Plan Review Details - Permit 07040785
Plan Review Stops For Permit 07040785
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-12-28 Cont ID  
Sent By kconrad Date 2007-12-28 Time 18:45 Rev Time 0.00
Received By kconrad Date 2007-12-28 Time 17:13 Sent To I
Notes
2008-01-08 17:20:06REVISED SHEET A-6. SEE TYPE 1A WALL ASSEMBLY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-12-11 Cont ID  
Sent By kconrad Date 2007-12-11 Time 18:01 Rev Time 0.00
Received By kconrad Date 2007-12-11 Time 16:30 Sent To FIRE
Notes
2007-12-11 18:10:57PROJECT: 250 SOUTH AUSTRALIAN, SUITE 200
  
 CONTRACTOR: ITASCA
  
 BUILDING CODE: FEBC AND FBC 2004 WITH 2006 REVISIONS
  
 REVISION: CHANGE WALL TYPE AT CORRIDOR TO 1A/SHEETS A-4
 THRU A-6.
  
 STATUS: DENIED
  
 COMMENTS:
  
 1) PLEASE SUBMIT A TESTED AND APPROVED RATED PARTITION
 ASSEMBLY DETAIL FOR THE PROPOSED CHANGE OF THE CORRIDOR
 WALL AND THE SPECIFICATIONS FOR THE BIOSTOP BF150
 FIRESTOPPING SEALANT.
 ( 2 COPIES)
  
  
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: KCONRAD @WPB.ORG
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-08-23 Cont ID  
Sent By kconrad Date 2007-08-23 Time 18:32 Rev Time 0.00
Received By kconrad Date 2007-08-23 Time 15:59 Sent To I
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-14 Cont ID  
Sent By kconrad Date 2007-06-14 Time 19:49 Rev Time 0.00
Received By kconrad Date 2007-06-14 Time 16:56 Sent To I
Notes
2007-06-14 19:49:11 
  
  
 PROJECT: 250 SOUTH AUSTRALIAN, SUITE 200
  
 CONTRACTOR: ITASCA
 BUILDING CODE: FEBC AND FBC 2004 WITH 2006 REVISIONS
  
 1ST REVIEW
 STATUS: DENIED
  
 COMMENTS:
  
 1) FBC 105.9 ASBESTOS.
 THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT
 FOR THE DEMOLITION OR RENOVATION OF AN EXISTING
 STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT
 WHICH INDICATES THE OWNER?S OR OPERATOR?S
 RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION
 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT
 OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO
 REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH
 STATE AND FEDERAL LAW. PLEASE CONTACT ALEX ORTEGA OF
 THE DEP FOR DEMOLITION CLEARANCE AT 561.355.3023,
 EXT.48.
  
 2) FEBC 1302.1REMODELING AND ADDITIONS.
 REQUIRED EXITS, EXISTING STRUCTURAL ELEMENTS, FIRE
 PROTECTION DEVICES AND SANITARY SAFEGUARDS SHALL BE
 MAINTAINED AT ALL TIMES DURING REMODELING, ALTERATIONS,
 REPAIRS OR ADDITIONS TO ANY BUILDING OR STRUCTURE.
 EXCEPTIONS:
 1. WHEN SUCH REQUIRED ELEMENTS OR DEVICES ARE BEING
 REMODELED, ALTERED OR REPAIRED, ADEQUATE SUBSTITUTE
 PROVISIONS SHALL BE MADE.
 2. WHEN THE EXISTING BUILDING IS NOT OCCUPIED.
  
 3)FEBC1309.1WHERE REQUIRED.
 ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR
 DEMOLITION SHALL BE PROVIDED WITH NOT LESS THAN ONE
 APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH
 SECTION 906 OF THE FLORIDA BUILDING CODE, BUILDING AND
 SIZED FOR NOT LESS THAN ORDINARY HAZARD AS FOLLOWS:
 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATE
 2. IN EVERY STORAGE AND CONSTRUCTION SHED.
 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
  
 4)FEBC 1310.2MAINTENANCE OF EXITS.
 REQUIRED MEANS OF EGRESS SHALL BE MAINTAINED AT ALL
 TIMES DURING CONSTRUCTION, DEMOLITION, REMODELING OR
 ALTERATIONS AND ADDITIONS TO ANY BUILDING. EXCEPTION:
 APPROVED TEMPORARY MEANS OF EGRESS SYSTEMS AND
 FACILITIES.
  
 5) PLEASE INDICATE BUILDING CONSTRUCTION TYPE ( TYPE 1A
 OR TYPE 1B), OCCUPANCY LOADS AS PER FBC 1004.1 AND
 LEVEL OF ALTERATION AS PER FEBC 305.1 WITHIN THE
 PROJECT INFORMATION LOCATED ON SHEET A-1. ALSO REVISE
 THE BUILDING CODES TO INDICATE FBC AND FEBC WITH 2006
 REVISIONS WITHIN THE SAME.
  
