Plan Review Details - Permit 07040835
Plan Review Stops For Permit 07040835
Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2008-05-28 Cont ID  
Sent By shill Date 2008-05-28 Time 11:33 Rev Time 0.00
Received By shill Date 2008-05-28 Time 11:33 Sent To  
Notes
2008-05-28 11:34:54REVISED A3, A3.1, A3.2, D1, D2, S1, S2, S3, S3.1, S3.2,
 S4, S5, S6
 DATED 5/7/8
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2008-05-12 Cont ID  
Sent By shill Date 2008-05-12 Time 17:47 Rev Time 0.00
Received By shill Date 2008-05-12 Time 17:47 Sent To  
Notes
2008-05-12 17:47:54REVISION, DOME CEILING FRAMING DETAIL DATED 4/2/8

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2008-03-21 Cont ID  
Sent By adarroug Date 2008-05-12 Time 11:03 Rev Time 0.00
Received By shill Date 2008-03-21 Time 12:52 Sent To  
Notes
2008-03-21 13:19:40****CORRECTIONS****
 ****REVISION****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.REVISED SHEETS SHOULD REPLACE THE SHEET WITH THE
 SAME NAME.THE SCOPE OF WORK IS NOT CLEAR; SEE OTHER
 COMMENTS.
  
 2.IN THE RECORD SET, SHEET S1 DATED 9/20/07 SHOWS A
 "RAISED NEW PLATFORM".THIS DOES NOT APPEAR ON THE NEW
 S1 SUBMITTED DATED 3/11/08, AND THIS AREA IS NOT
 CLOUDED AS A CHANGE TO THE PLAN.IF THIS IS TO BE
 INCLUDED IN THE SCOPE OF WORK, S1 SHOULD SHOW THE
 PLATFORM.IF YOU ARE REMOVING THIS RAISED PLATFORM
 FROM THE SCOPE OF WORK THIS AREA SHOULD BE CLOUDED AND
 OTHER AFFECTED SHEETS ARE TO BE REVISED.
  
 3.SHEET 2 IN THE PERMIT SET DOES NOT BEAR ANY
 RESEMBLANCE TO THE REVISED S2 SUBMITTED. IF THIS IS A
 NEW SHEET WITH NEW DETAILS, IT SHOULD HAVE A NEW
 (UNIQUE) PAGE NUMBER AND WILL THEN BE ADDED TO THE SET,
 RATHER THAN REPLACING THE OLD S2.
  
 4.SHEET S2, OTHER PLACES, PLEASE SEE FBC603 REGARDING
 USE OF COMBUSTIBLE MATERIALS IN TYPE I & II BUILDINGS.
 PLEASE CLARIFY UNDER WHICH EXCEPTION PLYWOOD SHEATHING
 IS PERMITTED, IF ANY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-03-12 Cont ID  
Sent By jwitmer Date 2008-03-12 Time 09:37 Rev Time 0.55
Received By jwitmer Date 2008-03-12 Time 09:36 Sent To PC
Notes
2008-03-12 09:37:39REVISIONS FIRE STOPPING DETAILS

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-02-27 Cont ID  
Sent By jwitmer Date 2008-02-27 Time 12:09 Rev Time 0.77
Received By jwitmer Date 2008-02-27 Time 12:09 Sent To PC
Notes
2008-02-27 12:12:13REVISIONDATED 2/21/08 STOREFRONT 81/2 X 11 2SHEETS

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status   Date 2008-02-21 Cont ID  
Sent By jwitmer Date 2008-02-21 Time 15:06 Rev Time 0.88
Received By jwitmer Date 2008-02-21 Time 15:06 Sent To  
Notes
2008-02-25 15:07:54REVISION PRODUCT APPROVALS

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-01-31 Cont ID  
Sent By jwitmer Date 2008-01-31 Time 16:59 Rev Time 0.77
Received By jwitmer Date 2008-01-31 Time 16:59 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-10-23 Cont ID  
Sent By jwitmer Date 2007-10-23 Time 14:15 Rev Time 2.22
Received By jwitmer Date 2007-10-23 Time 14:15 Sent To  
Notes
2007-10-23 14:16:41PROVISO: CONTRACTOR TO SUBMIT THE ORIGINAL PERMIT
 APPLICATION AND LETTER OF TRARNSFER FROM THE ORIGINAL
 CONTRACTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-01 Cont ID  
Sent By jwitmer Date 2007-10-01 Time 12:52 Rev Time 2.22
Received By jwitmer Date 2007-10-01 Time 12:52 Sent To  
Notes
2007-10-01 13:34:55TAVERNA OPA 2ND REVIEW
 700 S. ROSEMARY
 BUILDING PLAN REVIEW
 PERMIT: 07040835
 ADD: 700 S ROSEMARY # 232
 CONT: L. DAVIS CONSTRUCTION
 TEL: (561)718-8161
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW ? BUILDING8-25-07
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUNDWILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3-7) COMPLIED.
  
 8) RED LINE ACI-318-02 UPDATE
 ACI 531-79 NOT EVEN LISTED
 ACI 530.1-05 THERE IS THIS NUMBER FOR
 MASONRY REQUIREMENTS
 9-19) COMPLIED.
  
 20) COMPLIED.
  
 21-23) COMPLIED.
  
 24) CHANGE IN OCCUPANCY,BEFORE A PERMIT TO
 CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY
 OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE INFORMATION.
  
 25) NEW COMMENT, SHEET S3 DETAIL # 1, SEE NOTES FOR
 STRUCTURAL MULLIONS,NOTES 8,9 & 10 INDICATE THE
 MULLIONS ARE VERTICAL WHEN THEY ARE HORIZONTAL.
  
 26) NEW COMMENT, CHANGE OF CONTRACTOR PLEASE NOTE THE
 PERMIT APPLICATION SUBMITTED INDICATES 700 S ROSEMARY
 SUITE 100, WHERE ASTHE RESUB SHEET AND ORIGINAL
 CONTRACTOR PERMIT APPLICATION INDICATES SUITE # 232
 AAAS WELL AS THE PLANS. PLEASE CORRECT.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-25 Cont ID  
Sent By jwitmer Date 2007-08-25 Time 12:15 Rev Time 3.77
Received By jwitmer Date 2007-08-25 Time 12:15 Sent To  
Notes
2007-08-25 12:26:26TAVERNA OPA 2ND REVIEW
 700 S. ROSEMARY
 BUILDING PLAN REVIEW
 PERMIT: 07040835
 ADD: 700 S ROSEMARY # 232
 CONT: L. DAVIS CONSTRUCTION
 TEL: (561)718-8161
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW ? BUILDING8-25-07
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUNDWILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) 2ND REQUEST,COVERSHEET BLDG DESIGN DATA PLEASE
 CORRECT NUMBER OF STORIES, NOTE THE PARKING GARAGE AND
 B BLOCK RETAIL ARE CONSIDERED ONE BUILDING, NOT TWO.
 NOTE RESPONSE INDICATES A TYPE I BUILDING PROVIDE IF
 DESIGNED AS A IA OR IB?
  
 4-7) COMPLIED.
  
  
  
 8) PLEASE CLOUD DELTA TO INDICATE CHANGES MADE AS
 REQUESTED IN COMMENT NUMBER1. SHEET A-1 GENERAL NOTE#
 15 PLEASE CORRECT THE EDITION THESTANDARDS REFERENCE
 INTHE 2006 FBC-BUILDING CHAPTER 35.
 UPDATE 8A) ASTM C-83
 8B) ACI 318-83
 8C) ACI 301-84
 8D) ACI 531-79 (REVISE THE STANDARD
 NUMBER AND EDITION)
  
 9A) 2ND REQUEST,PLEASE PROVIDE A LIFE SAFETY PLAN
 INDICATING THE EGRESS PATTERNS, PROVIDE WIDTH OF THE
 AISLE AND OCCUPANT LOADS THROUGH TO THE EXIT
 DISCHARGE.
 SEMI-COMPLIED PLEASE PROVIDE 44? ACCESS AISLES.
 1024.9.1.1THE MINIMUM WIDTH OF AISLES SERVING SEATING
 AT TABLES SHALL BE 44 INCHES (1118 MM).
 EXCEPTION: THIRTY-SIX INCHES (914 MM) WHERE SERVING AN
 OCCUPANT LOAD OF NOT MORE THAN 50.
  
 9B) PRIVATE ELEVATOR COMPLIED.
  
 10-11) COMPLIED.
  
 12) 2ND REQUEST, SHEET S-2 INDICATES THE VARIOUS TYPES
 OF MATERIALS TO BE USED IN CONSTRUCTING THE RAISED
 PLATFORMS PLEASE SEE SECTION:410.4 PLATFORM
 CONSTRUCTION.PERMANENT PLATFORMS SHALL BE CONSTRUCTED
 OF MATERIALS AS REQUIRED FOR THE TYPE OF CONSTRUCTION
 OF THE BUILDING IN WHICH THE PERMANENT PLATFORMS IS
 LOCATED. PERMANENT PLATFORMS ARE PERMITTED TO BE
 CONSTRUCTED OF FIRE-RETARDANT-TREATED WOOD FOR TYPE I,
 II, AND IV CONSTRUCTION WHERE THE PLATFORMS ARE NOT
 MORE THAN 30 INCHES (762 MM) ABOVE THE MAIN FLOOR, AND
 NOT MORE THAN ONE-THIRD OF THE ROOM FLOOR AREA AND NOT
 MORE THAN 3,000 SQUARE FEET (279 M2) IN AREA. THE
 RAISED PLATFORM MEETS THE QUALIFICATIONS ABOVE SHEET
 S-2 DOESN?T INDICATE THAT THE WOOD IS REQUIRED TO BE
 FIRE RETARDANT TREATED WOOD.
  
 13) 2ND REQUEST, PROVIDE PRODUCT APPROVALS GLAZED
 OPENING WILL NEED TO COMPLY WITH: 1609.1.4 PROTECTION
 OF OPENINGS. IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE IN THE LOWER 60
 FEET (18.3 M) IN BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED OPENINGS IN THE REST
 OF THE BUILDING SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE IS IMPACT
 RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT
 COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E
 1886 AND ASTM E 1996, ANSI/DASMA 115 (FOR GARAGE DOORS
 AND ROLLING DOORS) OR MIAMI-DADE TAS 201, 202 AND 203
 OR AAMA 506 REFERENCED THEREIN AS FOLLOWS: 1. GLAZED
 OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE SHALL
 MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 13A) 2ND REQUEST,FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES (3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
 A) WINDOWS FIXED
 B) SLIDERS
 C) GLAZED SLIDING GLASS DOORS
 D) GLAZED EXTERIOR SWING DOORS
 E) OVERHEAD DOOR, DOOR SCHEDULE STILL INDICATES
 SUCH DOOR TO BE USED!
 F) MULLIONS-HORIZONTAL FRAMING
 G) PRE-ENGINEERED A/C STANDS
  
 13B) 2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCTAPPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 13C) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 14)COMPLIED.
  
 15) PLEASE PROVIDE COMPLIANCE WITH: 11-5.1 GENERAL.
 EXCEPT AS SPECIFIED OR MODIFIED IN THIS SECTION,
 RESTAURANTS AND CAFETERIAS SHALL COMPLY WITH THE
 REQUIREMENTS OF SECTION 11-4.1 TO SECTION 11-4.35 .
 WHERE FIXED TABLES (OR DINING COUNTERS WHERE FOOD IS
 CONSUMED BUT THERE IS NO SERVICE) ARE PROVIDED,
 AT LEAST 5 PERCENT, 206X.05= 11 SPACES BUT NOT LESS
 THAN ONE, OF THE FIXED TABLES (OR A PORTION OF THE
 DINING COUNTER) SHALL BE ACCESSIBLE AND SHALL COMPLY
 WITH SECTION 11-4.32 AS REQUIRED IN SECTION 11-4.1.3
 (18).
  
 16-19) COMPLIED.
  
  
 20A) 2ND REQUEST,THE PLANS ALSO LACK FIRE SPRINKLER
 PLANS THIS IS A FIRE SPRINKLED BUILDING PLEASE PROVIDE
 THE FIRE SPRINKLER PLAN. THE ORIGINAL DESIGN TOOK THE
 AREA INCREASES FOR A FIRE SPRINKLED BUILDING. SINCE THE
 AREA INCREASES WERE GIVEN UNDER 504.2 ALL TENANT
 IMPROVEMENTS ALSO NEED TO COMPLY WITH THE FIRE
 SPRINKLER REQUIREMENTS.
  
 20B) 2ND REQUEST,NOTE: 2604.1.2(4) BE PROTECTED BY
 AN AUTOMATIC SPRINKLER SYSTEM. WHERE THE COOLER OR
 FREEZER IS WITHIN A BUILDING, BOTH THE COOLER OR
 FREEZER AND THAT PART OF THE BUILDING IN WHICH IT IS
 LOCATED SHALL BE SPRINKLED.
  
 21) ENERGY CALCULATIONS:(1) ARE NOT SIGNED NOR SEALED
 BY THE DESIGNER,
 (2)UNDER THE DOOR HEADING THE LINES ARE BLANK! PLEASE
 FILL IN THE DOOR INFORMATION.
  
  
 22)PLEASE CORRECT THE PERMIT APPLICATION THE CORRECT
 PCN (PROPERTY CONTROL NUMBER) IS LISTED ON THE PERMIT
 APPLICATION BUT THE WRONG ADDRESS. 701 S. ROSEMARY IS
 LOCATED ON THE WEST SIDE OF THE STREET. THE EAST SIDE
 IS 700 S. ROSEMARY.
  
 23) ANEW COMMENT, THE PLANS SHEET A-3 DOESN?T INDICATE
 WHAT TYPE OF TENANT IS LOCATED IN THE NEXT TENANT
 SPACE, IF A A-2 ASSEMBLY IS THE NEXT TENANT A 1 HR WALL
 IS OK BUT IF A BUSINESS OR MERCANTILE A 2HR OCCUPANCY
 SEPARATION WALL WILL BE REQUIRED, SEE TABLE 302.3.2.
  
 24) CHANGE IN OCCUPANCY:BEFORE A PERMIT TO CONSTRUCT,
 MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025
 FOR MORE INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS
 A RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 TAVERNA OPA 2NDT REVIEW.DOC

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-07 Cont ID  
Sent By jwitmer Date 2007-06-07 Time 15:27 Rev Time 6.00
Received By jwitmer Date 2007-06-07 Time 15:27 Sent To  
Notes
2007-06-07 15:28:55BUILDING PLAN REVIEW
 PERMIT: 07040835
 ADD: 701 S ROSEMARY # 232
 CONT: L. DAVIS CONSTRUCTION
 TEL: (561)718-8161
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) COVERSHEET BLDG DESIGN DATA PLEASE CORRECT NUMBER OF
 STORIES, NOTE THE PARKING GARAGE AND B BLOCK RETAIL ARE
 CONSIDERED ONE BUILDING, NOT TWO.
  
