IS NEVER UNDER A POSITIVE | | | PRESSURE, AND NEVER UNDER A NEGATIVE PRESSURE EXCEEDING | | | 0.02 INCH W.G. RELATIVE TO ALL INDOOR SPACES | | | SURROUNDING THE KITCHEN SPACE, DURING ALL COOKING | | | HOURS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-05-10 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-05-10 |
Time |
09:32 |
Rev Time |
3.00 |
| Received By |
tgordon |
Date |
2007-05-10 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2007-05-10 10:10:43 | *** DENIED *** | | | A COMPLETE MECHANICAL REVIEW CAN NOT BE DONE DUE TO A | | | LACK OF INFORMATION. | | | | | | 1) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC | | | 13-400. | | | | | | 2) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004 | | | FBC 13-407.1.ABC.1. | | | | | | 3) PLEASE SUBMIT DETAILED MANUFACTURER'S SPECIFICATION | | | SHEETS FOR A/C SYSTEMS AND INDICATE WHICH UNITS ARE | | | BEING INSTALLED. | | | | | | 4) PLEASE SUBMIT INFORMATION ON EXISTING A/C SYSTEMS | | | FOR THIS SPACE BEING REMOVED. | | | | | | 5) PLEASE PROVIDE INFORMATION REGARDING THE KITCHEN | | | EXHAUST HOODS (ENGINEERING ON HOODS NOT REQUIRED AT | | | THIS TIME) NEED SPEC'S. ON HOODS TO KNOW CORRECT | | | EXHAUST AIR AND MAKE-UP AIR IF BEING PROVIDE BY HOODS. | | | IF NOT PLEASE STATE WERE MAKE-UP AIR IS COMING FROM. | | | | | | 6) PLEASE CHECK AIR BALANCE SCHEDULE ON PAGE M2.01 TO | | | BE CERTAIN THE BUILDING NEEDS TO BE AT A +6450 TOTAL | | | PRESSURE. | | | | | | 7) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK OF | | | ALL PAGES. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
F |
Date |
2008-05-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-05-20 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-05-20 |
Time |
12:07 |
Sent To |
|
|
| Notes |
| 2008-05-20 12:15:17 | DENIED | | | REFERENCE: FBC-2004 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SHTS P2.01 & P2.02 SHOW REVISIONS 6 & 7 IN THE | | | REVISION INDEX, BUT REVISIONS 6 & 7 ARE NOT SHOWN ON | | | THE FLOOR PLAN. ALL REVISIONS SHALL BE CLOUDED AND THE | | | REVISION NUMBER INDICATED ON THE FLOOR PLAN IN ORDER TO | | | KEEP RECORD OF ALL REVISIONS AND TO HELP EXPEDITE PLAN | | | REVIEW OF REVISIONS. SECTION 106.1.3. | | | | | | 2. SHTS P2.01 & P2.O2 ALL REVISIONS TO A SIGNED, | | | SEALED, DATED PLAN SHALL BE SIGNED, SEALED & DATED BY | | | THE ENGINEER OF RECORD. SECTION 106.1. FAC | | | 61G15-23-002(1)(2) & FS 471.025. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
F |
Date |
2008-04-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-12 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-04-12 |
Time |
10:13 |
Sent To |
|
|
| Notes |