 6) FIRE RESISTANT CONSTRUCTION REQUIREMENTS:
  
 PLEASE PROVIDE DETAILS OF THROUGH PENETRATION
 FIRESTOP SYSTEMS APPLICABLE TO THIS PROJECT AS PER THE
 FOLLOWING:
  
 712.4 HORIZONTAL ASSEMBLIES.
 PENETRATIONS OF A FLOOR, FLOOR/CEILING ASSEMBLY OR THE
 CEILING MEMBRANE OF A ROOF/CEILING ASSEMBLY SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 707. PENETRATIONS
 PERMITTED BY EXCEPTIONS 3 AND 4 OF SECTION 707.2 SHALL
 COMPLY WITH SECTIONS 712.4.1 THROUGH 712.4.4.
 EXCEPTION: PENETRATIONS LOCATED WITHIN THE SAME ROOM OR
 UNDIVIDED AREA AS FLOOR OPENINGS ARE NOT REQUIRED TO
 HAVE A SHAFT ENCLOSURE IN ACCORDANCE WITH EXCEPTION 1,
 2, 5, 7, 8 OR 9 IN SECTION 707.2.
  
 712.4.1 THROUGH PENETRATIONS.
 THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED
 HORIZONTAL ASSEMBLIES SHALL COMPLY WITH SECTION
 712.4.1.1 OR 712.4.1.2.
 EXCEPTIONS:
 1. PENETRATIONS BY STEEL, FERROUS OR COPPER CONDUITS,
 PIPES, TUBES, VENTS, CONCRETE, OR MASONRY THROUGH A
 SINGLE FIRE-RESISTANCE-RATED FLOOR ASSEMBLY WHERE THE
 ANNULAR SPACE IS PROTECTED WITH MATERIALS THAT PREVENT
 THE PASSAGE OF FLAME AND HOT GASES SUFFICIENT TO IGNITE
 COTTON WASTE WHEN SUBJECTED TO ASTM E 119
 TIME-TEMPERATURE FIRE CONDITIONS UNDER A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA)
 OF WATER AT THE LOCATION OF THE PENETRATION FOR THE
 TIME PERIOD EQUIVALENT TO THE FIRE-RESISTANCE RATING OF
 THE CONSTRUCTION PENETRATED. PENETRATING ITEMS WITH A
 MAXIMUM 6-INCH (152 MM) NOMINAL DIAMETER SHALL NOT BE
 LIMITED TO THE PENETRATION OF A SINGLE
 FIRE-RESISTANCE-RATED FLOOR ASSEMBLY PROVIDED THAT THE
 AREA OF THE PENETRATION DOES NOT EXCEED 144 SQUARE
 INCHES (92 900 MM2) IN ANY 100 SQUARE FEET (9.3 M2) OF
 FLOOR AREA.
 2. PENETRATIONS IN A SINGLE CONCRETE FLOOR BY STEEL,
 FERROUS OR COPPER CONDUITS, PIPES, TUBES AND VENTS WITH
 A MAXIMUM 6-INCH (152 MM) NOMINAL DIAMETER PROVIDED
 CONCRETE, GROUT OR MORTAR IS INSTALLED THE FULL
 THICKNESS OF THE FLOOR OR THE THICKNESS REQUIRED TO
 MAINTAIN THE FIRE-RESISTANCE RATING. THE PENETRATING
 ITEMS WITH A MAXIMUM 6-INCH (152 MM) NOMINAL DIAMETER
 SHALL NOT BE LIMITED TO THE PENETRATION OF A SINGLE
 CONCRETE FLOOR PROVIDED THAT THE AREA OF THE
 PENETRATION DOES NOT EXCEED 144 SQUARE INCHES (0.0929
 M2).
 3. ELECTRICAL OUTLET BOXES OF ANY MATERIAL ARE
 PERMITTED PROVIDED THAT SUCH BOXES ARE TESTED FOR USE
 IN FIRE-RESISTANCE-RATED ASSEMBLIES AND INSTALLED IN
 ACCORDANCE WITH THE TESTED ASSEMBLY.
  
 712.4.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. THROUGH
 PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLED AND
 TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A
 MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH
 (2.49 PA) OF WATER. THE SYSTEM SHALL HAVE AN F RATING
 AND A T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS
 THAN THE REQUIRED RATING OF THE FLOOR PENETRATED.
 EXCEPTION: FLOOR PENETRATIONS CONTAINED AND LOCATED
 WITHIN THE CAVITY OF A WALL DO NOT REQUIRE A T RATING.
  