 4) COVERSHEET CODE SUMMARY, 2.1 OCCUPANCY GROUP PLEASE
 CORRECT SEE
 SECTION 303 OF THE FBC- BUILDING.
  
 5) COVERSHEET FAILS TO MENTION IN THE CODE SUMMARY THE
 2006 EXISTING BUILDING CODE AND THE LEVEL OF ALTERATION
 TO BE COMPLETED UNDER THIS PERMIT.
  
 6) SHEET A-1 IN THE GENERAL NOTES# 1 PLANS INDICATE
 THAT CONSTRUCTION SHALL FOLLOW THE ?FLORIDA RESIDENTIAL
 CODE? PLEASE CORRECT.
  
 7) SHEET A-1 GENERAL NOTE# 10 INDICATES COMPLIANCE WITH
 THE STATES
 ENERGY SECTION 5024? PLEASE PROVIDE ADDITIONAL
 INFORMATION 106.1.2*.
  
 8) SHEET A-1 GENERAL NOTE# 15 PLEASE CORRECT THE
 EDITION THESTANDARDS REFERENCEINTHE 2006
 FBC-BUILDING CHAPTER 35.
 UPDATE 8A) ASTM C-83
 8B) ACI 318-83
 8C) ACI 301-84
 8D) ACI 531-79 (REVISE THE STANDARD
 NUMBER AND EDITION)
  
 9) PLEASE PROVIDE A LIFE SAFETY PLAN INDICATING THE
 EGRESS PATTERNS, PROVIDE WIDTH OF THE AISLE AND
 OCCUPANT LOADS THROUGH TO THE EXIT DISCHARGE. PLANS
 ALSO INCLUDE AN ELEVATOR TO THE FIRST FLOOR, PLEASE
 PROVIDE ADDITIONAL INFORMATION ON THE FIRST FLOOR
 LEVEL, IS THE ELEVATOR USED BY ANY OTHER TENANT?
 DOES THE ELEVATOR COMMUNICATE WITH THE EXTERIOR, AND IF
 SO HOW/
 PLEASE INCORPORATE :
 11-5.3 ACCESS AISLES. ALL ACCESSIBLE FIXED TABLES SHALL
 BE ACCESSIBLE BY MEANS OF AN ACCESS AISLE AT LEAST 36
 INCHES (915 MM) CLEAR BETWEEN PARALLEL EDGES OF TABLES
 OR BETWEEN A WALL AND THE TABLE EDGES.
 1013.4.2 SEATING AT TABLES.
 1013.4.2.2 TABLE AND SEATING ACCESSWAY WIDTH.
 1013.4.2.3 TABLE AND SEATING AISLE ACCESSWAY LENGTH.
  
 10) SHEET A-3 INDICATES THE USE OF A SINGLE STAIR ON TO
 TIERED PLATFORMS SEE SECTION: 1003.5.2 WHERE CHANGE IN
 ELEVATION OF 12 INCHES (305 MM) OR LESS OCCURS IN EXIT
 ACCESS CORRIDORS, EXITS AND EXIT DISCHARGE, RAMPS
 COMPLYING WITH SECTION 1010 SHALL BE PROVIDED.
  
 11) 1003.5.1 WHERE A CHANGE IN LEVEL MEANS OF EGRESS
 NOT EXCEEDING 21 INCHES (533 MM) IS ACHIEVED BY A
 STAIR, THE MINIMUM TREAD DEPTH OF SUCH STAIR SHALL BE
 13 INCHES (330 MM) AND THE PRESENCE AND LOCATION OF
 EACH STEP SHALL BE READILY APPARENT.
  
 12)SHEET S-2 INDICATES THE VARIOUS TYPES OF MATERIALS
 TO BE USED IN CONSTRUCTING THE RAISED PLATFORMS PLEASE
 SEE SECTION:410.4 PLATFORM CONSTRUCTION.PERMANENT
 PLATFORMS SHALL BE CONSTRUCTED OF MATERIALS AS REQUIRED
 FOR THE TYPE OF CONSTRUCTION OF THE BUILDING IN WHICH
 THE PERMANENT PLATFORMS IS LOCATED. PERMANENT PLATFORMS
 ARE PERMITTED TO BE CONSTRUCTED OF
 FIRE-RETARDANT-TREATED WOOD FOR TYPE I, II, AND IV
 CONSTRUCTION WHERE THE PLATFORMS ARE NOT MORE THAN 30
 INCHES (762 MM) ABOVE THE MAIN FLOOR, AND NOT MORE THAN
 ONE-THIRD OF THE ROOM FLOOR AREA AND NOT MORE THAN
 3,000 SQUARE FEET (279 M2) IN AREA. WHERE THE SPACE
 BENEATH THE PERMANENT PLATFORM IS USED FOR STORAGE OR
 ANY OTHER PURPOSE OTHER THAN EQUIPMENT, WIRING OR
 PLUMBING, THE FLOOR CONSTRUCTION SHALL NOT BE LESS THAN
 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. WHERE THE
 SPACE BENEATH THE PERMANENT PLATFORM IS USED ONLY FOR
 EQUIPMENT, WIRING OR PLUMBING, THE UNDERSIDE OF THE
 PERMANENT PLATFORM NEED NOT BE PROTECTED.
  
 13) GLAZED OPENING WILL NEED TO COMPLY WITH: 1609.1.4
 PROTECTION OF OPENINGS. IN WIND-BORNE DEBRIS REGIONS,
 EXTERIOR GLAZING THAT RECEIVES POSITIVE PRESSURE IN THE
 LOWER 60 FEET (18.3 M) IN BUILDINGS SHALL BE ASSUMED TO
 BE OPENINGS AND THE BALANCE OF GLAZED OPENINGS IN THE
 REST OF THE BUILDING SHALL BE ASSUMED TO BE ZERO UNLESS
 SUCH GLAZING THAT RECEIVES POSITIVE PRESSURE IS IMPACT
 RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT
 COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E
 1886 AND ASTM E 1996, ANSI/DASMA 115 (FOR GARAGE DOORS
 AND ROLLING DOORS) OR MIAMI-DADE TAS 201, 202 AND 203
 OR AAMA 506 REFERENCED THEREIN AS FOLLOWS:
 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF
 GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE
 TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 13A) FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES (3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
 A) WINDOWS FIXED
 B) SLIDERS
 C) GLAZED SLIDING GLASS DOORS
 D) GLAZED EXTERIOR SWING DOORS
 E) GLAZED SWING EXTERIOR DOORS
 F) OVERHEAD DOORS
 G) MULLIONS-HORIZONTAL FRAMING
 H) PRE-ENGINEERED A/C STANDS
  
 13B) PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCTAPPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 13C) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 14)2006 FL. BLD CODE 1603.1.4 THE FOLLOWING
 INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN WIND PRESSURES IN
 TERMS OF PSF.
 NOTE 5 STORY BUILDING POS/ NEG PRESSURE!
  
 15) PLEASE PROVIDE COMPLIANCE WITH :
 15A) 11-5.2 COUNTERS AND BARS.
 WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34
 INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS
 SEATED ON STOOLS OR STANDING AT THE COUNTER, A PORTION
 OF THE MAIN COUNTER WHICH IS 60 INCHES (1525 MM) IN
 LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE WITH
 SECTION 11-4.32 OR SERVICE SHALL BE AVAILABLE AT
 ACCESSIBLE TABLES WITHIN THE SAME AREA.
 15B) 11-5.4 DINING AREAS.
 IN NEW CONSTRUCTION, ALL DINING AREAS, INCLUDING RAISED
 OR SUNKEN DINING AREAS, LOGGIAS, AND OUTDOOR SEATING
 AREAS, SHALL BE ACCESSIBLE. IN ALTERATIONS,
 ACCESSIBILITY TO RAISED OR SUNKEN DINING AREAS, OR TO
 ALL PARTS OF OUTDOOR SEATING AREAS IS NOT REQUIRED
 PROVIDED THAT THE SAME SERVICES AND DECOR ARE PROVIDED
 IN AN ACCESSIBLE SPACE USABLE BY THE GENERAL PUBLIC AND
 ARE NOT RESTRICTED TO USE BY PEOPLE WITH DISABILITIES.
  
 15C) 11-4.32 FIXED OR BUILT-IN SEATING AND TABLES.
 11-4.32.1 MINIMUM NUMBER.
 FIXED OR BUILT-IN SEATING OR TABLES REQUIRED TO BE
 ACCESSIBLE BY SECTION 11-4.1 SHALL COMPLY WITH SECTION
 11-4.32.
  
 15D) 11-4.32.2 SEATING.
 IF SEATING SPACES FOR PEOPLE IN WHEELCHAIRS ARE
 PROVIDED AT FIXED TABLES OR COUNTERS, CLEAR FLOOR SPACE
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED. SUCH
 CLEAR FLOOR SPACE SHALL NOT OVERLAP KNEE SPACE BY MORE
 THAN 19 INCHES (485 MM) (SEE FIGURE 45).
 ALL FIXED SEATING IN PUBLIC FOOD SERVICE
 ESTABLISHMENTS, IN ESTABLISHMENTS LICENSED UNDER THE
 BEVERAGE LAW FOR CONSUMPTION ON THE PREMISES, AND IN
 ALL OTHER FACILITIES GOVERNED BY REFERENCE SECTION
 11-4.1 SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE
 WITH THE FOLLOWING REQUIREMENTS:
 (1) ALL AISLES ADJACENT TO FIXED SEATING SHALL PROVIDE
 CLEAR FLOOR SPACE FOR WHEELCHAIRS.
 (2) WHERE THERE ARE OPEN POSITIONS ALONG BOTH SIDES OF
 SUCH AISLES, THE AISLES SHALL BE NOT LESS THAN 52
 INCHES (1321 MM) WIDE.
 11-4.32.3 KNEE CLEARANCES.
 IF SEATING FOR PEOPLE IN WHEELCHAIRS IS PROVIDED AT
 TABLES OR COUNTERS, KNEE SPACES AT LEAST 27 INCHES (685
 MM) HIGH, 30 INCHES (760 MM) WIDE, AND 19 INCHES (485
 MM) DEEP SHALL BE PROVIDED (SEE FIGURE 45).
 11-4.32.4 HEIGHT OF TABLES OR COUNTERS.
 THE TOPS OF ACCESSIBLE TABLES AND COUNTERS SHALL BE
 FROM 28 INCHES TO 34 INCHES (710 MM TO 865 MM) ABOVE
 THE FINISH FLOOR OR GROUND.
  
 16) THE RAISED PLATFORMS HAVE AN OCCUPANT LOAD GREATER
 THAN 50, THAT WILL REQUIRE 2 MEANS OF EGRESS BUT THERE
 IS ONLY ONE ACCESSIBLE RAMP. SEE TABLE 1018.2.
 11-4.3.10 EGRESS.
 ACCESSIBLE ROUTES SERVING ANY ACCESSIBLE SPACE OR
 ELEMENT SHALL ALSO SERVE AS A MEANS OF EGRESS FOR
 EMERGENCIES OR CONNECT TO AN ACCESSIBLE AREA OF RESCUE
 ASSISTANCE.
  
 17) SHEET E2.01 INDICATES AN EXIT LIGHT AT THE BACK OF
 THE PRIVATE MEETING ROOM ,1013.2 EGRESS THROUGH
 INTERVENING SPACES.EGRESS FROM A ROOM OR SPACE SHALL
 NOT PASS THROUGH ADJOINING OR INTERVENING ROOMS OR
 AREAS, EXCEPT WHERE SUCH ADJOINING ROOMS OR AREAS ARE
 ACCESSORY TO THE AREA SERVED; ARE NOT A HIGH-HAZARD
 OCCUPANCY AND PROVIDE A DISCERNIBLE PATH OF EGRESS
 TRAVEL TO AN EXIT. EGRESS SHALL NOT PASS THROUGH
 KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES USED FOR
 SIMILAR PURPOSES. PLEASE CORRECT.
  
 18) PLANS DO NOT PROVIDE ANY INFORMATION FOR DOOR
 HARDWARE OR PANIC HARDWARE, SEE 1008.1.9.
  
 19)SHEETS A7-8 SHOW A CUT SECTION THROUGH THE
 RESTAURANT BUT THERE IS NO INFORMATION AS TO WALL AND
 CEILING FINISHES, PLEASE PROVIDE INFORMATION COMPLYING
 WITH: 803.1 GENERAL.
 INTERIOR WALL AND CEILING FINISHES SHALL BE CLASSIFIED
 IN ACCORDANCE WITH ASTM E 84. SUCH INTERIOR FINISH
 MATERIALS SHALL BE GROUPED IN THE FOLLOWING CLASSES IN
 ACCORDANCE WITH THEIR FLAME SPREAD AND SMOKE-DEVELOPED
 INDEX.
 CLASS A:
 FLAME SPREAD INDEX 0-25; SMOKE-DEVELOPED INDEX 0-450.
 CLASS B:
 FLAME SPREAD INDEX 26-75; SMOKE-DEVELOPED INDEX 0-450.
 CLASS C:
 FLAME SPREAD INDEX 76-200; SMOKE-DEVELOPED INDEX
 0-450.
 EXCEPTION: MATERIALS, OTHER THAN TEXTILES, TESTED IN
 ACCORDANCE WITH SECTION 803.2.
 803.2INTERIOR WALL OR CEILING FINISHES OTHER THAN
 TEXTILES.
 INTERIOR WALL OR CEILING FINISHES, OTHER THAN TEXTILES,
 SHALL BE PERMITTED TO BE TESTED IN ACCORDANCE WITH NFPA
 286. FINISHES TESTED IN ACCORDANCE WITH NFPA 286 SHALL
 COMPLY WITH SECTION 803.2.1.
  
 20) THE PLANS ALSO LACK FIRE SPRINKLER PLANS THIS IS A
 FIRE SPRINKLED BUILDING PLEASE PROVIDE THE FIRE
 SPRINKLER PLAN. NOTE: 2604.1.2(4) BE PROTECTED BY AN
 AUTOMATIC SPRINKLER SYSTEM. WHERE THE COOLER OR FREEZER
 IS WITHIN A BUILDING, BOTH THE COOLER OR FREEZER AND
 THAT PART OF THE BUILDING IN WHICH IT IS LOCATED SHALL
 BE SPRINKLED.
  
 21) IT ALSO APPEARS THAT THE ENERGY CALCULATIONS SEE
 CHAPTER 13 OF THE FBC BUILDING.
  