| 2008-04-12 10:17:18 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | FBC-2004 CHAPTER 1 | | | | | | 1. REVISIONS TO A SIGNED, SEALED SET OF PLANS SHALL BE | | | DRAWN, SIGNED, SEALED & DATED BY THE ENGINEER OF RECORD | | | AND SUBMITTED WITH REQUIRED TITLE BLOCKS PER FAC | | | 61G15-23.002(2) & FS 471.025 AS WELL AS SECTION | | | 106..1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2008-02-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-02-12 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-02-12 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2008-02-12 10:47:27 | REVISION DENIED | | | REFERENCE: FBC-2004 CHAPTER 1 | | | | | | 1.SHT P1.03 REVISION NUMBER 5 INDICATED IN THE REVISION | | | INDEX WAS NOT FOUND ON THE FLOOR PLAN. PLEASE CLOUD AND | | | DELTA ALL REVISIONS. SECTIONS 106.1.3 & 106.1.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2008-02-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-02-12 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-02-12 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2008-02-12 10:43:50 | REVISIONS APPROVED--SHTS P1.01, P1.02, P2.01, P2.02 | | | & P2.03. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-10-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-10-27 |
Time |
17:16 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-10-27 |
Time |
17:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2007-10-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-10-03 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-10-02 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2007-10-03 14:10:18 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FBC-2004 BUILDING | | | CITY WPB MUNICIPAL CODE | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW DATED 06-07-07. COMMENT | | | NUMBERS TO REMAIN THE SAME. | | | ******FROM PREVIOUS REVIEWS: | | | | | | 1. THE COVER AND ALL ARCHITECTURAL SHEETS REQUIRE THE | | | FIRM LICENSE NUMBER. (CERTIFICATE OF AUTHORIZATION), IN | | | THE TITLE BLOCK. FAC 61G1-16.004(2) & FS 481.219, | | | 481.2055. | | | ****RESPONSE NOTED, BUT THE FIRM LICENSE NUMBER DOES | | | NOT REFLECT THE LICENSE NUMBER ON THE FLORIDA STATE | | | DBPR WEBSITE. PLEASE UPDATE THE DBPR WEBSITE OR THE | | | TITLE BLOCK ADDRESS PRIOR TO RESUBMITTING FOR PLAN | | | REVIEW. (SEE ATTACHED SHEET). ALSO THE FIRM LICENSE | | | NUMBER AND CORRECT ADDRESS SHALL BE INDICATED ON ALL | | | SHEETS WITH ARCHITECTURAL TITLE BLOCK. ******RESPONSE | | | NOTED, BUT THE ADDRESS ON THE TITLE BLOCK DOES NOT | | | REFLECT THE ADDRESS OF RECORD ON THE FLORIDA STATE DBPR | | | WEBSITE. EITHER UPDATE THE DBPR WEBSITE OR THE TITLE | | | BLOCKS PRIOR TO RESUBMITTING FOR REVIEW. | | | | | | 2. OK | | | 3. OK | | | | | | 4. SHT A-9 SHOW COMPLIANCE WITH THE FOLLOWING: (PLEASE | | | SHOW ON ALL DETAILS OR INDICATE TYPICAL OF ALL TOILET | | | ROOMS) | | | | | | __FOR W/C'S: | | | A. OK | | | B. OK | | | C. OK | | | D. 11-4.16.5 FLUSH CONTROLS ****NOT ADDRESSED | | | ******RESPONSE NOTED BUT THE REQUIREMENT IS FOR THE | | | FLUSH CONTROL TO BE ON THE WIDE SIDE OF THE W/C. | | | DETAILS 1 & 9 SHOW THE FLUSH HANDLE ON THE WALL SIDE OF | | | THE W/C. DETAIL 9 ALSO SHOWS THE W/C 17" OFF THE WALL | | | TO THE CENTERLINE OF THE FIXTURE. 