 715.3.5 LABELED PROTECTIVE ASSEMBLIES.
 FIRE DOOR ASSEMBLIES SHALL BE LABELED BY AN APPROVED
 AGENCY. THE LABELS SHALL COMPLY WITH NFPA 80, AND SHALL
 BE PERMANENTLY AFFIXED TO THE DOOR OR FRAME.
  
 717.5 COMBUSTIBLES IN CONCEALED SPACES IN TYPE I OR II
 CONSTRUCTION.
 COMBUSTIBLES SHALL NOT BE PERMITTED IN CONCEALED SPACES
 OF BUILDINGS OF TYPE I OR II CONSTRUCTION. EXCEPTIONS:
 1. COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION
 603.
 2. COMBUSTIBLE MATERIALS COMPLYING WITH SECTION 602 OF
 THE FLORIDA BUILDING CODE, MECHANICAL.
 3. CLASS A INTERIOR FINISH MATERIALS. 4. COMBUSTIBLE
 PIPING WITHIN PARTITIONS OR ENCLOSED SHAFTS INSTALLED
 IN ACCORDANCE WITH THE PROVISIONS OF THIS CODE.
 COMBUSTIBLE PIPING SHALL BE PERMITTED WITHIN CONCEALED
 CEILING SPACES WHERE INSTALLED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, MECHANICAL AND THE FLORIDA
 BUILDING CODE, PLUMBING.
  
 7) SYMBOL LEGEND, NEW PARTITION TYPES REFERS TO SHEET
 A-10; SHOULD REFER TO SHEET A-6. ALSO REFERENCES TO TO
 DOOR SCHEDULE IS SHEET A-10A: SHOULD BE SHEET A-6.
 PLEASE REVISE.
  
 8) PLAN INDICATES TWO WALL TYPES AT GRIDLINE 6 AT THE
 COPY STORAGE ROOM. PLEASE PROVIDE CLARIFICATION.
  
 9) PROVIDE MECHANICAL ATTACHMENT DETAILS FOR METAL WALL
 FRAMING AT THE TOP AND BOTTOM RUNNERS AND THE DIAGONAL
 METAL SUPPORTS TO CEILING SLAB INTERFACE AS SHOWN ON
 SHETT A-6, WALL TYPES 1-3. PLEASE CLARIFY THE USE OF #8
 TEK SCREWS INTO CONCRETE AS REFLECT ED ON THE WALL TYPE
 DETAILS 1 AND 2 ON SHEET A-6.
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 FAX: 561.805.6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-08-23 Cont ID  
Sent By dpalmer Date 2007-08-23 Time 09:55 Rev Time 0.00
Received By dpalmer Date 2007-08-22 Time 21:13 Sent To  
Notes
2007-08-23 10:12:01**** THE FP SHEETS ARE STILL MISSING REQUIRED LICENSE
 INFORMATION ON TITLE BLOCKS PER FAC 61G15-23.002 AND FS
 471.023.
 LOOK FOR COMMENTS FROM FIRE MARSHAL AND/OR BUILDING
 REVIEW. THIS INFORMATION IS FROWARDED TO THOSE TRADES.
2007-08-22 21:13:532007-08-22 21:13:53
 IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-07 Cont ID  
Sent By dpalmer Date 2007-05-07 Time 17:04 Rev Time 0.00
Received By dpalmer Date 2007-05-07 Time 17:04 Sent To  
Notes
2007-05-07 17:04:21** UNSAT 2ND REVIEW**
  
 ***** IMPORTANT *****
 ** PLEASE SEE THERE ARE SEVERAL ITEMS FROM THE PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
 ** PLEASE ALSO SEE THAT THERE ARE SEVERAL NEW COMMENTS
 BASED ON THE RESPONSES AND THE REVISED PLANS. MANY
 ITEMS WERE SUBSTANTIALLY REVISED INCLUDING THE SCOPE OF
 WORK PER FLOOR UNDER SEPARATE PERMITS.
  
 ** THIS IS A REVIEW FOR SECOND FLOOR UNDER A NEW PERMIT
 NUMBER HOWEVER THE REVIEW WAS PREVIOUSLY CONDUCTED
 UNDER #07011148 WHEN BOTH FLOORS WERE SUBMITTED UNDER
 ONE PERMIT.
 PLEASE SEE MANY OF THE COMMENTS ON THE ABOVE REFERENCED
 NUMBER MAY AFFECT THESE PLANS AND INFORMATION.
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 MANY COMMENTS ARE FROM THE FIRST REVIEW.
  