 22) SEE ELECTRICAL COMMENTS ABOUT ARCHITECTURAL AND
 ENGINEERING DEFICIENCIES, SIGNATURES, DELINQUENCIES,
 CERTIFICATE OF AUTHORIZATION, ETC.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS
 A RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 TAVERNA OPA 1ST REVIEW.DOC

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2008-10-29 Cont ID  
Sent By dpalmer Date 2008-10-29 Time 15:29 Rev Time 0.00
Received By dpalmer Date 2008-10-29 Time 15:29 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 11 Status F Date 2008-10-10 Cont ID  
Sent By dpalmer Date 2008-10-10 Time 17:05 Rev Time 0.00
Received By dpalmer Date 2008-10-10 Time 17:05 Sent To PC
Notes
2008-10-10 17:06:06 
 ** DENIED REVIEW**
  
  
 1) NOTE: PLEASE BE SURE ALL CIRCUITING ON PLANS
 COORDINATE.
 SOME EXAMPLES:
 L-76, L-51, L2-39, 37,ETC
  
 THERE ARE OTHERS. ALL PANEL SCHEDULE ON RECORD PLANS
 NEED TO COORDINATE. SPOKE WITH DESIGNER AND IS AWARE OF
 THE ITEMS. WILL NEED TO GET REVISED PANEL SCHEDULES
 FROM ELECTRICAL CONTRACTOR FOR WHAT WAS ACTUALLY DONE
 ON-SITE SO REVISED PLANS AND PANEL SCHEDULES CAN BE
 ACCURATE FOR RECORD PLANS.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2008-10-08 Cont ID  
Sent By dpalmer Date 2008-10-08 Time 11:13 Rev Time 0.00
Received By dpalmer Date 2008-10-08 Time 11:13 Sent To PC
Notes
2008-10-08 11:13:23** DENIED **
  
 1) NOTE: ALL REVISIONS AND CHANGES TO PLANS NEED TO BE
 IDENTIFIED BY CLOUDS, TRIANGLES ETC. THE PLANS DO NOT
 CONTAIN ANY INDICATION OF REVISIONS MADE TO THE MOST
 RECENT PLANS ON FILE.
 FOR EXAMPLE: REVISED CIRCUITING FROM THE LAST REVISED
 PLAN ON FILE WOULD BE INDICATED HOWEVER ONLY FOR THOSE
 CIRCUITS. AS SHOWN THERE ARE NO REVISIONS. PLEASE CALL
 TO GO OVER.
 FOR EXAMPLE: AS THE LATEST PLANS ON FILE SUPPOSEDLY
 CONTAIN THE LATEST REVISED CIRCUITING, WE WOULD ONLY
 NEED THE REVISED PANEL SCHEDULE.
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2008-09-10 Cont ID  
Sent By dpalmer Date 2008-09-10 Time 11:48 Rev Time 0.00
Received By dpalmer Date 2008-09-10 Time 11:48 Sent To PC
Notes
2008-09-10 11:48:58** REDLINED/PROVISO **
  
 1) NOTE: STILL NEED TO SUBMIT REVISED PANEL SCHEDULES
 TO COORDINATE WITH THE REVISED CIRCUITING ON POWER
 PLANS.
 408.4
 FBC 106.1.1,106.3.5.1.2
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2008-05-06 Cont ID  
Sent By dpalmer Date 2008-05-06 Time 11:12 Rev Time 0.00
Received By dpalmer Date 2008-05-06 Time 11:12 Sent To PC
Notes
2008-05-06 11:13:05REV FOR PROJECT FOR FINAL.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2008-04-07 Cont ID  
Sent By dpalmer Date 2008-04-07 Time 13:02 Rev Time 0.00
Received By dpalmer Date 2008-04-07 Time 13:02 Sent To PC
Notes
2008-04-07 13:02:50** DENIED**
  
 1) NOTE: PLEASE SEE THE SUBMITTED LIGHTING SUBMITTALS
 ARE NOT REQUIRED FOR ELECTRICAL REVIEW. ANY CHANGES TO
 LIGHTING CONTROLS OR TO ORIGINAL PROPOSED LIGHTING
 WHICH WAS ON PERMITTED SET OF PLANS WOULD REQUIRE
 REVISED ELECTRICAL PLANS.
 FOR INFORMATIONAL PURPOSE: THE LIGHTING SUBMITTALS
 SUBMITTED DID NOT CONTAIN SHOP DRAWING REVIEW STAMP
 FROM ENGINEER OF RECORD.
 ** AS NOTED ABOVE, ANY CHANGES IN LIGHTING CONTROLS OR
 LIGHTING FROM THE ORIGINAL PLANS NEEDS TO HAVE REVISED
 ELECTRICAL PLANS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status N Date 2008-03-04 Cont ID  
Sent By dpalmer Date 2008-03-04 Time 12:35 Rev Time 0.00
Received By dpalmer Date 2008-03-04 Time 12:35 Sent To P
Notes
2008-03-04 12:36:14**SWITCH GEAR SUBMITTALS NOT NEEDED.
 EQUIPMENT AND LISTINGS TO BE VIF, 110.3, 90.7

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-01-28 Cont ID  
Sent By dpalmer Date 2008-01-28 Time 16:52 Rev Time 0.00
Received By dpalmer Date 2008-01-28 Time 16:52 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-10-23 Cont ID  
Sent By dpalmer Date 2007-10-23 Time 10:53 Rev Time 0.00
Received By dpalmer Date 2007-10-23 Time 09:32 Sent To  
Notes
2007-10-23 10:53:57***PROVISO/REVISION NEEDED ***
  
 1) NOTE: PLEASE SEE THE LIGHTING IN THE KITCHEN BACK
 HALLWAY AREA NEEDS TO MEET BOTH THE LIFE SAFETY ASPECT
 OF THE CODE IN NFPA-101 7.8/ALONG WITH FBC AND CHAPTER
 13 FOR LIGHTING CONTROLS.
 AS SHOWN ON PLANS WHEN THE SCHEDULED LIGHTING SYSTEM
 TURNS OFF THERE IS NO DEVICE OR LIGHTING PROVIDED FOR
 THE PATH TO THE OVER RIDE DEVICES.
 THERE IS ALSO NO *NIGHT-LIGHTS* SHOWN IN THESE SAME
 AREAS. THIS WAS GONE OVER IN MEETING AND AGREED THESE
 LIGHTING FIXTURES OR OCCUPANCY SENSORS WILL BE
 PROVIDED.
 PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 2) NOTE: REDLINED METHOD OF LIGHTING CALCULATIONS FROM
 METHOD *A* TO METHOD *C* AS GONE OVER IN MEETING.
  
 ** PLEASE REVISE THE ABOVE ALONG WITH ANY OTHER
 REVISIONS BEFORE ROUGH ELECTRICAL INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-09-27 Cont ID  
Sent By dpalmer Date 2007-09-27 Time 18:48 Rev Time 0.00
Received By dpalmer Date 2007-09-27 Time 15:26 Sent To  
Notes
2007-09-27 18:48:48** DENIED**
  
 *** PLEASE SEE THE FOLLOWING COMMENTS BELOW.
 THERE HAVE BEEN SEVERAL ON PLANS WITH RESPECT TO
 LIGHTING CONTROLS AND NEW COMMENTS BELOW WHICH MAY NOT
 BE WORD FOR WORD THE SAME FROM PREVIOUS REVIEW STILL
 HAVE TO DO WITH CHAPTER 13 COMPLIANCE. AS SOME NEW
 METHODS/CHANGES IN CONTROLS HAVE BEEN REVISED THIS HAS
 CREATED A COUPLE OF NEW COMMENTS ON PLANS.
 ** PLEASE KNOW IF ALL OTHER REVIEWS PASS WITHOUT ANY
 COMMENTS, THE FOLLOWING MAY BE SET UP AS A PROVISO
 HOWEVER WOULD NEED TO BE REVISED WITH THE GIVEN TIME.
 THIS IS ONLY IF ALL OTHER TRADES ARE OK WITH PLANS AND
 PROJECT IS READY TO ISSUE FOR PERMIT.
 THE ELECTRICAL DESIGNER HAS BEEN CONTACTED.
  
 1) NOTE:PLEASE THE LOCATIONS OF LIGHTING CONTROLS
 NEED TO MEET 13-415.1.ABC.1.1. PLEASE SEE FOR EXAMPLE
 THE REAR DOOR ENTRANCE WHICH DOES NOT CONTAIN ANY OVER
 RIDE. THERE ARE SEVERAL LOCATIONS WHICH SHOW STANDARD
 3-WAY AND 4-WAY SWITCHES HOWEVER WITH OUT AN OVER RIDE
 DEVICE OF SYSTEM, THESE SWITCHES WOULD BE INOPERABLE.
 PLEASE SEE THE BATHROOMS WHICH INDICATE A STANDARD
 SWITCH FOR CONTROL OF LIGHTING ALONG WITH AN OCCUPANCY
 DEVICE. IF AN OCCUPANT LEAVES THE BATHROOM AND TURNS
 THIS SWITCH OFF THEN ANY REMAINING OCCUPANTS WOULD HAVE
 NO LIGHTING TO MAKE WAY TO THE SWITCH TO TURN LIGHTING
 BACK ON. THIS SCENARIO WAS GONE OVER WITH DESIGNER AND
 ADJUSTMENTS TO TYPE OF FIXTURES AND POSSIBLE NIGHTS
 WILL BE REVISED ON PLANS.
  
 2) NOTE: PLEASE SEE LIFE SAFETY CODE NFPA-101 7.8 AND
 7.9 WITH RESPECT TO EGRESS LIGHTING UNDER NORMAL AND
 EMERGENCY CONDITIONS. THE LIGHTING WHICH IS BEING
 CONTROLLED FROM SYSTEM WHEN BEING SHUT DOWN LEAVES
 SEVERAL AREAS IN TOTAL DARKNESS WITHOUT LENDING ANY
 LIGHTING FOR EGRESS TO AREAS FOR THE OVER RIDE
 CONTROLS. THIS IS ALSO TO COORDINATE WITH THE COMMENT
 #1 ABOVE WITH RESPECT TO RESTROOMS AND HALLWAY AREAS.
 THESE LOCATIONS WERESPECIFICALLY GONE OVER WITH THE
 DESIGNER AND ADJUSTMENTS ARE BEING MADE TO LIGHTING
 FIXTURE TYPES AND/OR CONTROLS.
  
 3) NOTE: PLEASE SEE THE RISER IS STILL IN QUESTION AS
 SHOWN. THIS REVISED RISER HAS COMPLETELY CHANGED FROM
 THE PREVIOUS REVIEWED PLANS. PLEASE SEE THE RISER SHOWS
 THIS SERVICE BEING TAPPED FROM A GUTTER WHICH IS TAPPED
 FROM THE LOAD SIDE GUTTER WHICH IS FED FROM METERS AND
 DISCONNECTS. THIS IS UNCLEAR HOW THIS GUTTER BEING
 SHOWN ON THE LOAD SIDE OF THE METERS AND TENANT MAINS
 FEED THIS SECONDARY GUTTER?
 AS SHOWN THIS DOES NOT SEEM POSSIBLE. THIS REVIEW WILL
 PLACE CALL TO LAND-LORD AND REQUEST A MEETING ON-SITE
 FBC 106.1.2/106.3.5.1.2, NEC 215.5, 230.70 ETC
 THIS IS COORDINATION OF PLANS AND RISER.
  
 4) NOTE: PLEASE SEE COMMENTS FROM FIRE REVIEWER AND
 POSSIBLE BUILDING AS THE FIRE ALARMS PLANS FP-1 SHEET
 WAS NOT SIGNED, DATED OR SEALED BY THE ENGINEER OF
 RECORD. THIS IS REQUIRED FOR BASE BUILDING PLANS EVEN
 THOUGH THIS IS UNDER A SEPARATE PERMIT. AS MENTIONED ON
 PREVIOUS REVIEW THIS IS STILL REQUIRED UNDER BASE BUILD
 OUT PLANS.
 PLEASE ALSO SEE THE FIRE SPRINKLER SHEET FP3.1 AS THIS
 SHEET ONLY CONTAINS A PRINTED SEAL OF SOME SORT ON
 TITLE BLOCKS. PLEASE SEE THE SEAL AS SHOWN WOULD NOT
 MEET FAC 61G15-23.002.
 PLEASE BE SURE THIS IS ADDRESS EVEN IF COMMENTS ARE NOT
 FROM OTHER REVIEWS. IF THESE ITEMS ARE THE ONLY ITEMS
 ON THESE SHEETS FOR COMPLIANCE, THEN THESE DESIGN
 PROFESSIONALS MAY COME INTO THIS OFFICE AND SIGN, DATE
 AND SEAL PLANS.
  
 5) NOTE: PLEASE DO NOT ATTACH PRODUCT APPROVALS AND
 SUPPORTING DOCUMENTS DOWN THE LEFT HAND SIDE OF PLANS.
 THESE HAVE BEEN REMOVED BY THIS REVIEWER ON BOTH SETS.
 THESE DOCUMENTS SHOULD BE PLACED INTO TWO SEPARATE
 PACKAGES.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-25 Cont ID  
Sent By dpalmer Date 2007-08-25 Time 09:50 Rev Time 0.00
Received By dpalmer Date 2007-08-24 Time 19:17 Sent To  
Notes
2007-08-25 09:50:47 
 2007-08-25 09:50:47
  
 *** DENIED2ND REVIEW ***
  
 *** PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW
 ARE STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW
 COMMENTS BASED ON SOME INFORMATION ON REVISED PLANS.
 SOME INFORMATION IS ONLY NOW BEING SUBMITTED FOR
 REVIEW.
  
 1) NOTE: PLEASE SEE THE RESPONSE LETTER FROM THE DESIGN
 TEAM QUOTES THIS REVIEWER'S COMMENTS AND THEN CONTAINS
 A RESPONSE BELOW. PLEASE SEE THERE ARE NUMEROUS
 INSTANCES WHERE THE TYPEWRITTEN NOTES OF THIS
 REVIEWER'S COMMENTS ARE NOT WHAT WERE TYPED IN THE
 PREVIOUS REVIEW.
 SOME ARE TYPED AS STATING THE REVIEWER HAS REQUIRED
 CERTAIN ITEMS WHICH ARE NOT THE CASE. PLEASE SEE THE
 FOLLOWING FOR EXAMPLE.
 **RESPONSE TO COMMENT #2 FROM PREVIOUS REVIEW IN
 LETTER.
 PART OF THE REVIEW COMMENT MENTIONS: *PLANS ONLY SHOW
 STANDARD SWITCHES* AND THE RESPONSE LETTER TYPES
 *PLEASE ONLY SHOW STANDARD SWITCHES*.
 THIS WOULD COMPLETELY CHANGE THE CODE REQUIRED ITEM. IF
 THE RESPONSE LETTER IS GOING TO *QUOTE* REVIEWER'S
 COMMENTS PLEASE BE SURE TO ACCURATELY PLACE ACTUAL
 NOTES.
  
 2) NOTE: PLEASE SEE COMMENT #2 FROM PREVIOUS REVIEW
 WHICH REQUESTED COMPLIANCE WITH THE FBC CHAPTER 13.
 THIS IS THE FIRST REVIEW FOR SOME INFORMATION SUBMITTED
 FOR CHAPTER 13.
 PLEASE SEE THERE ARE MANY ITEMS WHICH STILL NEED TO BE
 ADDRESSED:
 PLEASE SEE NOTE #3 BELOW WITH RESPECT TO THE ENERGY
 CALCULATIONS.
  