18" IS REQUIRED. (SEE | | | FIGURE 11-28). | | | E. OK | | | | | | __FOR URINALS: | | | A. 11-4.18.2 OK | | | B. 11-4.18.3 OK | | | C. 11-4.18.4 OK | | | | | | __FOR LAVS: | | | A. 11-4.19.2 OK | | | B. 11-4.19.3 OK | | | C. 11-4.19.4 OK | | | D. 11-4.19.5 FAUCETS ****NOT ADDRESSED ******RESPONSE | | | NOTED, BUT THE REQUIREMENT FOR THE LAV FAUCETS IS FOR | | | THE OPERATING CONTROLS, NOT THE HEIGHT. LEVER TYPE, | | | PUSH TYPE, ELECTRONICALLY CONTROLLED ETC. INDICATE | | | FAUCET TYPE. | | | E. 11-4.19.6 OK | | | | | | 5. OK | | | 6. OK | | | 7. OK | | | 8. OK | | | | | | 9. SHTS P1.01 & P2.01 SEPARATE GAS PERMIT REQUIRED. THE | | | FOLLOWING INFORMATION IS REQUIRED FOR REVIEW PRIOR TO | | | ISSUING THE GAS PERMIT: | | | | | | A. OK | | | B. OK | | | C. OK | | | D. OK | | | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE NOTED, BUT THE ARCHITECT INDICATED THAT | | | FORMICA WILL RESPOND TO COMMENT. PLEASE COMMUNICATE | | | WITH ARCHITECT. | | | ******RESPONSE NOTED, BUT ITEM 59 (TILT SKILLET), AND | | | THE WATER HEATER MANUF SHEETS HAVE NOT BEEN SUBMITTED. | | | | | | F. N/A | | | G. N/A | | | H. OK | | | 10. OK | | | | | | 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE | | | TO THE SPACE. PLEASE INDICATE THE LOCATION. RPZV | | | BACKFLOW SHALL BE INSTALLED A MAXIMUM 4' ABOVE THE | | | FLOOR FOR SERVICING & TESTING. | | | ****RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED | | | AND SHALL BE LOCATED MAXIMUM 4' ABOVE THE FLOOR, NOT AN | | | INLINE BACKFLOW LOCATED IN THE CEILING AS INDICATED. | | | ******RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED | | | AND SHALL BE LOCATED MAXIMUM 4' ABOVE THE FLOOR, NOT AN | | | INLINE BACKFLOW LOCATED IN THE CEILING AS INDICATED. | | | THE RPZV BACKFLOW IS STILL NOT INDICATED FOR THE | | | SPACE. | | | | | | 12. OK | | | 13. OK | | | 14. OK | | | | | | 15. TWO SETS OF PLANS SHALL BE SUBMITTED. LOOSE SHEETS | | | K-4 & K-5 SHALL BE INSERTED AS PART OF THE PLANS. THE | | | TWO PAGE "WORKSHEETS"FROM THE DEPT OF BUSINESS | | | REGULATION HOTEL & RESTURANT DIVISION SHALL BE ATTACHED | | | TO EACH SET OF PLANS ON THE SHEET STAMPED FOR REVIEW BY | | | DBPR. | | | ****RESPONSE NOTED, BUT REMOVING THE SHEETS THAT HAVE | | | THE FLORIDA STATE DBPR PLAN REVIEW STAMP IS NOT | | | APPROVED. THE REVIEWED PLANS ARE REQUIRED IN BOTH SETS | | | OF PLAN. ALSO THE TWO PAGE "WORKSHEETS" HAVE NOT BEEN | | | ATTACHED TO THE DBPR REVIEWED SHEETS AS REQUIRED FOR | | | EACH SET OF PLANS. | | | ******RESPONSE NOTED, BUT THE SHEETS WITH THE DBPR | | | SHEETS HAVE BEEN REMOVED. THE SHEETS WITH THE DBPR | | | REVIEW STAMPS ARE REQUIRED IN EACH SET OF PLANS. ALSO | | | AS INDICATED PREVIOUSLY, THE 2 PAGE "SPECIFICATION | | | WORKSHEETS" HAVE NOT BEEN ATTACHED TO THE SHEETS WITH | | | THE DBPR REVIEW STAMP. PLEASE SUBMIT SHEETS WITH