 1) NOTE:THIS IS THE SAME COMMENT AS PREVIOUS REVIEW.
 PLEASE SEE THE ARCHITECTURAL PLANS STILL INDICATE THE
 PREVIOUS CODES. PLEASE LIST THE FOLLOWING AS REQUESTED
 ON PREVIOUS REVIEW. PLEASE SEE ONLY THE CORRECTED CODES
 WERE ADDED TO THE ELECTRICAL SHEETS AND NOT TO A
 SHEETS.
 PLEASE SEE THE CODES SHALL BE STATED ON THE PLANS. ALL
 APPLICATIONS AFTER DECEMBER 8TH, 2006 ARE UNDER THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE ALSO SEE THAT THE FOLLOWING SHALL ALSO BE
 STATED. 2003 NFPA-101 AND THE 2002 NFPA-72. **PLANS
 STATE LATEST EDITION.
 FBC 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE INDICATE THE SUITE/UNIT NUMBER(S) ON
 PLANS.
 SAME NOTE AS PREVIOUS REVIEW. ONLY THE ELECTRICAL
 SHEETS WERE CORRECTED TO INDICATE THE SUITE/UNIT
 NUMBER. PLEASE SEE THIS COMMENT IS FOR ALL TRADES AND
 FOR ALL SHEETS WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
 ** PLEASE KNOW THAT ANY SHEETS WHICH ARE NOT REQUIRED
 TO BE CORRECTED FOR ANY TRADE/CODE RELATED COMMENT MAY
 HAVE THE SUITE/UNIT NUMBER WRITTEN/PRINTED OR STAMPED
 ON TITLE BLOCKS.
 FBC 106.1.2,
 FAC 61G1-16.004
  
 3) NOTE: PLEASE SEE THE MISSING PRINTED LICENSE NUMBER
 FOR THE ARCHITECT ON THE TITLE BLOCKS. 61G1-16.004.
 THIS COMMENT WAS MADE ON THE PREVIOUS REVIEW AND THE
 RESPONSE MENTIONS THAT PERHAPS THIS WAS MISSED AS IT IS
 LISTED ON THE UPPER RIGHT HAND CORNER OF THE
 PLANS/TITLE BLOCKS.
 PLEASE SEE THE TITLE BLOCKS INDICATE THE PRINTED *FIRM*
 CERTIFICATE OF AUTHORIZATION NUMBER WHICH IS OK AND
 REQUIRED BUT DOES NOT INDICATE THE PRINTED LICENSE
 NUMBER OF THE ARCHITECT AS REQUIRED PER SECTION STATED
 PREVIOUSLY. NONE OF THE SHEETS CONTAIN THIS "PRINTED
 LICENSE NUMBER" OF THE ARCHITECT.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
 PLEASE REVISE AND ADDRESS ACCORDINGLY. ** ONE SHEETS
 WHICH DO NOT NEED TO BE REVISED BY OTHER TRADES FOR
 CODE COMPLIANCE, THIS MAY BE PRINTED/STAMPED ON
 SHEETS.
  
 4) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS AND
 PERFORMANCE DENSITIES PER 13-415.1.AB.1, 13-415.2. NO
 CALCULATIONS COULD BE LOCATED.
 ONLY THE LIGHTING PERFORMANCE FOR LIGHTING WAS LOCATED
 ON PLANS. PLEASE VERIFY THE NUMBER OF FIXTURES, THE
 WATTAGES, AND SQ FT FOR LPD.
 THE TOTAL WATTAGE WHICH WAS DERIVED USING THE NUMBER OF
 FIXTURES ON PLANS AND THE WATTAGE FOR EACH AS LISTED ON
 FIXTURE LEGEND SEEMS TO BE SLIGHTLY DIFFERENT THAN THAT
 SHOWN ON LIGHTING PLANS.
  