 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 DO NOT REFLECT THE SAME INFORMATION AS SHOWN ON PLANS.
 THE INPUT DATA REPORT CONTAINS INPUT OF LIGHTING
 LUMINARIES WHICH ARE NOT ON PLANS AND ALSO THE PLANS
 CONTAIN LIGHTING FIXTURES WHICH ARE NOT INPUTTED INTO
 THE REPORT.
 PLEASE SEE SHEET 2 OF THE IDR WHICH CONTAINS ONLY SEVEN
 LUMINARIES, HOW IS THIS POSSIBLE WHEN THE PLANS
 INDICATE A SUBSTANTIALLY HIGHER AMOUNT OF FIXTURES?
 PLEASE SEE THE WATTAGE OF THESE DO NOT CORRELATE WITH
 THE FIXTURE LEGEND AND FIXTURES ON PLANS.
 PLEASE SEE THE LIGHTING POWER DENSITIES CALCULATIONS
 INDICATE DIFFERENT WATTAGES THAN ON PLANS AND WHAT IS
 SHOWN ON CALCULATIONS. 13-415.1.A, 13-415.2
 PLEASE SEE NO EXTERIOR LIGHTING WAS ENTERED YET PLANS
 CONTAIN THESE LIGHTING FIXTURES 13-415.2.ABC.1.3. THE
 CALCULATIONS AS SUBMITTED ARE UNDER METHOD A. THE PLANS
 ARE INDICATING THE TABLE 13-415.2.C.1
 PLEASE EXPLAIN AND COORDINATE.
  
 4) NOTE:PLEASE SEE NO INFORMATION IS SHOWN FOR THE
 MINIMUM LOADS FOR TRACK LIGHTING AS REQUIRED AND STATED
 IN THE PREVIOUS REVIEW. THIS SECTION OF THE CODE WAS
 SPECIFICALLY QUOTED ON THE PREVIOUS REVIEW AS TRACK
 LIGHTING INPUT IS OFTEN NOT CORRECT IN
 DESIGNS.13-415.2.ABC.1.2.
  
 5) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED
 INFORMATION AND DESIGNS FOR 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE SEE ONLY SOME INFORMATION WAS SUBMITTED AND
 SHOWN ON PLANS.
 PLEASE SEE THE PLANS STATE THERE IS GOING TO THE A
 LIGHTING CONTROL PANEL HOWEVER NO INFORMATION WAS SHOWN
 FOR SCHEDULING , ALL OVER RIDE LOCATIONS, AND MAXIMUM
 TIMES ON OVER RIDES AND DEVICES FOR LIGHTING CONTROLS.
 PLANS INDICATE SEVERAL OS TYPE DEVICES, HOWEVER NO
 MAXIMUM TIMES ON THESE DEVICES.
 PLEASE SEE THE LOCATIONS REQUIRED FOR OVER RIDES WERE
 NOT CLEAR AT ALL OF THE LOCATIONS REQUIRED.
 COULD NOT LOCATE CONTROLS FOR DISPLAY OR ACCENT
 LIGHTING WHICH IS SHOWN ON PLANS.
 PLEASE SEE THERE ARE SEVERAL LOCATIONS ON PLANS WHICH
 STILL ONLY CONTAIN STANDARD CONTROL SWITCHES. (SOME OF
 THESE LOCATIONS ARE REDLINED)
 PLEASE INCLUDE INFORMATION FOR ZONES AND SQ FT AS
 REQUIRED PER 13-415.1.ABC.1.2
 PLEASE SEE THE LIGHTING PLANS INDICATE A NOTE #2 ON THE
 COOLER LIGHTS WHICH MENTIONS TO WIRE THROUGH LIGHTING
 CONTROL PANEL. HOW IS THIS POSSIBLE WHEN THE LIGHTING
 CONTROL PANEL IS 120/208V AND THE CIRCUIT NOTED IS
 277/480V? PLEASE COORDINATE ALL.(KITCHEN LIGHTING NOTED
 ON THIS SAME CIRCUIT ON PANEL SCHEDULE)
 PLEASE COMPLETE THE FIXTURE LEGEND WITH ALL INFORMATION
 AT THIS TIME. SOME ARE NOTED TO BE *SELECTED BY OWNER*
 HOWEVER THE MINIMUM ARE REQUIRED AT THIS TIME. THESE
 CAN ALWAYS BE REVISED AT A LATER DATE IF NEEDED.(
 PREVIOUS NOTE #18)
 PLEASE SEE ALL OF CHAPTER 13, THERE ARE MANY ITEMS
 WHICH CAN NOT BE REVIEWED AT THIS TIME.
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 6) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 IN FACT CONTAIN A PHOTO-COPIED SIGNATURE ON THE
 CERTIFICATION SHEETS WHEN THESE ARE REQUIRED TO BE
 SIGNED, SEALED AND DATED PER FLORIDA STATUTES 471.025,
 481.221.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND
 FBC 13-103.1.1.1
 PLEASE ALSO SEE THE OWNER AGENT IS NOT SIGNED ON
 SHEETS.
  
 7) NOTE:PLEASE SHOW ALL DEVICE LOCATIONS AND LEVELS
 FOR ADA COMPLIANCE FOR HORN, STROBES. PER FBC
 11.4-28.1, .2 AND .3(4).
 ** PLEASE KNOW EVEN AS THE FIRE ALARM PERMIT WILL BE
 SEPARATE ALONG WITH FIRE SPRINKLER, THE BASE BUILDING
 PLANS MUST SHOW THE MINIMUM REQUIRED INTENDED SYSTEM.
 FBC 106.3.5.1.1
 THIS NOTE WAS NOTE #9 ON THE PREVIOUS REVIEW AND
 REMAINS. THE RESPONSE FROM THE ENGINEERING FIRM STATES
 *NOT PROVIDED* BY FIRM.
 THE RESPONSE FROM THE ARCHITECT MENTIONS TO SEE A3.2
 HOWEVER PLEASE SEE THE DEVICES AS SHOWN ON THIS SHEET
 DO NOT MEET THE LOCATIONS AS REQUIRED. PLEASE ALSO SEE
 THE SYMBOL BEING USED FOR HORNS, STROBES OR
 HORN/STROBES IS NOT THAT OF THE STANDARD USE IN THE
 INDUSTRY AND ON PLANS.
 PLEASE SUBMIT COMPLETED INFORMATION FOR MINIMUM DESIGN
 FOR BASE FIRE ALARM DEVICES ON BASE BUILD OUT PLANS AS
 REQUIRED PER FS 633 AND 106.3.5.1.2 OF THE FBC
 ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF WEST
 PALM BEACH.
  
 8) NOTE:PLEASE SEE THE PREVIOUS NOTE #13 IS STILL IN
 NEED OF ADDRESSING. THE ELECTRICAL PLANS AS REQUIRED DO
 NOT CONTAIN THE REQUIRED AND NEEDED INFORMATION FOR THE
 TRANSFORMER INSTALLATION AS PREVIOUSLY REQUESTED. A
 NOTE ON THE ELECTRICAL SHEET MENTIONS TO SEE THE
 ARCHITECTURAL AND/OR STRUCTURAL SHEETS HOWEVER NO
 COMPLETED INFORMATION WAS LOCATED ON THESE SHEETS. THIS
 IS A LIFE SAFETY, FIRE, AND PROPERTY HAZARD ISSUE.
 SERIOUS INJURY OR DEATH COULD RESULT IN AN INSTALLATION
 OF EQUIPMENT OF THIS NATURE WHICH IS IMPROPERLY
 INSTALLED. THIS INFORMATION IS NEEDED ON PLANS FOR THE
 CODE REQUIRED INSTALLATION AT THIS TIME. PLANS MAY NOT
 SIMPLY STATE TO SEE OTHER SHEETS. PLEASE KNOW THAT
 THESE UNITS CREATE A SUBSTANTIAL AMOUNT OF HEAT AND
 BEING LOCATED NEAR EASILY IGNITABLE MATERIALS AND
 COMBUSTIBLES IS STRICTLY PROHIBITED. PLEASE SEE 110.26,
 240.24A, C AND D, 450.9, 450.13, 450.21-450.27. AS NO
 INFORMATION SPECIFICALLY IS SHOWN ON THE TRANSFORMER
 SECTIONS .21-.27 ARE BEING NOTED. PLEASE KNOW THIS
 PROPOSED LOCATION ABOVE THE AREA AS STATED IS NOT
 PERMITTED.
 PLEASE SEE NO STRUCTURAL INFORMATION WAS SUBMITTED FOR
 SUPPORT AS THE PLANS STATE THIS WILL BE LOCATED OFF THE
 FLOOR.
 ** CAREFUL CONSIDERATION IS TO BE GIVEN ON THE
 LOCATION.
  
 *** PREVIOUS REVIEW NOTE****
 PLEASE SEE THE PLANS ARE MISSING THE LOCATION FOR THE
 REQUIRED DISCONNECT AND TRANSFORMER. PLEASE SEE 110.26
 AND 450 AS NO REVIEW FOR THIS CAN BE DONE AT THIS
 TIME.
 PLEASE SEE 450.9, 450.13 ETC AS THE TRANSFORMER MAY NOT
 BE ABOVE CEILING.
 PLEASE ALSO SUBMIT STRUCTURAL ENGINEERED DETAIL AT THIS
 TIME FOR THE LOCATION AND HOW THIS UNIT WILL BE
 INSTALLED.
 ** PLANS CURRENTLY MENTION THE LOCATION OF THE
 TRANSFORMER IS TO BE DETERMINED BY THE BUILDING
 ENGINEER, HOWEVER THE NEC DETERMINES LOCATION BASED ON
 WIRING METHODS, CLEARANCES, ETC. THE STRUCTURAL ELEMENT
 WILL THEN BE THE CONSIDERATION FOR NEEDED STRUCTURAL
 SUPPORT ETC.
 ** SOME ELECTRICAL CODE COMPLIANCE ITEMS CAN NOT BE
 REVIEWED AT THIS TIME**
  
  
 9) NOTE: THIS NOTE REMAINS FROM THE PREVIOUS REVIEW.
 PLEASE SEE THE RESPONSE MENTIONS THERE ARE NO OTHER
 LOADS ON THIS MAIN. THIS NOTED EXISTING MAIN IS NOT
 KNOWN BY THIS OFFICE BEING DIRECTLY FROM FPL WITH ITS
 OWN SERVICE AS BEING SHOWN ON THE REVISED RISER. PLEASE
 KNOW THAT A FIELD INSPECTION WILL NEED TO BE PERFORMED
 TO GO OVER THE SERVICES AND EQUIPMENT AT THIS LOCATION.
 THIS OFFICE WILL NEED TO BE IN CONTACT WITH THE
 LANDLORDS OFFICE TO OBTAIN ACCESS TO LOCATION.
 AS REQUESTED FROM PREVIOUS REVIEW:
 **PLEASE SUBMIT THE COMPLETED LOAD CALCULATIONS ON
 SERVICE AND THE ADDED LOAD TO THE EXISTING MAIN SERVICE
 WITH NEW LOAD ADDED.
 THE PLANS CURRENTLY ONLY SHOW THE LOAD CALCULATIONS ON
 *L*.
 220 (ALL), 215.5, CONTINUOUS LOADS PER 215.3, 230.42
 ETC
 NEC 220 WAS GIVEN IN GENERAL AS THERE ARE TOO MANY
 SPECIFIC CODE SECTIONS WHICH APPLY FROM 220. (TRACK
 LTS, LIGHTING, RECEPTACLES) ETC.
 FBC 106.3.5.1.2, 106.1.2.
 ** PLEASE BE SURE TO OBTAIN ANY INFORMATION FROM OTHER
 POSSIBLE BUILD-OUTS FOR NEW TENANTS WHICH *WILL* AFFECT
 THE LOAD CALCULATIONS ON MAIN SERVICE.
  
 10) NOTE:THE PREVIOUS REVIEW NOTE #20 REQUESTED
 COORDINATION OF SHUNT TRIP BREAKERS FOR EQUIPMENT. MOST
 OF THIS SEEMS TO BE DONE HOWEVER PLEASE SEE THE
 EQUIPMENT SCHEDULES ON E1.02 AND BE SURE ALL
 COORDINATE.
 PLEASE KNOW MANY OF THESE ITEMS SEEM TO BE MISPRINTS
 FOR ACTUAL LOADS ETC.
 REDLINED SHEETS ON ONE SET. FBC 106.1.2 FOR
 COORDINATION.
 MAY CALL TO GO OVER.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE INDICATE THE REQUIRED SHUNT OF ALL
 ELECTRICAL UNDER HOODS PER NFPA-96.
 PLEASE SEE SOME EQUIPMENT IS ALREADY BEING NOTED AS
 HAVING THE SHUNT TRIP BREAKERS, BUT NOT ALL.
  
 11) NOTE: THIS NOTE REMAINS FROM PREVIOUS REVIEW NOTE #
 22. THE ENGINEER'S FIRM RESPONSE MENTIONS *NOT
 PROVIDED* PER FIRM.
 THE ARCHITECT'S RESPONSE MENTIONS THIS WAS COMPLETED IN
 TITLE BLOCKS HOWEVER UPON REVIEW OF SEVERAL SHEETS
 INCLUDING CHECKING THE TITLE BLOCKS OF OTHER TRADES,
 THIS WAS NOT COMPLETED AS NEEDED AND AS REQUESTED.
 PLEASE BE SURE THE TITLE BLOCKS REFLECT THE ADDRESS AND
 SUITE/UNIT NUMBER FOR NEW BUILD-OUT. FAC 61G15-23.002,
 61G1-16.004
  
 12) NOTE: PLEASE CLARIFY HOW IT IS DIMMERS ARE BEING
 SHOWN ON LIGHTING WHICH IS LOCATED IN THE EGRESS
 PATHS.
 PLEASE SEE LS 101 7.8 AND 7.9.
 PLEASE PROVIDE THE MINIMUM LEVELS ARE NEEDED ON THESE
 PATHS.
 PLEASE SEE FAC 61G15-33.004.
 FBC 106.1.2
  
 13) NOTE: PLEASE SEE ATTACHED COPY OF FS 553.80(2)(B)
 WITH RESPECT TO DESIGN PROFESSIONALS AND REPEAT
 COMMENTS FOR CODE COMPLIANCE.
 PLEASE KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
 PLEASE ALSO KNOW THAT ONE SET OF ELECTRICAL PLANS AND
 ENERGY CALCULATIONS ARE BEING RETAINED BY THIS OFFICE
 AT THIS TIME.
  