THE | | | DBPR REVIEW STAMP AND ATTACH THE TWO PAGE | | | "SPECIFICATION WORKSHEETS" TO THE REVIEW SHEETS. | | | | | | 16. OK | | | | | | ***********NEW COMMENTS********** | | | | | | 1B. SHT P1.01 THE FLOOR SINK IN THE COOLER SHALL NOT | | | CONNECT TO THE SANITARY DIRECTLY. SECTION 802.1.2. | | | INDIRECT CONNECTION REQUIRED. | | | ******RESPONSE NOTED, BUT A SAFE WASTE IS NOT AN | | | INDIRECT WASTE. AN AIR GAP IS REQUIRED PER SECTION | | | 802.1.2. NO AIR GAP IS INDICATED. | | | | | | 2B. OK | | | 3B. OK | | | 4B. OK | | | | | | **********NEW COMMENTS********** | | | | | | 1C. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33).THE MANUF SHEETS SUBMITTED DO NOT REFLECT | | | THE BTU LOADS INDICATED ON THE RISER DIAGRAM FOR ALL | | | BUT ITEM 31. PLEASE MAKE SURE THAT THE GAS RISER | | | DIAGRAM REFLECTS THE MANUF SHEETS FOR THE BTU LOADS. | | | ALSO MAKE SURE THE TOTAL BTU LOAD IS CORRECT. | | | | | | 2C. SHOW THE REGULATORS ON THE GAS RISER DIAGRAM. THE | | | SHUT OFF VALVE SHALL BE UPSTREAM OF THE REGULATORS AND | | | A UNION IS REQUIRED IF THE REGULATOR IS NOT AT THE END | | | OF A RUN. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR | | | THE REGULATOR BEING USED. SECTIONS 106.1.2. &409.4. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY.A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-08-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-08-27 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-08-27 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2007-08-27 18:55:24 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FBC-2004 BUILDING | | | CITY WPB MUNICIPAL CODE | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW DATED 06-07-07. COMMENT | | | NUMBERS TO REMAIN THE SAME. | | | | | | 1. THE COVER AND ALL ARCHITECTURAL SHEETS REQUIRE THE | | | FIRM LICENSE NUMBER. (CERTIFICATE OF AUTHORIZATION), IN | | | THE TITLE BLOCK. FAC 61G1-16.004(2) & FS 481.219, | | | 481.2055. | | | ****RESPONSE NOTED, BUT THE FIRM LICENSE NUMBER DOES | | | NOT REFLECT THE LICENSE NUMBER ON THE FLORIDA STATE | | | DBPR WEBSITE. PLEASE UPDATE THE DBPR WEBSITE OR THE | | | TITLE BLOCK ADDRESS PRIOR TO RESUBMITTING FOR PLAN | | | REVIEW. (SEE ATTACHED SHEET). ALSO THE FIRM LICENSE | | | NUMBER AND CORRECT ADDRESS SHALL BE INDICATED ON ALL | | | SHEETS WITH ARCHITECTURAL TITLE BLOCK. | | | | | | 2. SHT A-5 FINISH SCHEDULE CALLS FOR RESTROOM FLOOR TO | | | HAVE WOOD PLATFORMS. PLEASE INDICATE HOW THIS COMPLIES | | | WITH THE REQUIREMENT FOR A "SMOOTH, HARD, NONABSORBENT | | | SURFACE" AS INDICATED IN SECTION 1210.1. ALSO NO | | | INFORMATION IS GIVEN SHOWING COMPLIANCE WITH SECTION | | | 1210.2 REQUIREMENTS FOR "SMOOTH, HARD, NONABSORBENT | | | SURFACE" FOR THE WALLS WITHIN 2 FEET OF URINALS & WATER | | | CLOSETS. PLEASE CLARIFY. | | | ****RESPONSE NOTED, BUT MANUF. SPECIFICATION SHEETS | | | REQUIRED FOR SEALANT OF CONCRETE TO VERIFY | | | NONABSORBENCY. ALSO THE FINISH SCHEDULE CALLS FOR | | | CERAMIC TILE FOR THE FLOOR. PLEASE CLARIFY. SECTION | | | 106.1.1. | | | | | | 3. OK | | | | | | 4. SHT A-9 SHOW COMPLIANCE WITH THE FOLLOWING: (PLEASE | | | SHOW ON ALL DETAILS OR INDICATE TYPICAL OF ALL TOILET | | | ROOMS) | | | | | | __FOR W/C'S: | | | A. OK | | | B. OK | | | C. OK | | | D. 11-4.16.5 FLUSH CONTROLS ****NOT ADDRESSED | | | E. OK | | | | | | __FOR URINALS: | | | A. 11-4.18.2 OK | | | B. 11-4.18.3 OK | | | C. 11-4.18.4 OK | | | | | | __FOR LAVS: | | | A. 11-4.19.2 OK | | | B. 11-4.19.3 OK | | | C. 11-4.19.4 OK | | | D. 11-4.19.5 FAUCETS ****NOT ADDRESSED | | | E. 11-4.19.6 OK | | | | | | 5. OK | | | 6. OK | | | 7. OK | | | 8. OK | | | | | | 9. SHTS P1.01 & P2.01 SEPARATE GAS PERMIT REQUIRED. THE | | | FOLLOWING INFORMATION IS REQUIRED FOR REVIEW PRIOR TO | | | ISSUING THE GAS PERMIT: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | ****RESPONSE NOTED, BUT NOT ALL CUT SECTIONS INDICATE | | | THE LENGTH. SEE THE SECTIONS DOWNSTREAM OF THE DROP, | | | (7'0")THRU THE RISE SECTION AFTER THE SOLENOID VALVE | | | AND THE 3 SECTIONS AFTER THE 13'6" LENGTH OF PIPE | | | DOWNSTREAM OF THE SOLENOID VALVE. PLEASE CHECK THAT | | | ---ALL--- CUT SECTIONS INDICATE THE LENGTH. SCALING THE | | | RISER ON SHEET P1.03 DOES NOT CORRELATE WITH | | | MEASURMENTS ON THE RISER ISOMETRIC. PLEASE CHECK ALL | | | MEASUREMENTS FOR THE LENGHTS OF PIPE. | | | | | | B. TYPE OF GAS, (LP OR NATURAL). | | | ****RESPONSE NOTED, BUT NOT INDICATED ON THE PLANS. | | | | | | C. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). (TO BE DETERMINED WHEN | | | COMMENT (A) IS ADDRESSED. | | | ****RESPONSE NOTED, BUT WILL BE VERIFIED AFTER ALL CUT | | | SECTION LENGTHS ARE INDICATED IN COMMENT A. | | | | | | D. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | ****RESPONSE NOTED, BUT FLORIDA PUBLIC UTILITIES ONLY | | | DELIVERS 2PSI OR .5PSI. PLEASE INDICATE THE DELIVERY | | | PRESSURE. | | | | | | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE NOTED, BUT THE ARCHITECT INDICATED THAT | | | FORMICA WILL RESPOND TO COMMENT. PLEASE COMMUNICATE | | | WITH ARCHITECT. | | | | | | F. N/A | | | G. N/A | | | | | | H. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | ****RESPONSE NOTED, BUT THE MANUAL SHUT OFF VALVE AND | | | UNION ARE NOT INDICATED ON THE RISER DIAGRAM AS | | | REQUIRED. | | | | | | 10. SHT P2.02 WATER HEATER DETAIL AND WATER RISER | | | DIAGRAM. THE FLOOR DRAIN IS NOT AN APPROVED INDIRECT | | | WASTE RECEPTOR. SECTIONS 802.3 & 802.3.2. EITHER A | | | FLOOR SINK OR A HUB DRAIN IS REQUIRED FOR INDIRECT | | | WASTE. | | | ****RESPONSE NOTED, BUT RISER INDICATES A MOP SINK, NOT | | | HUB DRAIN AS INDICATED IN COMMENT RESPONSE. | | | | | | 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE | | | TO THE SPACE. PLEASE INDICATE THE LOCATION. RPZV | | | BACKFLOW SHALL BE INSTALLED A MAXIMUM 4' ABOVE THE | | | FLOOR FOR SERVICING & TESTING. | | | ****RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED | | | AND SHALL BE LOCATED MAXIMUM 4' ABOVE THE FLOOR, NOT AN | | | INLINE BACKFLOW LOCATED IN THE CEILING AS INDICATED. | | | | | | 12. OK | | | 13. OK | | | 14. OK | | | | | | 15. TWO SETS OF PLANS SHALL BE SUBMITTED. LOOSE SHEETS | | | K-4 & K-5 SHALL BE INSERTED AS PART OF THE PLANS. THE | | | TWO PAGE "WORKSHEETS"FROM THE DEPT OF BUSINESS | | | REGULATION HOTEL & RESTURANT DIVISION SHALL BE ATTACHED | | | TO EACH SET OF PLANS ON THE SHEET STAMPED FOR REVIEW BY | | | DBPR. | | | ****RESPONSE NOTED, BUT REMOVING THE SHEETS THAT HAVE | | | THE FLORIDA STATE DBPR PLAN REVIEW STAMP IS NOT | | | APPROVED. THE REVIEWED PLANS ARE REQUIRED IN BOTH SETS | | | OF PLAN. ALSO THE TWO PAGE "WORKSHEETS" HAVE NOT BEEN | | | ATTACHED TO THE DBPR REVIEWED SHEETS AS REQUIRED FOR | | | EACH SET OF PLANS. | | | | | | 16. THE COVER SHEET INDICATES SHEETS K-1 THRU K-5 ON | | | THE SHEET INDEX. ONLY K-4 & K-5 HAVE BEEN SUBMITTED. | | | PLEASE CORRELATE THE SHEET INDEX WITH THE SHEETS | | | SUBMITTED.SECTION 106.1. | | | ****RESPONSE NOTED, BUT SEE COMMENT 15 AND MAKE SURE | | | THE SHEET INDEX REFLECT SHEETS SUBMITTED. | | | | | | ***********NEW COMMENTS********** | | | | | | 1B. SHT P1.01 THE FLOOR SINK IN THE COOLER SHALL NOT | | | CONNECT TO THE SANITARY DIRECTLY. SECTION 108.1.2. | | | INDIRECT CONNECTION REQUIRED. | | | | | | 2B. SHT P102 THE FLOOR SINK AT FIXTURES 49 & 50 SHALL | | | CONNECT TO THE VENTED LINE SEPARATELY. AS SHOWN IT | | | CONNECTS TO THE LINE TO THE FLOOR SINK FOR FIXTURES | | | 41.1 & 44. SECTION 912.2.4. | | | | | | 3B. SHT P2.01 THE SANITARY ISOMETRIC RISER DIAGRAM, THE | | | RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN IN THE | | | TOILET ROOM NEXT TO THE OFFICE. THE RISER DIAGRAM SHOWS | | | A FLOOR DRAIN NOT SHOWN ON THE FLOOR PLAN. PLEASE | | | CORRELATE RISER & FLOOR PLAN. SECTION 106.1.1. | | | | | | 4B. SHT P2.01 THE GREASE ISOMETRIC RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN. THE VENT DOWNSTREAM OF THE | | | FLOOR SINK FOR FIXTURE 55SHOWN ON THE FLOOR PLAN IS | | | NOT INDICATED ON THE RISER DIAGRAM. PLEASE CORRELATE. | | | --THE FLOOR SINK FOR FIXTURES 49 & 50 SHALL CONNECTED | | | TO THE VENTED MAIN LINE SEPARATELY. SECTION 106.1.1 & | | | SECTION 912.2.4. (SEE COMMENT 2B). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-06-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-06-07 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-06-06 |
Time |
17:30 |
Sent To |
|
|
| Notes |