 5) NOTE:PLEASE SEE THIS NOTE AS LISTED IS THE SAME AS
 PREVIOUS REVIEW. IN FACT ONE OF THE SAME ELECTRICAL
 SHEETS SUBMITTED ON PREVIOUS PLANS WAS NOW SUBMITTED AS
 E3.3 WHICH IS MISSING MUCH OF THE INFORMATION WHICH WAS
 SHOWN ON PREVIOUS PLANS ON SHEET E3?
 PLEASE SEE NO SCHEDULING, OVER RIDE TIMES, SYSTEM,
 CONTROL PANEL LOCATION, CIRCUITS, ZONES, ETC IS SHOWN.
 ** PLEASE SEE THAT THE LIGHTING PANEL WHICH IS ON THE
 3RD FLOOR MAY NOT BE USED FOR SECOND FLOOR.
 PLEASE SEE RESPONSE MENTIONS 1HR OVER RIDES, HOWEVER ON
 AN OCCUPANCY SENSOR TYPE DEVICES, THE MAXIMUM OVER RIDE
 TIME IS 30MINS.
 PLEASE REVISE PLANS, PROVIDE COMPLETE DETAILS FOR
 CHAPTER 13 CODE COMPLIANCE.
 ** PLEASE SEE THERE ARE NOTES ON LIGHTING SHEETS WHICH
 REFLECT TO A NOTE #4, THIS NOTE #4 MENTIONS TO SEE
 DETAILS ON SHEET E-4,HOWEVER NO SHEET E4 IS IN SETS
 PR SUBMITTED?
 DEVICES ON LEGEND NEED TO COORDINATE WITH DETAIL FOR
 ALL DEVICES, TIMES, TYPES ETC. THE LEGEND DOES NOT
 INDICATE ANY SENTRY DEVICE AS NOTED ON PLANS.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETE SCHEDULING FOR THE TIMES IN USE
 FOR THE LIGHTING CONTROL SYSTEM. PLEASE SEE THE SECTION
 OF THE CODE OF CHAPTER 13 QUOTED AS 413 SHOULD BE 415.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 AS THERE IS
 MISSING CONTROLS FOR SEPARATE SPACES.
 PLEASE BE SURE TO INDICATE ALL OF THESE DEVICES AND
 CORRELATE WITH THE SYMBOL LEGEND. PLEASE INDICATE THE
 MAXIMUM AMOUNT OF TIME FOR OVER RIDE(S).
 (PLEASE SEE SOME DEVICES ON PLANS AND THE DESIGNATIONS
 ON PLAN SYMBOL LEGEND DO NOT SEEM TO INDICATE DEVICES
 FOR COMPLIANCE WITH CHAPTER 13.
  
  
 6) NOTE:THIS SAME NOTE WILL REMAIN AS THE SCOPE OF
 WORK APPLIED FOR UNDER 3RD AND 2ND FLOOR IS NOT CLEAR
 ON HOW THE PANELS ETC FOR THE IT ROOM WILL BE DONE. THE
 NOTE IS THE SAME OF THAT WHICH IS ON 07011148IT ROOM
 REQUIREMENTS SEEMS TO HAVE BEEN ADDRESSED, HOWEVER
 QUESTION HAS NOW RISEN OVER SCOPE OF WORK AND WHICH
 PERMIT THIS WORK WILL BE UNDER. PLEASE SEE THE
 ELECTRICAL RISER NOW SHOWS, NOTES AND INDICATES THIS
 SCOPE OF WORK IS NOT INCLUDED FOR THIRD FLOOR AND IS
 UNDER 2ND FLOOR SCOPE?? PLEASE SEE THE PERMIT
 APPLICATION AND PLANS FOR THE SECOND FLOOR ALSO STATE
 THE SAME THING?
 PLEASE BE SURE TO COORDINATE ALL SCOPES OF WORK, UNDER
 WHICH PERMIT AND REVISE PLANS AS NEEDED. HOW WILL THE
 3RD FLOOR WHICH IS UNDER A SEPARATE PERMIT FROM THE 2ND
 FLOOR OBTAIN A FINAL/CERTIFICATE OF COMPLETE ION OR
 OCCUPANCY WHEN THE SCOPE FOR THAT FLOOR HAS NOT BEEN
 DONE YET?
 PLEASE SUBMIT THE SPECS/PLANS AND DOCUMENTS UNDER THE
 PERMIT BEING APPLIED FOR.
 FBC 106.1.2, 106.3.5.1.2ADMIN SECTION.
  