 AS STATED ON THE PREVIOUS REVIEW:
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-08-25 07:55:042007-08-25 07:55:04
  
 REVIEW CONTINUED
2007-08-24 21:04:562007-08-24 21:04:56
  
 PLANS ARE IN ELEC FOR REVIEW.
 REVIEW TO CONTINUE ON 8/25, NOTES WILL FOLLOW ONCE
 REVIEW IS COMPLETE.
 PLANS WILL BE GOING INTO A *F* STATUS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-10 Cont ID  
Sent By dpalmer Date 2007-05-10 Time 15:45 Rev Time 0.00
Received By dpalmer Date 2007-05-10 Time 15:45 Sent To  
Notes
2007-05-10 15:45:23** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE KNOW THAT CODE ADOPTED AS OF DECEMBER
 8TH, 2006 IS LISTED AS FOLLOWS.
 PLEASE SEE THERE ARE PARTS OF THE PLANS WHICH REFLECT A
 2004 NEC AND A 2002 NEC.
 PLEASE KNOW THAT THERE WAS NOT ANY 2004 NEC. PLEASE
 LIST THE FOLLOWING CODES AT A MINIMUM ON THE ELECTRICAL
 PAGES AND ARCHITECTURAL SHEETS. SOME CODES ARE ALREADY
 REFLECTED ON PLANS, HOWEVER WILL BE AS FOLLOWS FOR
 INFORMATION AS SOME NEED TO BE CHANGED. 2005 NFPA-70
 (NEC).
 2003 NFPA- 101
 2002 NFPA-72
 2004 FBC W/2006 REVISIONS.
 AS STATED, SOME OF THESE ARE DONE ALREADY. PLEASE
 COORDINATE.
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13.
 PLEASE SUBMIT COMPLETED ENERGY CALCULATIONS/PERFORMANCE
 CALCULATIONS. 13-415.1.AB.1.1, 13-415.2
 PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING LINE OR
 LOW VOLTAGE.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR LIGHTING
 CONTROLS, OVER RIDES, OVER RIDE LOCATION, OVER RIDE
 TIMES, SCHEDULING ETC.
 PLANS ONLY INDICATE STANDARD SWITCHES.
 PLEASE SEE ZONES BASED ON SQ FT.
 PLEASE SEE ALL OF CHAPTER 13, THERE ARE MANY ITEMS
 WHICH CAN NOT BE REVIEWED AT THIS TIME.
  
 3) NOTE: PLEASE SEE THE OCCUPANCY STATED ON PLANS IS
 STATED A *COMMERCIAL*? PLEASE VERIFYAND SEE ANY
 COMMENTS FROM OTHER TRADES FOR THIS.
 FBC 106.1.2
  
 4) NOTE: ** NOT A COMMENT FOR FORMICA AND ASSOC. PLEASE
 SEE THE CERTIFICATE OF AUTHORIZATION NUMBER LISTED FOR
 THE STRUCTURALLY ENGINEERING FIRM IS *DELINQUENT* AS OF
 THIS REVIEW DATE. PLEASE SEE THE ATTACHED PRINT OUT
 FROM THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION WHICH SHOWS THIS.
 PLEASE ALSO SEE THE ADDRESS ON TITLE BLOCKS IS NOT THAT
 AS LISTED WITH THE STATE OF FLORIDA.
 ** PLEASE KNOW THE ABOVE IS REQUIRED WHETHER OR NOT
 COMMENT IS MADE BY ANY OTHER TRADE.
  
 5) NOTE: PLEASE BE SURE ALL RAISED SEALS FOR THE
 ARCHITECT OF RECORD ARE CLEAR AND VISIBLE WITH ALL
 INFORMATION ON SAID SEALS AS REQUIRED PER FAC 61G1-16.
 PLEASE SEE THERE ARE SOME SEALS WHICH ARE NOT
 CLEAR/VISIBLE WITH SOME INFORMATION.
  
 6) NOTE: PLEASE KNOW THAT ALL LOW VOLTAGE WILL BE
 REQUIRED TO BE UNDER SEPARATE PERMIT.
  
 7) NOTE: PLEASE SEE THE CODE SECTION FOR GFI PROTECTION
 FOR ALL RECEPTACLES IN KITCHEN AREAS SHOULD BE 210.8B3.
 THIS SECTION SEEMS TO BE MISPRINTED ON PLANS.
  
 8) NOTE: PLEASE SEE 408.4 WHICH REQUIRES ALL CIRCUITS
 TO BE SPECIFIC TO ALL ROOMS, AREAS, LOCATIONS AND
 CIRCUIT SPECIFIC. PLEASE SEE THE FOLLOWING TEXT FROM
 THE NEC.
 **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO
 REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.1.2
  
 9) NOTE: PLEASE SHOW ALL DEVICE LOCATIONS AND LEVELS
 FOR ADA COMPLIANCE FOR HORN, STROBES. PER FBC
 11.4-28.1, .2 AND .3(4).
 ** PLEASE KNOW EVEN AS THE FIRE ALARM PERMIT WILL BE
 SEPARATE ALONG WITH FIRE SPRINKLER, THE BASE BUILDING
 PLANS MUST SHOW THE MINIMUM REQUIRED INTENDED SYSTEM.
 FBC 106.3.5.1.1
  
 10) NOTE: PLEASE SEE THE CIRCUIT L2-36 WHICH APPEARS TO
 BE IN PLACE FOR THE REQUIRED SIGN CIRCUIT, HOWEVER
 PLEASE SEE 600.5 AS THE LOAD OF 1200VA PER OUTLET , MAY
 NOT FEED ANY OTHER OUTLETS. PLEASE ALSO INDICATE IF
 INDEED THIS IS FOR THE SIGN CIRCUIT(S).
  
 11) NOTE: PLEASE SEE L2-31 WHICH IS SHOWN FEEDING
 HOUSE/COMMON AREA WHICH MAY NOT BE FED FROM THE TENANT
 SPACE. THIS WOULD BE SHOWN FROM A HOUSE PANEL CIRCUIT.
 210.25, 240.24
  
 12) NOTE: PLEASE SEE THE MINIMUM CLEARANCES ARE NOT
 SHOWN FOR THE ELECTRICAL PANELS. IN FACT THERE ARE
 ITEMS/RACKS OR SOME OTHER NON-ELECTRICAL EQUIPMENT
 SHOWN ON PLANS WHICH ARE SHOWN IN THE AREA ABOUT
 ELECTRICAL EQUIPMENT WHICH IS NOT PERMITTED. 110.26
  
 13) NOTE: PLEASE SEE THE PLANS ARE MISSING THE LOCATION
 FOR THE REQUIRED DISCONNECT AND TRANSFORMER. PLEASE SEE
 110.26 AND 450 AS NO REVIEW FOR THIS CAN BE DONE AT
 THIS TIME.
 PLEASE SEE 450.9, 450.13 ETC AS THE TRANSFORMER MAY NOT
 BE ABOVE CEILING.
 PLEASE ALSO SUBMIT STRUCTURAL ENGINEERED DETAIL AT THIS
 TIME FOR THE LOCATION AND HOW THIS UNIT WILL BE
 INSTALLED.
 ** PLANS CURRENTLY MENTION THE LOCATION OF THE
 TRANSFORMER IS TO BE DETERMINED BY THE BUILDING
 ENGINEER, HOWEVER THE NEC DETERMINES LOCATION BASED ON
 WIRING METHODS, CLEARANCES, ETC. THE STRUCTURAL ELEMENT
 WILL THEN BE THE CONSIDERATION FOR NEEDED STRUCTURAL
 SUPPORT ETC.
 ** SOME ELECTRICAL CODE COMPLIANCE ITEMS CAN NOT BE
 REVIEWED AT THIS TIME**
  
 14) NOTE: PLEASE INDICATE IF THE PANEL *L* SECTION 1
 CONTAINS FEED-THRU LUGS OR IS THERE OVER CURRENT
 PROTECTION IN THIS PANEL WHICH FEEDS PANEL *L* SECTION
 2?
 FBC 106.1.2
  
 15) NOTE: PLEASE SEE THE TAPPED CONDUCTORS ON THE
 SECONDARY SIDE OF THE TRANSFORMER ARE NOT OF SUFFICIENT
 SIZE PER 310.16, 240.21C.
 PLEASE SEE THAT THE TAPPED CONDUCTORS SHALL TERMINATE
 IN OCP WHICH LIMITS THE LOAD ON THE CONDUCTOR WHICH IT
 IS RATED. (MAY NOT GO TO NEXT SIZE UP) (600MCM MIN).
  
 16) NOTE: PLEASE COORDINATE THE RISER AND THE PANEL
 SCHEDULES AS THE PANELS *L* SECTIONS ONE AND TWO ARE
 BOTH BEING SHOWN AS 225AMP PANELS, YET THE RISER SHOWS
 400AMP OVER CURRENT PROTECTION FEEDING THESE PANELS??
 PLEASE SEE THE LOADS ON PANEL *L* AFTER DE-RATING
 EXCEED THAT OF THE RATING OF THESE PANELS.
  
 17) NOTE: PLEASE SEE THE EQUIPMENT GROUNDING CONDUCTORS
 ON RISER DIFFER FROM THOSE INDICATED ON PANELS *L* ONE
 AND TWO.
 PLEASE CORRELATE.
 FBC 106.1.2
  
 18) NOTE: PLEASE COMPLETE THE FIXTURE LEGEND WITH ALL
 INFORMATION ON FIXTURES BEING INSTALLED AND THE NUMBER
 OF FIXTURES. PLEASE SEE THE COMMENT ABOVE WITH RESPECT
 TO THE FBC CHAPTER 13.
 FBC 106.1.2, 106.3.5.1.2
  
 19) NOTE: PLEASE SUBMIT THE COMPLETED LOAD CALCULATIONS
 ON SERVICE AND THE ADDED LOAD TO THE EXISTING MAIN
 SERVICE WITH NEW LOAD ADDED.
 THE PLANS CURRENTLY ONLY SHOW THE LOAD CALCULATIONS ON
 *L*.
 220 (ALL), 215.5, CONTINUOUS LOADS PER 215.3, 230.42
 ETC
 FBC 106.3.5.1.2, 106.1.2.
 ** PLEASE BE SURE TO OBTAIN ANY INFORMATION FROM OTHER
 POSSIBLE BUILD-OUTS FOR NEW TENANTS WHICH *WILL* AFFECT
 THE LOAD CALCULATIONS ON MAIN SERVICE.
  
 20) NOTE: PLEASE SEE INDICATE THE REQUIRED SHUNT OF ALL
 ELECTRICAL UNDER HOODS PER NFPA-96.
 PLEASE SEE SOME EQUIPMENT IS ALREADY BEING NOTED AS
 HAVING THE SHUNT TRIP BREAKERS, BUT NOT ALL.
  
 21) NOTE: PLEASE SEE 424.3B FOR THE MINIMUM OCP FOR THE
 AHU/HEAT. THE MINIMUM OCP IS TO BE SIZED AT 125%.
  
 22) NOTE: PLEASE BE SURE THE TITLE BLOCKS REFLECT THE
 ADDRESS AND SUITE/UNIT NUMBER FOR NEW BUILD-OUT. FAC
 61G15-23.002, 61G1-16.004
  
 23) NOTE: PLEASE SEE THE BASED BUILDING PLANS HAD THE
 *DEMO PLANS* REMOVED FOR THE INTERIOR DEMO PERMIT,
 THESE SHEETS NEED TO BE REPLACED IN THIS SET OF PLANS.
  
 **PLEASE KNOW THERE MAY BE NEW COMMENTS IN THE FUTURE
 AS SOME ITEMS CAN NOT BE REVIEWED AT THIS TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2008-05-19 Cont ID  
Sent By mawillia Date 2008-05-19 Time 11:11 Rev Time 0.00
Received By mawillia Date 2008-05-19 Time 10:30 Sent To B1
Notes
2008-05-19 11:10:49*****REVISION #6, DATED 4/22/08, APPROVED*****
  
 REVISED PLAN SHEETS A-3, A-3.1, A-3.2, D-1, D-2, AND
 S-1 THRU S-6 WERE REVIEWED;SHEET A-3.2 STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2008-04-01 Cont ID  
Sent By mawillia Date 2008-04-01 Time 16:30 Rev Time 0.00
Received By mawillia Date 2008-04-01 Time 16:16 Sent To  
Notes
2008-04-01 16:28:13*****REVISION #5, DATED 3/10/08, APPROVED*****
  
 REVISED PLAN SHEETS A-3, A-7, A-8, AND D-1 WERE
 REVIEWED;HOWEVER, NO FIRE-STAMPING NEEDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-02-01 Cont ID  
Sent By mwennerg Date 2008-02-01 Time 11:24 Rev Time 0.00
Received By mwennerg Date 2008-02-01 Time 11:24 Sent To  
Notes
2008-02-01 11:25:11REVISION DATED 1/11/08 STAMPED LIFE SAFETY SHEET A-3.2.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-01-31 Cont ID  
Sent By mwennerg Date 2008-01-31 Time 15:03 Rev Time 0.00
Received By mwennerg Date 2008-01-31 Time 15:03 Sent To  
Notes
2008-01-31 15:04:09REVISED SHEET FA1.01

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-10-23 Cont ID  
Sent By mawillia Date 2007-10-23 Time 15:53 Rev Time 0.00
Received By mawillia Date 2007-10-23 Time 15:26 Sent To  
Notes
2007-10-23 15:43:50*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS A-3.2, A-4, E2.01, FA1.01,
 AND FP-3.1 WERE STAMPED, INITIALED, AND DATED

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-10-11 Cont ID  
Sent By mwennerg Date 2007-10-11 Time 13:03 Rev Time 0.00
Received By mwennerg Date 2007-10-11 Time 13:03 Sent To  
Notes
2007-10-11 13:08:21***DENIED***
  
 02.) OK
  
 08.) OK
  
 09.) OK
  
 NEW COMMENT:
  
 1) FIRE PROTECTION AND ALARM SYSTEMS REQUIRE A
 PROFESSIONAL ENGINEER TO SIGN, SEAL AND DATE ALL PLANS,
 SPECIFICATIONS ETC TO BE FILED FOR PUBLIC RECORD. FP-1
 AND FP-3.1
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-08-29 Cont ID  
Sent By mawillia Date 2007-08-29 Time 10:48 Rev Time 0.00
Received By mawillia Date 2007-08-29 Time 10:17 Sent To E
Notes
2007-08-29 10:48:42*****UNSAT*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 REVIEW STILL NEED TO BE ADDRESSED:
  
 02.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.NO ADDRESS IN THE TITLE
 BLOCK FOR THE M, P, AND E PLAN SHEETS
  
 08.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL
 BE CLASS A, CLASS B, OR CLASS C.IT IS NOTED ON SHEET
 A-5 THAT THE INTERIOR WALLS FINISH TO BE CLASS "A" ,
 HOWEVER THE CLASSIFICATION OF THE CEILING FINISH IS NOT
 NOTED
  
 09.WILL THE SCOPE OF WORK HAVE CAUSE FOR FIRE
 SPRINKLERS TO BE MODIFIED?IF SO SEPARATE PLANS WILL
 BE REQUIRED.PLEASE ACKNOWLEDGE
  
  
  
  
 TO EXPIDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW / WHERE EACH ITEM WAS ADDRESSED.
  