| 2007-06-07 11:02:16 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FBC-2004 BUILDING | | | CITY WPB MUNICIPAL CODE | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. THE COVER AND ALL ARCHITECTURAL SHEETS REQUIRE THE | | | FIRM LICENSE NUMBER. (CERTIFICATE OF AUTHORIZATION), IN | | | THE TITLE BLOCK. FAC 61G1-16.004(2) & FS 481.219, | | | 481.2055. | | | | | | 2. SHT A-5 FINISH SCHEDULE CALLS FOR RESTROOM FLOOR TO | | | HAVE WOOD PLATFORMS. PLEASE INDICATE HOW THIS COMPLIES | | | WITH THE REQUIREMENT FOR A "SMOOTH, HARD, NONABSORBENT | | | SURFACE" AS INDICATED IN SECTION 1210.1. ALSO NO | | | INFORMATION IS GIVEN SHOWING COMPLIANCE WITH SECTION | | | 1210.2 REQUIREMENTS FOR "SMOOTH, HARD, NONABSORBENT | | | SURFACE" FOR THE WALLS WITHIN 2 FEET OF URINALS & WATER | | | CLOSETS. PLEASE CLARIFY. | | | | | | 3. SHT A-9 ACCESSIBLE STALL DETAIL. LAVS SHALL BE A | | | MINIMUM 15" OFF THE WALL TO THE CENTERLINE OF THE | | | FIXTURE TO BE CENTERED ON THE 30" OF THE 30"X48" CLEAR | | | FLOOR SPACE. SECTION 11-4.19.3. | | | | | | 4. SHT A-9 SHOW COMPLIANCE WITH THE FOLLOWING: (PLEASE | | | SHOW ON ALL DETAILS OR INDICATE TYPICAL OF ALL TOILET | | | ROOMS) | | | | | | __FOR W/C'S: | | | A. 11-4.16.2 CLEAR FLOOR SPACE (PER FIG 30E) | | | B. 11-4.16.3 HEIGHT | | | C. 11-4.16.4 GRAB BARS | | | D. 11-4.16.5 FLUSH CONTROLS | | | E. 11-4.16.6 DISPENSERS | | | | | | __FOR URINALS: | | | A. 11-4.18.2 HEIGHT | | | B. 11-4.18.3 CLEAR FLOOR SPACE | | | C. 11-4.18.4 FLUSH CONTROLS | | | | | | __FOR LAVS: | | | A. 11-4.19.2 HEIGHT & CLEARANCES | | | B. 11-4.19.3 CLEAR FLOOR SPACE | | | C. 11-4.19.4 EXPOSED PIPES & SURFACES | | | D. 11-4.19.5 FAUCETS | | | E. 11-4.19.6 MIRRORS | | | | | | 5. ALL STRUCTURAL SHEETS. PROFESSIONAL ENGINEER FIRM'S | | | CERTIFICATE OF AUTHORIZATION IS SHOWN AS DELINQUENT ON | | | THE STATE DBPR WEBSITE AND THE ADDRESS IN THE TITLE | | | BLOCK DOES NOT REFLECT THE ADDRESS INDICATED ON THE | | | DBPR WEBSITE. PLEASE UPDATE THE STATUS OF THE C.A. | | | NUMBER AND UPDATE EITHER THE DBPR WEBSITE OR THE TITLE | | | BLOCK ADDRESS. FAC 61G15-23.002(2) & FS 471.025. (SEE | | | ATTACHED SHEETS). | | | | | | 6. ALL E, M, & P SHEETS. THE ADDRESS OF FORMICA & | | | ASSOCIATES IN THE TITLE BLOCK DOES NOT REFLECT THE | | | ADDRESS INDICATED ON THE STATE DBPR WEBSITE. EITHER | | | UPDATE THE WEBSITE OR THE TITLE BLOCKS. FAC | | | 61G15-23.002(2) & FS 471.025. (SEE ATTACHED SHEET) | | | | | | 7. SHTS P1.01 & P2.01 SAFE WASTE IS NOT APPROVED. | | | SECTION 1002.1. (SEE FIXTURE 44.1). ALSO THE FLOOR SINK | | | SHALL NOT BE LOCATED IN THE MIDDLE OF THE FLOOR AS IT | | | CAN BE A TRIPPING HAZARD BECAUSE FLOOR SINKS ARE TO BE | | | USED FOR INDIRECT WASTE ONLY. SECTION 802.3. | | | | | | 8. SHTS P1.01 & P2.01 THE DISHWASHER SHALL CONNECT TO | | | THE SANITARY SYSTEM, NOT THE GREASE WASTE SYSTEM PER | | | ARTICLE III SECTION 90-124(7)(B). | | | | | | 9. SHTS P1.01 & P2.01 SEPARATE GAS PERMIT REQUIRED. THE | | | FOLLOWING INFORMATION IS REQUIRED FOR REVIEW PRIOR TO | | | ISSUING THE GAS PERMIT: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | | | | B. TYPE OF GAS, (LP OR NATURAL). | | | | | | C. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). (TO BE DETERMINED WHEN | | | COMMENT (A) IS ADDRESSED. | | | | | | D. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | | | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | F. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | G. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | H. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | | | | 10. SHT P2.02 WATER HEATER DETAIL AND WATER RISER | | | DIAGRAM. THE FLOOR DRAIN IS NOT AN APPROVED INDIRECT | | | WASTE RECEPTOR. SECTIONS 802.3 & 802.3.2. EITHER A | | | FLOOR SINK OR A HUB DRAIN IS REQUIRED FOR INDIRECT | | | WASTE. | | | | | | 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE | | | TO THE SPACE. PLEASE INDICATE THE LOCATION. RPZV | | | BACKFLOW SHALL BE INSTALLED A MAXIMUM 4' ABOVE THE | | | FLOOR FOR SERVICING & TESTING. | | | | | | 12. SHT P2.02 WATER HEATER DETAIL THERMAL EXPANSION | | | CONTROL IS REQUIRED PER SECTION 607.3.2. INDICATE | | | METHOD. | | | | | | 13. SHT P2.02 DETAIL NO. 2 SAFE WASTE IS NOT APPROVED. | | | SECTION 1002.1. | | | | | | 14. SHT P2.02 DETAIL NO. 3 THE AIR GAP SHALL BE PER | | | SECTION 802.2.1.PLEASE INDICATE ON DETAIL. | | | | | | 15. TWO SETS OF PLANS SHALL BE SUBMITTED. LOOSE SHEETS | | | K-4 & K-5 SHALL BE INSERTED AS PART OF THE PLANS. THE | | | TWO PAGE "WORKSHEETS"FROM THE DEPT OF BUSINESS | | | REGULATION HOTEL & RESTURANT DIVISION SHALL BE ATTACHED | | | TO EACH SET OF PLANS ON THE SHEET STAMPED FOR REVIEW BY | | | DBPR. | | | | | | 16. THE COVER SHEET INDICATES SHEETS K-1 THRU K-5 ON | | | THE SHEET INDEX. ONLY K-4 & K-5 HAVE BEEN SUBMITTED. | | | PLEASE CORRELATE THE SHEET INDEX WITH THE SHEETS | | | SUBMITTED.SECTION 106.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2007-10-01 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2007-10-01 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2007-10-01 |
Time |
15:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2007-08-28 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2007-08-28 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2007-08-28 |
Time |
16:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-05-15 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2007-05-15 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2007-05-15 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2007-05-15 09:29:04 | FAILED | | | | | | 1) PLEASE EXPLAIN WHY THERE IS A SERVICE STATION (#3) | | | IMMEDIATELY ADJACENT TO YOUR MAIN ENTRANCE.THIS DOES | | | NOT SEEM TO BE THE FIRST IMPRESSION A CUSTOMER SHOULD | | | HAVE - ESPECIALLY OUTSIDE - OF THE RESTAURANT, NOR DOES | | | IT SEEM THAT IT IS OPERATIONALLY EFFICIENTLY IF YOU | | | HAVE A BUSY NIGHT WITH PEOPLE WAITING FOR THE HOSTESS | | | AND WAITSTAFF IN AN OUT OF THE STATION.PLEASE PROVIDE | | | AN ELEVATION OF THE SOUTH SIDE OF THE BUILDING, | | | INCLUDING SERVICE STATION #3 WITH BOTH OPEN AND CLOSED | | | ROLL UP DOORS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|