 7) NOTE: ** THIS COMMENT IS NOT FOR MEP FIRM: PLEASE
 SEE FIRE REVIEW COMMENTS AS THE FP SHEETS IN NEW SETS
 ARE OF NEW DESIGNER AND NOTE THAT SUBMITTED FROM
 PREVIOUS REVIEWED PLANS.
 PLEASE SEE THE FOLLOWING ITEMS ARE REQUIRED WHETHER OR
 NOT COMMENT IS MADE BY THE FIRE REVIEWER.
 PLEASE SEE NEW REVISED SHEET FP-2 IS THE ONLY SHEET IN
 SETS.
 ** PLEASE SEE THE SEAL WHICH IS NOW BEING USED ON THE
 REVISED FP-2 SHEETS IS NO LONGER VALID WITH THE FLORIDA
 BOARD OF PROFESSIONAL ENGINEERS. PLEASE SEE RULING FAC
 61G15-23.001 WHICH CHANGED IN FEB *04* REQUIRING ALL
 SEALS FOR ENGINEERS TO CHANGE AND USE THE WORDING OF
 *LICENSE* IN SAID SEAL AND COULD NOT LONGER USE THE
 WORDING OF *CERTIFICATE*. AN EXTENSION WAS GRANTED BY
 THE BOARD TO THE DATE OF 12/31/05 HOWEVER ALL SEALING
 OF DOCUMENTS AFTER THAT DATE MUST BE DONE USING NEW
 SEAL.
 PLEASE OBTAIN CORRECTED SEAL FROM THE STATE/BOARD.
 **PLEASE ALSO SEE MISSING TITLE BLOCK INFORMATION
 REQUIRED FOR THE ENGINEER OF RECORD FOR THE FP SHEETS.
 PLEASE KNOW IF THE ENGINEER OF RECORD IS EMPLOYED BY
 THE FIRE PROTECTION COMPANY ( PHILLIPS FIRE SPRINKLERS
 INC) WHICH IS OFFERING ENGINEERING SERVICES, THEN SAID
 COMPANY SHALL OBTAIN AN ENGINEERING BUSINESS LICENSE
 NUMBER AS REQUIRED UNDER FLORIDA STATUTES 471.023 AND
 SHALL INCLUDE THIS INFORMATION ON TITLE BLOCKS AS
 REQUIRED PER FAC 61G15-23.002
 PLEASE KNOW THAT IF THE ENGINEER IS PRACTICING AS AN
 INDIVIDUAL AND NOT EMPLOYED BY THE SAID COMPANY THEN
 THE SHEETS ARE REQUIRED TO CONTAIN INFORMATION FOR THE
 INDIVIDUAL TITLE BLOCK AS REQUIRED UNDER THE SAME
 SECTION OF THE FLORIDA ADMINISTRATIVE CODE.
 ** THIS HAS BEEN CONFIRMED WITH THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS AND THE BOARDS LEGAL COUNSEL. IF
 THERE ARE ANY QUESTIONS ON THIS PLEASE CONTACT THE
 BOARD AS NOTED.
  
 8) NOTE: PLEASE SEE THE ELECTRICAL RISER DIAGRAM HAS
 NOW BEEN COMPLETELY REVISED IN WHICH THERE ARE SEVERAL
 NEW COMMENTS AS WELL AS SOME ITEMS FROM PREVIOUS REVIEW
 WHICH ARE IN NEED OF ADDRESSING.
 SOME OF THE BELOW IS TAKEN FROM THE NOTES UNDER
 07011148. PLEASE COORDINATE BOTH PERMITS, PLANS AND
 SCOPE OF WORK.
 PLEASE SEE THE RISER NOW INDICATES 277/480V SERVICE
 BEING INSTALLED FROM A NEW 1MA AND THE RISER STILL
 INDICATES THE BUS-DUCT RISER AS 277/480V? PLEASE SEE
 THE RISER FOR DISCONNECT WHICH IS NOTED #14 WHICH
 INDICATES THIS DISCONNECT AS 120/208V?
 PLEASE SEE RISER, WHICH SHOWS THE DISCONNECT FOR THE
 ASSUMED 277/480 OR 120/208 ON THE FORTH FLOOR WHICH IS
 FOR THE THIRD FLOOR AND THE DISCONNECT WHICH IS ON THE
 THIRD FLOOR WHICH FEEDS THE SECOND FLOOR? AS THE
 VOLTAGES CONFLICT, IT APPEARS THERE ARE TWO COMPLETELY
 SEPARATE 277/480VOLT SERVICES BEING FED FROM TWO
 SEPARATE MAINS??
 PLEASE SEE THE 2ND FLOOR WHICH CONTAINS LIGHTING
 CONTROLS WHICH IS BEING FED FROM THE THIRD FLOOR
 ELECTRICAL SERVICE WHICH IS NOT PERMITTED.( IN THE
 EVENT POWER IS NEEDED TO BE SHUT DOWN FOR THIS FLOOR,
 THESE SWITCHES WOULD REMAIN ENERGIZED).
  
 PLEASE SEE DISCONNECT #22 INDICATES A NEUTRAL ON THE
 LINE SIDE OF THE TRANSFORMER? IF THIS IS SUPPOSED TO BE
 A SEPARATELY DERIVED SYSTEM, THEN A NEUTRAL CONDUCTOR
 WOULD NOT BE INSTALLED TO THE TRANSFORMER FROM THIS
 DISCONNECT NOTED AS #22. SEE NOTE #15 FOR CONDUCTORS.
 THE RISER IS NOT CLEAR FOR VOLTAGES, SERVICES, CROSSING
 OVER OF SYSTEMS, WHAT IS OR IS NOT SEPARATELY DERIVED
 ETC. THESE ITEMS CAN NOT BE ASSUMED.
 PLEASE CLARIFY PANELS 3LA AND 3LB AS BOTH ARE SHOWN AS
 100AMP MCB, HOWEVER THIS IS BEING NOTED AND SHOWN ON
 RISER THAT EACH PANEL CONTAINS THIS AS PART OF THE
 EQUIPMENT, YET PANEL 3LB ALSO INDICATES THE PANEL
 CONTAINING A BACK FED BREAKER? IF THIS IS THE CASE,
 PLEASE NOTE REJECTION CLIP REQUIRED. 408.36F PLEASE SEE
 NEC 2005.
 FBC 106.3.5.1.2, 106.1.2.
  
 9) NOTE: PLEASE SEE THE NEW 1MA WHICH IS NOW SHOWN AS A
 500AMP MCB/MAIN CIRCUIT BREAKER PANEL WHICH CONTAINS AS
 BUS RATED AT 225AMPS.
 PLEASE EXPLAIN HOW THIS IS POSSIBLE.
 PLEASE SEE THE LOAD CALCULATIONS FOR THIS SAME PANEL
 INDICATES THE LOAD AT 297AMPS, AND THE BUS/SERVICE
 BEING RATED FOR 225AMPS.
 (ALSO LABELED AS 3MA)??
 THIS RISER IS STILL UNCLEAR FOR VOLTAGES AND
 INSTALLATION OF THE EQUIPMENT.
 PLEASE SEE THE 2005 NEC. PANELS AND EQUIPMENT MUST BE
 RATED FOR THE LOADS, ETC.
 FBC 106.3.5.1.2, 106.1.2
 ** PLEASE KNOW THAT AT THIS TIME THE RISER IS VERY
 CONFUSING AS THERE ARE MANY ITEMS THAT DO NOT CORRELATE
 OR ARE MISSING AT THIS TIME.
  
 10) NOTE:NOTE TO REMAIN AS RISER IS THE SAME OF THAT
 ON 07011148PLEASE INDICATE ANY GROUNDING ATTACHMENTS
 AND SIZES FOR SD SYSTEMS PER 250.20, 250.30, 250.66,
 AND 250.50
 THIS WAS NOTED ON PREVIOUS REVIEW. INDICATE THE
 ATTACHMENT LOCATIONS.
  
 11) NOTE: PLEASE SUBMIT AND SHOW LOAD CALCULATIONS ON
 ALL EXISTING WITH NEW LOADS BEING ADDED.
 THIS IS NOT ONLY FOR THE PANELS SHOWN, BUT FOR ALL
 EQUIPMENT WHICH LOADS, PANELS ETC ARE BEING ADDED.
 PLEASE SEE NOTE # 9 ABOVE WITH RESPECT TO 1MA. PLEASE
 SEE 220.10, 220.12, 220.14, 220.42, ETC, CONTINUOUS
 LOADS AT 125% PER 215.3, 230.42 ETC.
  
 12) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS
 ONLY NOTED AT THIS TIME.
 ** ONE SET OF EACH OF THE SETS OF PLANS SUBMITTED WILL
 BE RETAINED BY THIS OFFICE.
  
 ** PLEASE KNOW AT THIS TIME DUE TO SOME INFORMATION NOT
 YET AVAILABLE FOR REVIEW, THERE MAY BE NEW COMMENTS ON
 THE NEXT REVIEW WHICH HAVE NOT YET BEEN MADE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-01-09 Cont ID  
Sent By mwennerg Date 2008-01-09 Time 09:19 Rev Time 0.00
Received By mwennerg Date 2008-01-09 Time 09:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-01-07 Cont ID  
Sent By mwennerg Date 2008-01-07 Time 10:26 Rev Time 0.00
Received By mwennerg Date 2008-01-07 Time 10:26 Sent To  
Notes
2008-01-07 10:31:46***DENIED***
  
 1) PLEASE SEE BUILDING REVIEW COMMENT #1 AND IN
 ADDITION PROVIDE UL LISTING INFORMATION FOR WALL
 ASSEMBLY.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-08-30 Cont ID  
Sent By kconrad Date 2007-12-11 Time 18:13 Rev Time 0.00
Received By mawillia Date 2007-08-30 Time 15:04 Sent To  
Notes
2007-08-30 15:28:49*****APPROVED*****
  
  
 PLAN SHEET A-8, E2.2, AND FP-1 WERE STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-06-14 Cont ID  
Sent By mcarsill Date 2007-06-14 Time 14:22 Rev Time 0.00
Received By mcarsill Date 2007-06-14 Time 14:18 Sent To  
Notes
2007-06-14 14:21:561. IT APPEARS THAT ALL PREVIOUS MADE COMMENTS BY FIRE
 RESCUE HAVE BEEN ADDRESSED WITH REVISIONS TO THE
 PLANS.
  
 MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-12-27 Cont ID  
Sent By spalmer Date 2007-12-27 Time 11:09 Rev Time 0.00
Received By spalmer Date 2007-12-27 Time 11:09 Sent To B
Notes
2007-12-27 11:10:10TO KEN CONRADS DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-10 Cont ID  
Sent By adarroug Date 2007-12-10 Time 10:32 Rev Time 0.00
Received By adarroug Date 2007-12-10 Time 10:32 Sent To  
Notes
2007-12-10 10:34:41TO "COMM" BD#30

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-10 Cont ID  
Sent By adarroug Date 2007-12-10 Time 10:24 Rev Time 0.00
Received By adarroug Date 2007-12-10 Time 10:24 Sent To  
Notes
2007-12-10 10:24:51TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-02 Cont ID  
Sent By adarroug Date 2007-08-02 Time 13:53 Rev Time 0.00
Received By adarroug Date 2007-08-02 Time 13:53 Sent To  
Notes
2007-08-21 11:15:50TO "COMM" BD#8
2007-08-02 13:53:17WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-14 Cont ID  
Sent By rbrown Date 2007-06-14 Time 19:59 Rev Time 0.00
Received By rbrown Date 2007-04-24 Time 10:30 Sent To  
Notes
2007-05-03 08:24:34TO "COMM" BD#1
2007-04-24 10:30:21WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-12-11 Cont ID  
Sent By tgordon Date 2007-12-11 Time 08:14 Rev Time 0.25
Received By tgordon Date 2007-12-11 Time 08:14 Sent To  
Notes
2007-12-11 08:14:56REVISION TO MECH. PLAN PAGE M-1.2.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-08-17 Cont ID  
Sent By tgordon Date 2007-08-17 Time 14:45 Rev Time 0.25
Received By tgordon Date 2007-08-17 Time 14:44 Sent To  
Notes
2007-08-20 15:48:28RETURNED TO INCOMING WAITING TO GET ON COMM. BOARD.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-08 Cont ID  
Sent By tgordon Date 2007-05-08 Time 12:13 Rev Time 0.25
Received By tgordon Date 2007-05-08 Time 12:13 Sent To  
Notes
2007-05-08 12:14:17*** DENIED ***
 1) MECHANICAL PLANS DO NOT SHOW THE DUCT (FLEX) SIZES,
 OR A DETAIL SHOWING CFM'S TO DUCT (FLEX) SIZES, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status N Date 2007-08-30 Cont ID  
Sent By kstevens Date 2007-08-30 Time 14:20 Rev Time 0.00
Received By kstevens Date 2007-08-30 Time 14:20 Sent To  
Notes
2007-08-30 14:21:52 
  
 NO PLUMBING SHOWN THIS PHASE

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-10 Cont ID  
Sent By kstevens Date 2007-05-10 Time 12:30 Rev Time 0.00
Received By kstevens Date 2007-05-10 Time 12:30 Sent To  
Notes
2007-05-10 12:56:24DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW PERMIT #07011148:
  
 1. OK
  
 2. OK NO PLUMBING THIS PERMIT.
  
 3. ALL SHEETS. THE ADDRESS FOR THE ARCHITECTURAL
 BUSINESS SHOWN ON THE TITLE BLOCK DOES NOT REFLECT THE
 ADDRESS OF RECORD ON THE DBPR WEBSITE. PLEASE UPDATE
 THE DBPR WEBSITE OR SHOW THE CORRECT ADDRESS IN THE
 TITLE BLOCK.--THE TITLE BLOCK MUST SHOW THE
 BUSINESS LICENSE NUMBER. FAC 61G1-16.004(1)(2) & FS
 481.219 481.2055--(SEE ATTACHED SHEETS FROM DBPR
 WEBSITE).
 ****NO RESPONSE NOTED, BUT THE ADDRESS NOW REFLECTS THE
 DBPR WEBSITE. THE BUSINESS LICENSE NUMBER IS STILL NOT
 IN THE TITLE BLOCK AS REQUIRED.
  
 4. OK COMMENT FOR 3RD FLOOR ONLY.
  
 5. OK NOT REQUIRED 2ND FLOOR.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2007-05-10 Cont ID  
Sent By mflis Date 2007-05-10 Time 08:55 Rev Time 0.00
Received By mflis Date 2007-05-10 Time 08:55 Sent To  
Notes
2007-05-10 08:56:21ZONING REVIEW: NOT REQUIRED
  
 * REVIEW OF INTERIOR REMODEL WORK ONLY; NO EXTERIOR
 MODIFICATIONS FOR ZONING REVIEW
  
 MATT FLIS - 822-1445