 CAPT. MICHAEL WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-08 Cont ID  
Sent By mawillia Date 2007-06-08 Time 11:38 Rev Time 0.00
Received By mawillia Date 2007-06-08 Time 09:51 Sent To  
Notes
2007-06-08 11:16:34*****DENIED*****
  
  
 01.THE SITE LOCATION INDICATED ON THE COVER SHEET
 SHOWS THIS STRUCTURE AT THE SOUTHEAST CORNER OF
 HIBISCUS STREET AND SOUTH ROSEMARY AVENUE.THE
 NUMERICAL ADDRESS FOR THIS SITE WOULD BE 700 INSTEAD OF
 701.PLEASE VERIFY
  
 02.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.BE ADVISED THAT THE ZIP
 CODE FOR THIS AREA IS 33401 NOT 33305(SEE S SHEETS)
  
 03.PLEASE INDICATE IF THIS ASSEMBLY OCCUPANCY IS
 EXISTING OR NEW.
  
 04.THE REMOVAL AND/OR REPLACEMENT OF BUILDING
 MATERIALS & SUPPLIES SHALL NOT HINDER OR INTERFERE WITH
 EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ROADS, FIRE LANES).
  
 05.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 06.SHOW/DISPLAY THE SUITE NUMBER ON THE THE
 APPROPIATE EXTERIOR ELEVATION AS TO BE DISTINGUISHABLE
 FROM OTHER SUITESOF THIS BUILDING.
  
 07.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN
 AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS
 SHALL BE PERMITTED TO BE PROVIDED WITH PANIC HARDWARE
 OR FIRE EXIT HARDWARE.
  
 08.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL
 BE CLASS A, CLASS B, OR CLASS C.BE SPECIFIC
  
 09.WILL THE SCOPE OF WORK HAVE CAUSE FOR FIRE
 SPRINKLERS TO BE MODIFIED?IF SO SEPARATE PLANS WILL
 BE REQUIRED.
  
 10.SHOW THE LOCATION OF THE 2A:10BC FIRE EXTINGUISHER
 WHICH SATISFY 75' TRAVEL DISTANCE.
  
  
 TO EXPIDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW / WHERE EACH ITEM WAS ADDRESSED.
  
 CAPT. MICHAEL WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 5 Status N Date 2007-10-29 Cont ID  
Sent By kstevens Date 2007-10-29 Time 18:04 Rev Time 0.00
Received By kstevens Date 2007-10-29 Time 18:04 Sent To  
Notes
2007-10-29 18:05:53SEPARATE GAS PERMIT REQUIRED. SUBMIT PLANS, MANUF.
 SPECIFICATION SHEETS AND ALL REQUIRMENTS FROM GAS
 PERMIT APPLICATION CHECK LIST WITH PERMIT APPLICATION.
 ITEM 29 NOT APPROVED WITHOUT LISTING, MANUF.
 INSTALLATION INSTRUCTIONS & CERTIFICATION OF BTU LOAD
 PER HR.

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2007-10-27 Cont ID  
Sent By kstevens Date 2007-10-27 Time 17:17 Rev Time 0.00
Received By kstevens Date 2007-10-27 Time 17:17 Sent To  
Notes
2007-10-27 17:23:23DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 **********NEW COMMENT**********
  
 1D. NEW ITEM #29 NOT APPROVED. PER SECTION 301.3
 APPLIANCES REGULATED BY THIS CODE SHALL BE LISTED AND
 LABELED. PLEASE PROVIDE LISTING FOR THIS PRODUCT AND
 SHOW GAS LOAD PER HOUR AS INDICATED BY TESTING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-10-03 Cont ID  
Sent By kstevens Date 2007-10-03 Time 14:10 Rev Time 0.00
Received By kstevens Date 2007-10-02 Time 12:40 Sent To  
Notes
2007-10-03 14:12:13DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. SHTS P1.01 & P2.01 SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR REVIEW PRIOR TO
 ISSUING THE GAS PERMIT:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE ARCHITECT INDICATED THAT
 FORMICA WILL RESPOND TO COMMENT. PLEASE COMMUNICATE
 WITH ARCHITECT.
 ******RESPONSE NOTED, BUT ITEM 59 (TILT SKILLET), AND
 THE WATER HEATER MANUF SHEETS HAVE NOT BEEN SUBMITTED.
  
 F. N/A
 G. N/A
 H. OK
 10. OK
  
 **********NEW COMMENTS**********
  
 1C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).THE MANUF SHEETS SUBMITTED DO NOT REFLECT
 THE BTU LOADS INDICATED ON THE RISER DIAGRAM FOR ALL
 BUT ITEM 31. PLEASE MAKE SURE THAT THE GAS RISER
 DIAGRAM REFLECTS THE MANUF SHEETS FOR THE BTU LOADS.
 ALSO MAKE SURE THE TOTAL BTU LOAD IS CORRECT.
  
 2C. SHOW THE REGULATORS ON THE GAS RISER DIAGRAM. THE
 SHUT OFF VALVE SHALL BE UPSTREAM OF THE REGULATORS AND
 A UNION IS REQUIRED IF THE REGULATOR IS NOT AT THE END
 OF A RUN. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR
 THE REGULATOR BEING USED. SECTIONS 106.1.2. &409.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY.A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-08-27 Cont ID  
Sent By kstevens Date 2007-08-27 Time 18:55 Rev Time 0.00
Received By kstevens Date 2007-08-27 Time 14:21 Sent To  
Notes
2007-08-27 18:56:22DENIED
  
 SEE COMMENTS FROM PLUMBING REVIEW THIS DATE.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-06-07 Cont ID  
Sent By kstevens Date 2007-06-07 Time 11:23 Rev Time 0.00
Received By kstevens Date 2007-06-07 Time 11:23 Sent To  
Notes
2007-06-07 11:24:49DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHTS P1.01 & P2.01 SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR REVIEW PRIOR TO
 ISSUING THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. TYPE OF GAS, (LP OR NATURAL).
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (TO BE DETERMINED WHEN
 COMMENT (A) IS ADDRESSED.
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 F. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 G. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2008-10-24 Cont ID  
Sent By adarroug Date 2008-10-24 Time 16:44 Rev Time 0.00
Received By adarroug Date 2008-10-24 Time 16:44 Sent To E
Notes
2008-10-24 16:45:03TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2008-10-10 Cont ID  
Sent By adarroug Date 2008-10-10 Time 14:26 Rev Time 0.00
Received By adarroug Date 2008-10-10 Time 14:26 Sent To E
Notes
2008-10-10 14:26:28TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2008-10-03 Cont ID  
Sent By adarroug Date 2008-10-03 Time 16:34 Rev Time 0.00
Received By adarroug Date 2008-10-03 Time 16:34 Sent To  
Notes
2008-10-03 16:34:32TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2008-09-04 Cont ID  
Sent By adarroug Date 2008-09-04 Time 10:34 Rev Time 0.00
Received By adarroug Date 2008-09-04 Time 10:34 Sent To E
Notes
2008-09-04 10:34:45TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2008-05-19 Cont ID  
Sent By adarroug Date 2008-05-19 Time 09:41 Rev Time 0.00
Received By adarroug Date 2008-05-19 Time 09:41 Sent To FIRE
Notes
2008-05-12 11:04:20TO "MWILLIAMS" DESK--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2008-05-12 Cont ID  
Sent By adarroug Date 2008-05-12 Time 11:01 Rev Time 0.00
Received By adarroug Date 2008-05-12 Time 11:01 Sent To P
Notes
2008-05-12 11:01:51TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2008-05-06 Cont ID  
Sent By adarroug Date 2008-05-06 Time 15:06 Rev Time 0.00
Received By adarroug Date 2008-05-06 Time 15:06 Sent To B
Notes
2008-05-06 15:06:52TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2008-04-30 Cont ID  
Sent By adarroug Date 2008-04-30 Time 14:03 Rev Time 0.00
Received By adarroug Date 2008-04-30 Time 14:03 Sent To E
Notes
2008-04-30 14:03:22TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2008-04-30 Cont ID  
Sent By adarroug Date 2008-04-30 Time 11:55 Rev Time 0.00
Received By adarroug Date 2008-04-30 Time 11:55 Sent To M
Notes
2008-04-30 11:56:10TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-04-04 Cont ID  
Sent By adarroug Date 2008-04-04 Time 14:58 Rev Time 0.00
Received By adarroug Date 2008-04-04 Time 14:58 Sent To P
Notes
2008-04-04 14:59:12TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-04-04 Cont ID  
Sent By adarroug Date 2008-04-04 Time 10:34 Rev Time 0.00
Received By adarroug Date 2008-04-04 Time 10:34 Sent To E
Notes
2008-04-04 10:34:52TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-03-13 Cont ID  
Sent By adarroug Date 2008-03-13 Time 11:19 Rev Time 0.00
Received By adarroug Date 2008-03-13 Time 11:19 Sent To  
Notes
2008-03-13 11:24:27WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-03-05 Cont ID  
Sent By adarroug Date 2008-03-05 Time 10:18 Rev Time 0.00
Received By adarroug Date 2008-03-05 Time 10:18 Sent To B
Notes
2008-03-05 10:18:37TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-02-28 Cont ID  
Sent By adarroug Date 2008-02-28 Time 10:47 Rev Time 0.00
Received By adarroug Date 2008-02-28 Time 10:47 Sent To E
Notes
2008-02-28 10:49:34TO "E" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-02-25 Cont ID  
Sent By adarroug Date 2008-02-25 Time 09:04 Rev Time 0.00
Received By adarroug Date 2008-02-25 Time 09:04 Sent To B
Notes
2008-02-25 09:04:50TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-02-21 Cont ID  
Sent By adarroug Date 2008-02-21 Time 11:32 Rev Time 0.00
Received By adarroug Date 2008-02-21 Time 11:32 Sent To B
Notes
2008-02-21 11:33:18TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-01-25 Cont ID  
Sent By shill Date 2008-01-25 Time 16:07 Rev Time 0.00
Received By shill Date 2008-01-25 Time 16:07 Sent To  
Notes
2008-01-25 16:10:01TO "COMM" BD#9--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-01-25 Cont ID  
Sent By shill Date 2008-01-25 Time 15:50 Rev Time 0.00
Received By shill Date 2008-01-25 Time 15:50 Sent To P
Notes
2008-01-25 15:51:04TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-01-25 Cont ID  
Sent By shill Date 2008-01-25 Time 15:47 Rev Time 0.00
Received By shill Date 2008-01-25 Time 15:47 Sent To FIRE
Notes
2008-01-25 15:47:34TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-25 Cont ID  
Sent By shill Date 2008-01-25 Time 15:33 Rev Time 0.00
Received By shill Date 2008-01-25 Time 15:33 Sent To E
Notes
2008-01-25 15:34:21TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-19 Cont ID  
Sent By shill Date 2007-10-19 Time 15:49 Rev Time 0.00
Received By shill Date 2007-10-19 Time 15:49 Sent To  
Notes
2007-10-23 09:30:09TO "COMM" BD#48
2007-10-19 15:50:13WAITING FOR "COMM" BD--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-25 Cont ID  
Sent By adarroug Date 2007-09-25 Time 10:19 Rev Time 0.00
Received By adarroug Date 2007-09-25 Time 10:19 Sent To  
Notes
2007-09-25 10:29:45TO "COMM" BD#45--EXPEDITED--
2007-09-25 10:19:14WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-07 Cont ID  
Sent By dpalmer Date 2007-08-07 Time 20:39 Rev Time 0.00
Received By dpalmer Date 2007-08-07 Time 20:39 Sent To  
Notes
2007-08-24 14:24:09TO "COMM" BD#33--EXPEDITED PERMIT--
2007-08-07 20:39:23PLANS WAITING FOR COMM BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-08 Cont ID  
Sent By mawillia Date 2007-06-08 Time 11:38 Rev Time 0.00
Received By mawillia Date 2007-04-24 Time 16:01 Sent To  
Notes
2007-05-04 09:52:50TO "COMM" BD#40
2007-04-24 16:01:36WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-05-01 Cont ID  
Sent By tgordon Date 2008-05-01 Time 14:42 Rev Time 0.30
Received By tgordon Date 2008-05-01 Time 14:42 Sent To  
Notes
2008-05-01 14:43:21REVISION TO MECH. PLAN PAGE M1.01.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-10-24 Cont ID  
Sent By tgordon Date 2007-10-24 Time 09:29 Rev Time 0.30
Received By tgordon Date 2007-10-24 Time 09:28 Sent To  
Notes
2007-10-24 09:29:56ADDITIONAL MECHANICAL PERMITS REQUIRED FOR
 (A) WALK-IN-COOLER
 (B) KITCHEN HOOD
 (C) FIRE SUPPRESSION
 ** SUBMIT PLANS WITH PERMIT APPLICATION.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-10-10 Cont ID  
Sent By tgordon Date 2007-10-10 Time 10:59 Rev Time 1.30
Received By tgordon Date 2007-10-10 Time 10:59 Sent To  
Notes
2007-10-10 11:09:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) FIRM LICENSE NUMBER IN THE TITLE BLOCK FOR A.J.O.
 ARCH. IS INCORRECT SEE RED LINE ON PLANS, PLEASE
 CORRECT PER FAC 61G1-16.004 TITLE BLOCK.
  
 2) PAGE M2.01 AIR BALANCE SCHEDULE HAS INCORRECT
 INFORMATION IN IT, BATH EXHAUST SHOWS 500 SHOULD SHOW
 550 (EF-1 50CFM'S AND TWO EF-2 AT 250 CFM'S EACH =550
 CFM'S). ALSO THE TOTALS FOR O/A, R/A, AND PRESSURE/CFM
 ARE INCORRECT, PLEASE CORRECT AND COMPLY WITH 2004 FBC
 13-409.1.ABC.3.6.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status   Date 2007-10-05 Cont ID  
Sent By rregueir Date 2007-10-05 Time 15:24 Rev Time 0.00
Received By rregueir Date 2007-10-05 Time 14:39 Sent To  
Notes
2007-10-05 15:25:01PUT BACK ON SHELF FOR TOM GORDON.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-08-28 Cont ID  
Sent By tgordon Date 2007-08-28 Time 09:45 Rev Time 2.50
Received By tgordon Date 2007-08-28 Time 09:45 Sent To  
Notes
2007-08-28 10:03:54PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT
 (FIRM LICENSE AND JOB ADDRESS) ON EACH PAGE AS NOTED IN
 LAST REVIEW 5-10-07 NOTE #7.SEE FAC 61G1-16.004 TITLE
 BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 2) ENERGY CALCULATIONS ARE A PHOTO COPY. ENERGY
 CALCULATIONS NEED TO BE SIGNED AND SEALED BY A
 ARCHITECT OR ENGINEER, SEE 4004 FBC 13-103.1.1.1.
  
 3) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 4) NEED TO SHOW THE EER OF THE A/C EQUIPMENT IN THE
 "AIR CONDITIONING UNIT DATA" ON PAGE M2.01, SEE FBC
 13-407.1.ABC.3.2.1.
  
