| 2007-05-02 13:19:15 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE THE |
| | CORRESPONDING LENGTHS OF THE CUT SECTIONS OF PIPE OF |
| | THE PROPOSED GENERATOR GAS PIPING. PLEASE DO THIS ON |
| | THE RESUBMITTAL TO VERIFY THE INDICATED TOTAL DEVELOPED |
| | LENGTH OF THIRTY SIX FEET (36'). IS THE TOTAL DEVELOPED |
| | LENGTH OF THIRTY SIX FEET (36') FOR THE PROPOSED |
| | GENERATOR OR FOR THE EXISTING SYSTEM. PLEASE CLARIFY ON |
| | THE RESUBMITTAL. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | NOTE: NOT ALL PIPE SIZES ARE INDICATED ON THE |
| | ISOMETRIC. THE PIPING OUT OF THE METER SHOULD BE SIZED |
| | 1-1/4".PLEASE DO THIS ON THE RESUBMITTAL. |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: PLEASE CLEARLY INDICATE THE LONGEST LENGTH OF THE |
| | EXISTING SYSTEM AND THE PROPOSED SYSTEM TO VERIFY HOW |
| | SYSTEM IS TO BE SIZED. |
| | |
| | 4. PER FBC-2004 FUEL GAS, SECTION 404.13.3AN |
| | INSULATED COPPER TRACER WIRE SHALL BE INSTALLED |
| | ADJACENT TO UNDERGROUND NONMETALLIC GAS PIPING. THE |
| | TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 AWG AND THE |
| | INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL. |
| | NOTE: PLEASE INDICATE THIS ON THE RESUBMITTAL FOR THE |
| | UNDERGROUND PE. |
| | |
| | 5. PER FBC-2004 FUEL GAS SECTION 409.5 EQUIPMENT |
| | SHUTOFF VALVE: EACH APPLIANCE SHALL BE PROVIDED WITH A |
| | SHUTOFF VALVE SEPERATE FROM THE APPLIANCE. THE SHUTOFF |
| | VALVE SHALL BE LOCATED IN THE SAME ROOM AS THE |
| | APPLIANCE, NOT FURTHER THAN 6 FEET FROM THE APPLIANCE, |
| | AND SHALL BE INSTALLED UPSTREAM FROM THE UNION, |
| | CONNECTOR OR QUICK DISCONNECT DEVICE IT SERVES. SUCH |
| | SHUTOFF VALVES SHALL BE PROVIDED WITH ACCESS. NOTE: |
| | PLEASE INDICATE A SHUTOFF VALVE FOR THE PROPOSED |
| | GENERATOR ON THE RESUBMITTAL. |
| | |
| | 6. A GAS PERMIT CAN NOT BE ISSUED UNTIL |
| | A GEN/RES PERMIT APPLICATION HAS BEEN |
| | APPLIED FOR AND APPROVED BY ZONING FOR |
| | THE GENERATOR LOCATION. |
| | |
| | END OF COMMENTS: |
| | |