 5) PAGE M2.01 AIR BALANCE SCHEDULE SHOWS THE BUILDING
 AT A POSITIVE PRESSURE OF 2180. PLEASE SHOW COMPLIANCE
 WITH 2004 FBC 13-409.1.ABC.3.6.1 NONRESIDENTIAL KITCHEN
 SPACES.
 NONRESIDENTIAL KITCHEN SPACE AND AREAS IN DINING ROOMS
 OR OPEN MALLS WHERE A KITCHEN EXHAUST HOOD IS REQUIRED
 BY NFPA 96 SHALL COMPLY WITH THE FOLLOWING
 REQUIREMENTS:
 (1) BE DESIGNED WITH AN EXHAUST AIR AND MAKE UP AIR
 BALANCE SUCH THAT THE SPACE IS NEVER UNDER A POSITIVE
 PRESSURE, AND NEVER UNDER A NEGATIVE PRESSURE EXCEEDING
 0.02 INCH W.G. RELATIVE TO ALL INDOOR SPACES
 SURROUNDING THE KITCHEN SPACE, DURING ALL COOKING
 HOURS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-10 Cont ID  
Sent By tgordon Date 2007-05-10 Time 09:32 Rev Time 3.00
Received By tgordon Date 2007-05-10 Time 09:32 Sent To  
Notes
2007-05-10 10:10:43*** DENIED ***
 A COMPLETE MECHANICAL REVIEW CAN NOT BE DONE DUE TO A
 LACK OF INFORMATION.
  
 1) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-400.
  
 2) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-407.1.ABC.1.
  
 3) PLEASE SUBMIT DETAILED MANUFACTURER'S SPECIFICATION
 SHEETS FOR A/C SYSTEMS AND INDICATE WHICH UNITS ARE
 BEING INSTALLED.
  
 4) PLEASE SUBMIT INFORMATION ON EXISTING A/C SYSTEMS
 FOR THIS SPACE BEING REMOVED.
  
 5) PLEASE PROVIDE INFORMATION REGARDING THE KITCHEN
 EXHAUST HOODS (ENGINEERING ON HOODS NOT REQUIRED AT
 THIS TIME) NEED SPEC'S. ON HOODS TO KNOW CORRECT
 EXHAUST AIR AND MAKE-UP AIR IF BEING PROVIDE BY HOODS.
 IF NOT PLEASE STATE WERE MAKE-UP AIR IS COMING FROM.
  
 6) PLEASE CHECK AIR BALANCE SCHEDULE ON PAGE M2.01 TO
 BE CERTAIN THE BUILDING NEEDS TO BE AT A +6450 TOTAL
 PRESSURE.
  
 7) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK OF
 ALL PAGES.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 8 Status F Date 2008-05-20 Cont ID  
Sent By kstevens Date 2008-05-20 Time 12:07 Rev Time 0.00
Received By kstevens Date 2008-05-20 Time 12:07 Sent To  
Notes
2008-05-20 12:15:17DENIED
 REFERENCE: FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS P2.01 & P2.02 SHOW REVISIONS 6 & 7 IN THE
 REVISION INDEX, BUT REVISIONS 6 & 7 ARE NOT SHOWN ON
 THE FLOOR PLAN. ALL REVISIONS SHALL BE CLOUDED AND THE
 REVISION NUMBER INDICATED ON THE FLOOR PLAN IN ORDER TO
 KEEP RECORD OF ALL REVISIONS AND TO HELP EXPEDITE PLAN
 REVIEW OF REVISIONS. SECTION 106.1.3.
  
 2. SHTS P2.01 & P2.O2 ALL REVISIONS TO A SIGNED,
 SEALED, DATED PLAN SHALL BE SIGNED, SEALED & DATED BY
 THE ENGINEER OF RECORD. SECTION 106.1. FAC
 61G15-23-002(1)(2) & FS 471.025.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 7 Status F Date 2008-04-12 Cont ID  
Sent By adarroug Date 2008-05-12 Time 11:03 Rev Time 0.00
Received By kstevens Date 2008-04-12 Time 10:13 Sent To  
Notes
2008-04-12 10:17:18DENIED
 REFERENCE: FBC-2004 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2004 CHAPTER 1
  
 1. REVISIONS TO A SIGNED, SEALED SET OF PLANS SHALL BE
 DRAWN, SIGNED, SEALED & DATED BY THE ENGINEER OF RECORD
 AND SUBMITTED WITH REQUIRED TITLE BLOCKS PER FAC
 61G15-23.002(2) & FS 471.025 AS WELL AS SECTION
 106..1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 6 Status F Date 2008-02-12 Cont ID  
Sent By kstevens Date 2008-02-12 Time 10:44 Rev Time 0.00
Received By kstevens Date 2008-02-12 Time 10:43 Sent To  
Notes
2008-02-12 10:47:27REVISION DENIED
 REFERENCE: FBC-2004 CHAPTER 1
  
 1.SHT P1.03 REVISION NUMBER 5 INDICATED IN THE REVISION
 INDEX WAS NOT FOUND ON THE FLOOR PLAN. PLEASE CLOUD AND
 DELTA ALL REVISIONS. SECTIONS 106.1.3 & 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-02-12 Cont ID  
Sent By kstevens Date 2008-02-12 Time 10:40 Rev Time 0.00
Received By kstevens Date 2008-02-12 Time 10:40 Sent To  
Notes
2008-02-12 10:43:50REVISIONS APPROVED--SHTS P1.01, P1.02, P2.01, P2.02
 & P2.03.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-10-27 Cont ID  
Sent By kstevens Date 2007-10-27 Time 17:16 Rev Time 0.00
Received By kstevens Date 2007-10-27 Time 17:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-10-03 Cont ID  
Sent By kstevens Date 2007-10-03 Time 12:06 Rev Time 0.00
Received By kstevens Date 2007-10-02 Time 12:39 Sent To  
Notes
2007-10-03 14:10:18DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW DATED 06-07-07. COMMENT
 NUMBERS TO REMAIN THE SAME.
 ******FROM PREVIOUS REVIEWS:
  
 1. THE COVER AND ALL ARCHITECTURAL SHEETS REQUIRE THE
 FIRM LICENSE NUMBER. (CERTIFICATE OF AUTHORIZATION), IN
 THE TITLE BLOCK. FAC 61G1-16.004(2) & FS 481.219,
 481.2055.
 ****RESPONSE NOTED, BUT THE FIRM LICENSE NUMBER DOES
 NOT REFLECT THE LICENSE NUMBER ON THE FLORIDA STATE
 DBPR WEBSITE. PLEASE UPDATE THE DBPR WEBSITE OR THE
 TITLE BLOCK ADDRESS PRIOR TO RESUBMITTING FOR PLAN
 REVIEW. (SEE ATTACHED SHEET). ALSO THE FIRM LICENSE
 NUMBER AND CORRECT ADDRESS SHALL BE INDICATED ON ALL
 SHEETS WITH ARCHITECTURAL TITLE BLOCK. ******RESPONSE
 NOTED, BUT THE ADDRESS ON THE TITLE BLOCK DOES NOT
 REFLECT THE ADDRESS OF RECORD ON THE FLORIDA STATE DBPR
 WEBSITE. EITHER UPDATE THE DBPR WEBSITE OR THE TITLE
 BLOCKS PRIOR TO RESUBMITTING FOR REVIEW.
  
 2. OK
 3. OK
  
 4. SHT A-9 SHOW COMPLIANCE WITH THE FOLLOWING: (PLEASE
 SHOW ON ALL DETAILS OR INDICATE TYPICAL OF ALL TOILET
 ROOMS)
  
 __FOR W/C'S:
 A. OK
 B. OK
 C. OK
 D. 11-4.16.5 FLUSH CONTROLS ****NOT ADDRESSED
 ******RESPONSE NOTED BUT THE REQUIREMENT IS FOR THE
 FLUSH CONTROL TO BE ON THE WIDE SIDE OF THE W/C.
 DETAILS 1 & 9 SHOW THE FLUSH HANDLE ON THE WALL SIDE OF
 THE W/C. DETAIL 9 ALSO SHOWS THE W/C 17" OFF THE WALL
 TO THE CENTERLINE OF THE FIXTURE. 18" IS REQUIRED. (SEE
 FIGURE 11-28).
 E. OK
  
 __FOR URINALS:
 A. 11-4.18.2 OK
 B. 11-4.18.3 OK
 C. 11-4.18.4 OK
  
 __FOR LAVS:
 A. 11-4.19.2 OK
 B. 11-4.19.3 OK
 C. 11-4.19.4 OK
 D. 11-4.19.5 FAUCETS ****NOT ADDRESSED ******RESPONSE
 NOTED, BUT THE REQUIREMENT FOR THE LAV FAUCETS IS FOR
 THE OPERATING CONTROLS, NOT THE HEIGHT. LEVER TYPE,
 PUSH TYPE, ELECTRONICALLY CONTROLLED ETC. INDICATE
 FAUCET TYPE.
 E. 11-4.19.6 OK
  
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. SHTS P1.01 & P2.01 SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR REVIEW PRIOR TO
 ISSUING THE GAS PERMIT:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE ARCHITECT INDICATED THAT
 FORMICA WILL RESPOND TO COMMENT. PLEASE COMMUNICATE
 WITH ARCHITECT.
 ******RESPONSE NOTED, BUT ITEM 59 (TILT SKILLET), AND
 THE WATER HEATER MANUF SHEETS HAVE NOT BEEN SUBMITTED.
  
 F. N/A
 G. N/A
 H. OK
 10. OK
  
 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE
 TO THE SPACE. PLEASE INDICATE THE LOCATION. RPZV
 BACKFLOW SHALL BE INSTALLED A MAXIMUM 4' ABOVE THE
 FLOOR FOR SERVICING & TESTING.
 ****RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED
 AND SHALL BE LOCATED MAXIMUM 4' ABOVE THE FLOOR, NOT AN
 INLINE BACKFLOW LOCATED IN THE CEILING AS INDICATED.
 ******RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED
 AND SHALL BE LOCATED MAXIMUM 4' ABOVE THE FLOOR, NOT AN
 INLINE BACKFLOW LOCATED IN THE CEILING AS INDICATED.
 THE RPZV BACKFLOW IS STILL NOT INDICATED FOR THE
 SPACE.
  
 12. OK
 13. OK
 14. OK
  
 15. TWO SETS OF PLANS SHALL BE SUBMITTED. LOOSE SHEETS
 K-4 & K-5 SHALL BE INSERTED AS PART OF THE PLANS. THE
 TWO PAGE "WORKSHEETS"FROM THE DEPT OF BUSINESS
 REGULATION HOTEL & RESTURANT DIVISION SHALL BE ATTACHED
 TO EACH SET OF PLANS ON THE SHEET STAMPED FOR REVIEW BY
 DBPR.
 ****RESPONSE NOTED, BUT REMOVING THE SHEETS THAT HAVE
 THE FLORIDA STATE DBPR PLAN REVIEW STAMP IS NOT
 APPROVED. THE REVIEWED PLANS ARE REQUIRED IN BOTH SETS
 OF PLAN. ALSO THE TWO PAGE "WORKSHEETS" HAVE NOT BEEN
 ATTACHED TO THE DBPR REVIEWED SHEETS AS REQUIRED FOR
 EACH SET OF PLANS.
 ******RESPONSE NOTED, BUT THE SHEETS WITH THE DBPR
 SHEETS HAVE BEEN REMOVED. THE SHEETS WITH THE DBPR
 REVIEW STAMPS ARE REQUIRED IN EACH SET OF PLANS. ALSO
 AS INDICATED PREVIOUSLY, THE 2 PAGE "SPECIFICATION
 WORKSHEETS" HAVE NOT BEEN ATTACHED TO THE SHEETS WITH
 THE DBPR REVIEW STAMP. PLEASE SUBMIT SHEETS WITH THE
 DBPR REVIEW STAMP AND ATTACH THE TWO PAGE
 "SPECIFICATION WORKSHEETS" TO THE REVIEW SHEETS.
  
 16. OK
  
 ***********NEW COMMENTS**********
  
 1B. SHT P1.01 THE FLOOR SINK IN THE COOLER SHALL NOT
 CONNECT TO THE SANITARY DIRECTLY. SECTION 802.1.2.
 INDIRECT CONNECTION REQUIRED.
 ******RESPONSE NOTED, BUT A SAFE WASTE IS NOT AN
 INDIRECT WASTE. AN AIR GAP IS REQUIRED PER SECTION
 802.1.2. NO AIR GAP IS INDICATED.
  
 2B. OK
 3B. OK
 4B. OK
  
 **********NEW COMMENTS**********
  
 1C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).THE MANUF SHEETS SUBMITTED DO NOT REFLECT
 THE BTU LOADS INDICATED ON THE RISER DIAGRAM FOR ALL
 BUT ITEM 31. PLEASE MAKE SURE THAT THE GAS RISER
 DIAGRAM REFLECTS THE MANUF SHEETS FOR THE BTU LOADS.
 ALSO MAKE SURE THE TOTAL BTU LOAD IS CORRECT.
  
 2C. SHOW THE REGULATORS ON THE GAS RISER DIAGRAM. THE
 SHUT OFF VALVE SHALL BE UPSTREAM OF THE REGULATORS AND
 A UNION IS REQUIRED IF THE REGULATOR IS NOT AT THE END
 OF A RUN. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR
 THE REGULATOR BEING USED. SECTIONS 106.1.2. &409.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY.A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-08-27 Cont ID  
Sent By kstevens Date 2007-08-27 Time 16:05 Rev Time 0.00
Received By kstevens Date 2007-08-27 Time 14:21 Sent To  
Notes
2007-08-27 18:55:24DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW DATED 06-07-07. COMMENT
 NUMBERS TO REMAIN THE SAME.
  
 1. THE COVER AND ALL ARCHITECTURAL SHEETS REQUIRE THE
 FIRM LICENSE NUMBER. (CERTIFICATE OF AUTHORIZATION), IN
 THE TITLE BLOCK. FAC 61G1-16.004(2) & FS 481.219,
 481.2055.
 ****RESPONSE NOTED, BUT THE FIRM LICENSE NUMBER DOES
 NOT REFLECT THE LICENSE NUMBER ON THE FLORIDA STATE
 DBPR WEBSITE. PLEASE UPDATE THE DBPR WEBSITE OR THE
 TITLE BLOCK ADDRESS PRIOR TO RESUBMITTING FOR PLAN
 REVIEW. (SEE ATTACHED SHEET). ALSO THE FIRM LICENSE
 NUMBER AND CORRECT ADDRESS SHALL BE INDICATED ON ALL
 SHEETS WITH ARCHITECTURAL TITLE BLOCK.
  
 2. SHT A-5 FINISH SCHEDULE CALLS FOR RESTROOM FLOOR TO
 HAVE WOOD PLATFORMS. PLEASE INDICATE HOW THIS COMPLIES
 WITH THE REQUIREMENT FOR A "SMOOTH, HARD, NONABSORBENT
 SURFACE" AS INDICATED IN SECTION 1210.1. ALSO NO
 INFORMATION IS GIVEN SHOWING COMPLIANCE WITH SECTION
 1210.2 REQUIREMENTS FOR "SMOOTH, HARD, NONABSORBENT
 SURFACE" FOR THE WALLS WITHIN 2 FEET OF URINALS & WATER
 CLOSETS. PLEASE CLARIFY.
 ****RESPONSE NOTED, BUT MANUF. SPECIFICATION SHEETS
 REQUIRED FOR SEALANT OF CONCRETE TO VERIFY
 NONABSORBENCY. ALSO THE FINISH SCHEDULE CALLS FOR
 CERAMIC TILE FOR THE FLOOR. PLEASE CLARIFY. SECTION
 106.1.1.
  
 3. OK
  
 4. SHT A-9 SHOW COMPLIANCE WITH THE FOLLOWING: (PLEASE
 SHOW ON ALL DETAILS OR INDICATE TYPICAL OF ALL TOILET
 ROOMS)
  
 __FOR W/C'S:
 A. OK
 B. OK
 C. OK
 D. 11-4.16.5 FLUSH CONTROLS ****NOT ADDRESSED
 E. OK
  
 __FOR URINALS:
 A. 11-4.18.2 OK
 B. 11-4.18.3 OK
 C. 11-4.18.4 OK
  
 __FOR LAVS:
 A. 11-4.19.2 OK
 B. 11-4.19.3 OK
 C. 11-4.19.4 OK
 D. 11-4.19.5 FAUCETS ****NOT ADDRESSED
 E. 11-4.19.6 OK
  
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. SHTS P1.01 & P2.01 SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR REVIEW PRIOR TO
 ISSUING THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT NOT ALL CUT SECTIONS INDICATE
 THE LENGTH. SEE THE SECTIONS DOWNSTREAM OF THE DROP,
 (7'0")THRU THE RISE SECTION AFTER THE SOLENOID VALVE
 AND THE 3 SECTIONS AFTER THE 13'6" LENGTH OF PIPE
 DOWNSTREAM OF THE SOLENOID VALVE. PLEASE CHECK THAT
 ---ALL--- CUT SECTIONS INDICATE THE LENGTH. SCALING THE
 RISER ON SHEET P1.03 DOES NOT CORRELATE WITH
 MEASURMENTS ON THE RISER ISOMETRIC. PLEASE CHECK ALL
 MEASUREMENTS FOR THE LENGHTS OF PIPE.
  
 B. TYPE OF GAS, (LP OR NATURAL).
 ****RESPONSE NOTED, BUT NOT INDICATED ON THE PLANS.
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (TO BE DETERMINED WHEN
 COMMENT (A) IS ADDRESSED.
 ****RESPONSE NOTED, BUT WILL BE VERIFIED AFTER ALL CUT
 SECTION LENGTHS ARE INDICATED IN COMMENT A.
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ****RESPONSE NOTED, BUT FLORIDA PUBLIC UTILITIES ONLY
 DELIVERS 2PSI OR .5PSI. PLEASE INDICATE THE DELIVERY
 PRESSURE.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE ARCHITECT INDICATED THAT
 FORMICA WILL RESPOND TO COMMENT. PLEASE COMMUNICATE
 WITH ARCHITECT.
  
 F. N/A
 G. N/A
  
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
 ****RESPONSE NOTED, BUT THE MANUAL SHUT OFF VALVE AND
 UNION ARE NOT INDICATED ON THE RISER DIAGRAM AS
 REQUIRED.
  
 10. SHT P2.02 WATER HEATER DETAIL AND WATER RISER
 DIAGRAM. THE FLOOR DRAIN IS NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. SECTIONS 802.3 & 802.3.2. EITHER A
 FLOOR SINK OR A HUB DRAIN IS REQUIRED FOR INDIRECT
 WASTE.
 ****RESPONSE NOTED, BUT RISER INDICATES A MOP SINK, NOT
 HUB DRAIN AS INDICATED IN COMMENT RESPONSE.
  
 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE
 TO THE SPACE. PLEASE INDICATE THE LOCATION. RPZV
 BACKFLOW SHALL BE INSTALLED A MAXIMUM 4' ABOVE THE
 FLOOR FOR SERVICING & TESTING.
 ****RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED
 AND SHALL BE LOCATED MAXIMUM 4' ABOVE THE FLOOR, NOT AN
 INLINE BACKFLOW LOCATED IN THE CEILING AS INDICATED.
  
 12. OK
 13. OK
 14. OK
  
 15. TWO SETS OF PLANS SHALL BE SUBMITTED. LOOSE SHEETS
 K-4 & K-5 SHALL BE INSERTED AS PART OF THE PLANS. THE
 TWO PAGE "WORKSHEETS"FROM THE DEPT OF BUSINESS
 REGULATION HOTEL & RESTURANT DIVISION SHALL BE ATTACHED
 TO EACH SET OF PLANS ON THE SHEET STAMPED FOR REVIEW BY
 DBPR.
 ****RESPONSE NOTED, BUT REMOVING THE SHEETS THAT HAVE
 THE FLORIDA STATE DBPR PLAN REVIEW STAMP IS NOT
 APPROVED. THE REVIEWED PLANS ARE REQUIRED IN BOTH SETS
 OF PLAN. ALSO THE TWO PAGE "WORKSHEETS" HAVE NOT BEEN
 ATTACHED TO THE DBPR REVIEWED SHEETS AS REQUIRED FOR
 EACH SET OF PLANS.
  
 16. THE COVER SHEET INDICATES SHEETS K-1 THRU K-5 ON
 THE SHEET INDEX. ONLY K-4 & K-5 HAVE BEEN SUBMITTED.
 PLEASE CORRELATE THE SHEET INDEX WITH THE SHEETS
 SUBMITTED.SECTION 106.1.
 ****RESPONSE NOTED, BUT SEE COMMENT 15 AND MAKE SURE
 THE SHEET INDEX REFLECT SHEETS SUBMITTED.
  
 ***********NEW COMMENTS**********
  
 1B. SHT P1.01 THE FLOOR SINK IN THE COOLER SHALL NOT
 CONNECT TO THE SANITARY DIRECTLY. SECTION 108.1.2.
 INDIRECT CONNECTION REQUIRED.
  
 2B. SHT P102 THE FLOOR SINK AT FIXTURES 49 & 50 SHALL
 CONNECT TO THE VENTED LINE SEPARATELY. AS SHOWN IT
 CONNECTS TO THE LINE TO THE FLOOR SINK FOR FIXTURES
 41.1 & 44. SECTION 912.2.4.
  
 3B. SHT P2.01 THE SANITARY ISOMETRIC RISER DIAGRAM, THE
 RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN IN THE
 TOILET ROOM NEXT TO THE OFFICE. THE RISER DIAGRAM SHOWS
 A FLOOR DRAIN NOT SHOWN ON THE FLOOR PLAN. PLEASE
 CORRELATE RISER & FLOOR PLAN. SECTION 106.1.1.
  
 4B. SHT P2.01 THE GREASE ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. THE VENT DOWNSTREAM OF THE
 FLOOR SINK FOR FIXTURE 55SHOWN ON THE FLOOR PLAN IS
 NOT INDICATED ON THE RISER DIAGRAM. PLEASE CORRELATE.
 --THE FLOOR SINK FOR FIXTURES 49 & 50 SHALL CONNECTED
 TO THE VENTED MAIN LINE SEPARATELY. SECTION 106.1.1 &
 SECTION 912.2.4. (SEE COMMENT 2B).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-07 Cont ID  
Sent By kstevens Date 2007-06-07 Time 09:57 Rev Time 0.00
Received By kstevens Date 2007-06-06 Time 17:30 Sent To  
Notes
2007-06-07 11:02:16DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THE COVER AND ALL ARCHITECTURAL SHEETS REQUIRE THE
 FIRM LICENSE NUMBER. (CERTIFICATE OF AUTHORIZATION), IN
 THE TITLE BLOCK. FAC 61G1-16.004(2) & FS 481.219,
 481.2055.
  
 2. SHT A-5 FINISH SCHEDULE CALLS FOR RESTROOM FLOOR TO
 HAVE WOOD PLATFORMS. PLEASE INDICATE HOW THIS COMPLIES
 WITH THE REQUIREMENT FOR A "SMOOTH, HARD, NONABSORBENT
 SURFACE" AS INDICATED IN SECTION 1210.1. ALSO NO
 INFORMATION IS GIVEN SHOWING COMPLIANCE WITH SECTION
 1210.2 REQUIREMENTS FOR "SMOOTH, HARD, NONABSORBENT
 SURFACE" FOR THE WALLS WITHIN 2 FEET OF URINALS & WATER
 CLOSETS. PLEASE CLARIFY.
  
 3. SHT A-9 ACCESSIBLE STALL DETAIL. LAVS SHALL BE A
 MINIMUM 15" OFF THE WALL TO THE CENTERLINE OF THE
 FIXTURE TO BE CENTERED ON THE 30" OF THE 30"X48" CLEAR
 FLOOR SPACE. SECTION 11-4.19.3.
  
 4. SHT A-9 SHOW COMPLIANCE WITH THE FOLLOWING: (PLEASE
 SHOW ON ALL DETAILS OR INDICATE TYPICAL OF ALL TOILET
 ROOMS)
  
 __FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE (PER FIG 30E)
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS
 D. 11-4.16.5 FLUSH CONTROLS
 E. 11-4.16.6 DISPENSERS
  
 __FOR URINALS:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
  
 __FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
  
 5. ALL STRUCTURAL SHEETS. PROFESSIONAL ENGINEER FIRM'S
 CERTIFICATE OF AUTHORIZATION IS SHOWN AS DELINQUENT ON
 THE STATE DBPR WEBSITE AND THE ADDRESS IN THE TITLE
 BLOCK DOES NOT REFLECT THE ADDRESS INDICATED ON THE
 DBPR WEBSITE. PLEASE UPDATE THE STATUS OF THE C.A.
 NUMBER AND UPDATE EITHER THE DBPR WEBSITE OR THE TITLE
 BLOCK ADDRESS. FAC 61G15-23.002(2) & FS 471.025. (SEE
 ATTACHED SHEETS).
  
 6. ALL E, M, & P SHEETS. THE ADDRESS OF FORMICA &
 ASSOCIATES IN THE TITLE BLOCK DOES NOT REFLECT THE
 ADDRESS INDICATED ON THE STATE DBPR WEBSITE. EITHER
 UPDATE THE WEBSITE OR THE TITLE BLOCKS. FAC
 61G15-23.002(2) & FS 471.025. (SEE ATTACHED SHEET)
  
 7. SHTS P1.01 & P2.01 SAFE WASTE IS NOT APPROVED.
 SECTION 1002.1. (SEE FIXTURE 44.1). ALSO THE FLOOR SINK
 SHALL NOT BE LOCATED IN THE MIDDLE OF THE FLOOR AS IT
 CAN BE A TRIPPING HAZARD BECAUSE FLOOR SINKS ARE TO BE
 USED FOR INDIRECT WASTE ONLY. SECTION 802.3.
  
 8. SHTS P1.01 & P2.01 THE DISHWASHER SHALL CONNECT TO
 THE SANITARY SYSTEM, NOT THE GREASE WASTE SYSTEM PER
 ARTICLE III SECTION 90-124(7)(B).
  
 9. SHTS P1.01 & P2.01 SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR REVIEW PRIOR TO
 ISSUING THE GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. TYPE OF GAS, (LP OR NATURAL).
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (TO BE DETERMINED WHEN
 COMMENT (A) IS ADDRESSED.
  
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 F. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 G. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 10. SHT P2.02 WATER HEATER DETAIL AND WATER RISER
 DIAGRAM. THE FLOOR DRAIN IS NOT AN APPROVED INDIRECT
 WASTE RECEPTOR. SECTIONS 802.3 & 802.3.2. EITHER A
 FLOOR SINK OR A HUB DRAIN IS REQUIRED FOR INDIRECT
 WASTE.
  
 11. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE
 TO THE SPACE. PLEASE INDICATE THE LOCATION. RPZV
 BACKFLOW SHALL BE INSTALLED A MAXIMUM 4' ABOVE THE
 FLOOR FOR SERVICING & TESTING.
  
 12. SHT P2.02 WATER HEATER DETAIL THERMAL EXPANSION
 CONTROL IS REQUIRED PER SECTION 607.3.2. INDICATE
 METHOD.
  
 13. SHT P2.02 DETAIL NO. 2 SAFE WASTE IS NOT APPROVED.
 SECTION 1002.1.
  
 14. SHT P2.02 DETAIL NO. 3 THE AIR GAP SHALL BE PER
 SECTION 802.2.1.PLEASE INDICATE ON DETAIL.
  
 15. TWO SETS OF PLANS SHALL BE SUBMITTED. LOOSE SHEETS
 K-4 & K-5 SHALL BE INSERTED AS PART OF THE PLANS. THE
 TWO PAGE "WORKSHEETS"FROM THE DEPT OF BUSINESS
 REGULATION HOTEL & RESTURANT DIVISION SHALL BE ATTACHED
 TO EACH SET OF PLANS ON THE SHEET STAMPED FOR REVIEW BY
 DBPR.
  
 16. THE COVER SHEET INDICATES SHEETS K-1 THRU K-5 ON
 THE SHEET INDEX. ONLY K-4 & K-5 HAVE BEEN SUBMITTED.
 PLEASE CORRELATE THE SHEET INDEX WITH THE SHEETS
 SUBMITTED.SECTION 106.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-01 Cont ID  
Sent By eschneid Date 2007-10-01 Time 15:20 Rev Time 0.00
Received By eschneid Date 2007-10-01 Time 15:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-08-28 Cont ID  
Sent By eschneid Date 2007-08-28 Time 16:28 Rev Time 0.00
Received By eschneid Date 2007-08-28 Time 16:28 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-15 Cont ID  
Sent By eschneid Date 2007-05-15 Time 09:22 Rev Time 0.00
Received By eschneid Date 2007-05-15 Time 09:22 Sent To  
Notes
2007-05-15 09:29:04FAILED
  
 1) PLEASE EXPLAIN WHY THERE IS A SERVICE STATION (#3)
 IMMEDIATELY ADJACENT TO YOUR MAIN ENTRANCE.THIS DOES
 NOT SEEM TO BE THE FIRST IMPRESSION A CUSTOMER SHOULD
 HAVE - ESPECIALLY OUTSIDE - OF THE RESTAURANT, NOR DOES
 IT SEEM THAT IT IS OPERATIONALLY EFFICIENTLY IF YOU
 HAVE A BUSY NIGHT WITH PEOPLE WAITING FOR THE HOSTESS
 AND WAITSTAFF IN AN OUT OF THE STATION.PLEASE PROVIDE
 AN ELEVATION OF THE SOUTH SIDE OF THE BUILDING,
 INCLUDING SERVICE STATION #3 WITH BOTH OPEN AND CLOSED
 ROLL UP DOORS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved