| 2007-05-07 17:04:21 | ** UNSAT 2ND REVIEW** |
| | |
| | ***** IMPORTANT ***** |
| | ** PLEASE SEE THERE ARE SEVERAL ITEMS FROM THE PREVIOUS |
| | REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. |
| | ** PLEASE ALSO SEE THAT THERE ARE SEVERAL NEW COMMENTS |
| | BASED ON THE RESPONSES AND THE REVISED PLANS. MANY |
| | ITEMS WERE SUBSTANTIALLY REVISED INCLUDING THE SCOPE OF |
| | WORK PER FLOOR UNDER SEPARATE PERMITS. |
| | |
| | ** THIS IS A REVIEW FOR SECOND FLOOR UNDER A NEW PERMIT |
| | NUMBER HOWEVER THE REVIEW WAS PREVIOUSLY CONDUCTED |
| | UNDER #07011148 WHEN BOTH FLOORS WERE SUBMITTED UNDER |
| | ONE PERMIT. |
| | PLEASE SEE MANY OF THE COMMENTS ON THE ABOVE REFERENCED |
| | NUMBER MAY AFFECT THESE PLANS AND INFORMATION. |
| | |
| | ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1 |
| | ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF |
| | WEST PALM BEACH. |
| | |
| | |
| | MANY COMMENTS ARE FROM THE FIRST REVIEW. |
| | |
| | 1) NOTE:THIS IS THE SAME COMMENT AS PREVIOUS REVIEW. |
| | PLEASE SEE THE ARCHITECTURAL PLANS STILL INDICATE THE |
| | PREVIOUS CODES. PLEASE LIST THE FOLLOWING AS REQUESTED |
| | ON PREVIOUS REVIEW. PLEASE SEE ONLY THE CORRECTED CODES |
| | WERE ADDED TO THE ELECTRICAL SHEETS AND NOT TO A |
| | SHEETS. |
| | PLEASE SEE THE CODES SHALL BE STATED ON THE PLANS. ALL |
| | APPLICATIONS AFTER DECEMBER 8TH, 2006 ARE UNDER THE |
| | 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70. |
| | PLEASE ALSO SEE THAT THE FOLLOWING SHALL ALSO BE |
| | STATED. 2003 NFPA-101 AND THE 2002 NFPA-72. **PLANS |
| | STATE LATEST EDITION. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 2) NOTE: PLEASE INDICATE THE SUITE/UNIT NUMBER(S) ON |
| | PLANS. |
| | SAME NOTE AS PREVIOUS REVIEW. ONLY THE ELECTRICAL |
| | SHEETS WERE CORRECTED TO INDICATE THE SUITE/UNIT |
| | NUMBER. PLEASE SEE THIS COMMENT IS FOR ALL TRADES AND |
| | FOR ALL SHEETS WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | TRADES. |
| | ** PLEASE KNOW THAT ANY SHEETS WHICH ARE NOT REQUIRED |
| | TO BE CORRECTED FOR ANY TRADE/CODE RELATED COMMENT MAY |
| | HAVE THE SUITE/UNIT NUMBER WRITTEN/PRINTED OR STAMPED |
| | ON TITLE BLOCKS. |
| | FBC 106.1.2, |
| | FAC 61G1-16.004 |
| | |
| | 3) NOTE: PLEASE SEE THE MISSING PRINTED LICENSE NUMBER |
| | FOR THE ARCHITECT ON THE TITLE BLOCKS. 61G1-16.004. |
| | THIS COMMENT WAS MADE ON THE PREVIOUS REVIEW AND THE |
| | RESPONSE MENTIONS THAT PERHAPS THIS WAS MISSED AS IT IS |
| | LISTED ON THE UPPER RIGHT HAND CORNER OF THE |
| | PLANS/TITLE BLOCKS. |
| | PLEASE SEE THE TITLE BLOCKS INDICATE THE PRINTED *FIRM* |
| | CERTIFICATE OF AUTHORIZATION NUMBER WHICH IS OK AND |
| | REQUIRED BUT DOES NOT INDICATE THE PRINTED LICENSE |
| | NUMBER OF THE ARCHITECT AS REQUIRED PER SECTION STATED |
| | PREVIOUSLY. NONE OF THE SHEETS CONTAIN THIS "PRINTED |
| | LICENSE NUMBER" OF THE ARCHITECT. |
| | THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADES. |
| | PLEASE REVISE AND ADDRESS ACCORDINGLY. ** ONE SHEETS |
| | WHICH DO NOT NEED TO BE REVISED BY OTHER TRADES FOR |
| | CODE COMPLIANCE, THIS MAY BE PRINTED/STAMPED ON |
| | SHEETS. |
| | |
| | 4) NOTE: PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS AND |
| | PERFORMANCE DENSITIES PER 13-415.1.AB.1, 13-415.2. NO |
| | CALCULATIONS COULD BE LOCATED. |
| | ONLY THE LIGHTING PERFORMANCE FOR LIGHTING WAS LOCATED |
| | ON PLANS. PLEASE VERIFY THE NUMBER OF FIXTURES, THE |
| | WATTAGES, AND SQ FT FOR LPD. |
| | THE TOTAL WATTAGE WHICH WAS DERIVED USING THE NUMBER OF |
| | FIXTURES ON PLANS AND THE WATTAGE FOR EACH AS LISTED ON |
| | FIXTURE LEGEND SEEMS TO BE SLIGHTLY DIFFERENT THAN THAT |
| | SHOWN ON LIGHTING PLANS. |
| | |
| | 5) NOTE:PLEASE SEE THIS NOTE AS LISTED IS THE SAME AS |
| | PREVIOUS REVIEW. IN FACT ONE OF THE SAME ELECTRICAL |
| | SHEETS SUBMITTED ON PREVIOUS PLANS WAS NOW SUBMITTED AS |
| | E3.3 WHICH IS MISSING MUCH OF THE INFORMATION WHICH WAS |
| | SHOWN ON PREVIOUS PLANS ON SHEET E3? |
| | PLEASE SEE NO SCHEDULING, OVER RIDE TIMES, SYSTEM, |
| | CONTROL PANEL LOCATION, CIRCUITS, ZONES, ETC IS SHOWN. |
| | ** PLEASE SEE THAT THE LIGHTING PANEL WHICH IS ON THE |
| | 3RD FLOOR MAY NOT BE USED FOR SECOND FLOOR. |
| | PLEASE SEE RESPONSE MENTIONS 1HR OVER RIDES, HOWEVER ON |
| | AN OCCUPANCY SENSOR TYPE DEVICES, THE MAXIMUM OVER RIDE |
| | TIME IS 30MINS. |
| | PLEASE REVISE PLANS, PROVIDE COMPLETE DETAILS FOR |
| | CHAPTER 13 CODE COMPLIANCE. |
| | ** PLEASE SEE THERE ARE NOTES ON LIGHTING SHEETS WHICH |
| | REFLECT TO A NOTE #4, THIS NOTE #4 MENTIONS TO SEE |
| | DETAILS ON SHEET E-4,HOWEVER NO SHEET E4 IS IN SETS |
| | PR SUBMITTED? |
| | DEVICES ON LEGEND NEED TO COORDINATE WITH DETAIL FOR |
| | ALL DEVICES, TIMES, TYPES ETC. THE LEGEND DOES NOT |
| | INDICATE ANY SENTRY DEVICE AS NOTED ON PLANS. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT COMPLETE SCHEDULING FOR THE TIMES IN USE |
| | FOR THE LIGHTING CONTROL SYSTEM. PLEASE SEE THE SECTION |
| | OF THE CODE OF CHAPTER 13 QUOTED AS 413 SHOULD BE 415. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3 AS THERE IS |
| | MISSING CONTROLS FOR SEPARATE SPACES. |
| | PLEASE BE SURE TO INDICATE ALL OF THESE DEVICES AND |
| | CORRELATE WITH THE SYMBOL LEGEND. PLEASE INDICATE THE |
| | MAXIMUM AMOUNT OF TIME FOR OVER RIDE(S). |
| | (PLEASE SEE SOME DEVICES ON PLANS AND THE DESIGNATIONS |
| | ON PLAN SYMBOL LEGEND DO NOT SEEM TO INDICATE DEVICES |
| | FOR COMPLIANCE WITH CHAPTER 13. |
| | |
| | |
| | 6) NOTE:THIS SAME NOTE WILL REMAIN AS THE SCOPE OF |
| | WORK APPLIED FOR UNDER 3RD AND 2ND FLOOR IS NOT CLEAR |
| | ON HOW THE PANELS ETC FOR THE IT ROOM WILL BE DONE. THE |
| | NOTE IS THE SAME OF THAT WHICH IS ON 07011148IT ROOM |
| | REQUIREMENTS SEEMS TO HAVE BEEN ADDRESSED, HOWEVER |
| | QUESTION HAS NOW RISEN OVER SCOPE OF WORK AND WHICH |
| | PERMIT THIS WORK WILL BE UNDER. PLEASE SEE THE |
| | ELECTRICAL RISER NOW SHOWS, NOTES AND INDICATES THIS |
| | SCOPE OF WORK IS NOT INCLUDED FOR THIRD FLOOR AND IS |
| | UNDER 2ND FLOOR SCOPE?? PLEASE SEE THE PERMIT |
| | APPLICATION AND PLANS FOR THE SECOND FLOOR ALSO STATE |
| | THE SAME THING? |
| | PLEASE BE SURE TO COORDINATE ALL SCOPES OF WORK, UNDER |
| | WHICH PERMIT AND REVISE PLANS AS NEEDED. HOW WILL THE |
| | 3RD FLOOR WHICH IS UNDER A SEPARATE PERMIT FROM THE 2ND |
| | FLOOR OBTAIN A FINAL/CERTIFICATE OF COMPLETE ION OR |
| | OCCUPANCY WHEN THE SCOPE FOR THAT FLOOR HAS NOT BEEN |
| | DONE YET? |
| | PLEASE SUBMIT THE SPECS/PLANS AND DOCUMENTS UNDER THE |
| | PERMIT BEING APPLIED FOR. |
| | FBC 106.1.2, 106.3.5.1.2ADMIN SECTION. |
| | |
| | 7) NOTE: ** THIS COMMENT IS NOT FOR MEP FIRM: PLEASE |
| | SEE FIRE REVIEW COMMENTS AS THE FP SHEETS IN NEW SETS |
| | ARE OF NEW DESIGNER AND NOTE THAT SUBMITTED FROM |
| | PREVIOUS REVIEWED PLANS. |
| | PLEASE SEE THE FOLLOWING ITEMS ARE REQUIRED WHETHER OR |
| | NOT COMMENT IS MADE BY THE FIRE REVIEWER. |
| | PLEASE SEE NEW REVISED SHEET FP-2 IS THE ONLY SHEET IN |
| | SETS. |
| | ** PLEASE SEE THE SEAL WHICH IS NOW BEING USED ON THE |
| | REVISED FP-2 SHEETS IS NO LONGER VALID WITH THE FLORIDA |
| | BOARD OF PROFESSIONAL ENGINEERS. PLEASE SEE RULING FAC |
| | 61G15-23.001 WHICH CHANGED IN FEB *04* REQUIRING ALL |
| | SEALS FOR ENGINEERS TO CHANGE AND USE THE WORDING OF |
| | *LICENSE* IN SAID SEAL AND COULD NOT LONGER USE THE |
| | WORDING OF *CERTIFICATE*. AN EXTENSION WAS GRANTED BY |
| | THE BOARD TO THE DATE OF 12/31/05 HOWEVER ALL SEALING |
| | OF DOCUMENTS AFTER THAT DATE MUST BE DONE USING NEW |
| | SEAL. |
| | PLEASE OBTAIN CORRECTED SEAL FROM THE STATE/BOARD. |
| | **PLEASE ALSO SEE MISSING TITLE BLOCK INFORMATION |
| | REQUIRED FOR THE ENGINEER OF RECORD FOR THE FP SHEETS. |
| | PLEASE KNOW IF THE ENGINEER OF RECORD IS EMPLOYED BY |
| | THE FIRE PROTECTION COMPANY ( PHILLIPS FIRE SPRINKLERS |
| | INC) WHICH IS OFFERING ENGINEERING SERVICES, THEN SAID |
| | COMPANY SHALL OBTAIN AN ENGINEERING BUSINESS LICENSE |
| | NUMBER AS REQUIRED UNDER FLORIDA STATUTES 471.023 AND |
| | SHALL INCLUDE THIS INFORMATION ON TITLE BLOCKS AS |
| | REQUIRED PER FAC 61G15-23.002 |
| | PLEASE KNOW THAT IF THE ENGINEER IS PRACTICING AS AN |
| | INDIVIDUAL AND NOT EMPLOYED BY THE SAID COMPANY THEN |
| | THE SHEETS ARE REQUIRED TO CONTAIN INFORMATION FOR THE |
| | INDIVIDUAL TITLE BLOCK AS REQUIRED UNDER THE SAME |
| | SECTION OF THE FLORIDA ADMINISTRATIVE CODE. |
| | ** THIS HAS BEEN CONFIRMED WITH THE FLORIDA BOARD OF |
| | PROFESSIONAL ENGINEERS AND THE BOARDS LEGAL COUNSEL. IF |
| | THERE ARE ANY QUESTIONS ON THIS PLEASE CONTACT THE |
| | BOARD AS NOTED. |
| | |
| | 8) NOTE: PLEASE SEE THE ELECTRICAL RISER DIAGRAM HAS |
| | NOW BEEN COMPLETELY REVISED IN WHICH THERE ARE SEVERAL |
| | NEW COMMENTS AS WELL AS SOME ITEMS FROM PREVIOUS REVIEW |
| | WHICH ARE IN NEED OF ADDRESSING. |
| | SOME OF THE BELOW IS TAKEN FROM THE NOTES UNDER |
| | 07011148. PLEASE COORDINATE BOTH PERMITS, PLANS AND |
| | SCOPE OF WORK. |
| | PLEASE SEE THE RISER NOW INDICATES 277/480V SERVICE |
| | BEING INSTALLED FROM A NEW 1MA AND THE RISER STILL |
| | INDICATES THE BUS-DUCT RISER AS 277/480V? PLEASE SEE |
| | THE RISER FOR DISCONNECT WHICH IS NOTED #14 WHICH |
| | INDICATES THIS DISCONNECT AS 120/208V? |
| | PLEASE SEE RISER, WHICH SHOWS THE DISCONNECT FOR THE |
| | ASSUMED 277/480 OR 120/208 ON THE FORTH FLOOR WHICH IS |
| | FOR THE THIRD FLOOR AND THE DISCONNECT WHICH IS ON THE |
| | THIRD FLOOR WHICH FEEDS THE SECOND FLOOR? AS THE |
| | VOLTAGES CONFLICT, IT APPEARS THERE ARE TWO COMPLETELY |
| | SEPARATE 277/480VOLT SERVICES BEING FED FROM TWO |
| | SEPARATE MAINS?? |
| | PLEASE SEE THE 2ND FLOOR WHICH CONTAINS LIGHTING |
| | CONTROLS WHICH IS BEING FED FROM THE THIRD FLOOR |
| | ELECTRICAL SERVICE WHICH IS NOT PERMITTED.( IN THE |
| | EVENT POWER IS NEEDED TO BE SHUT DOWN FOR THIS FLOOR, |
| | THESE SWITCHES WOULD REMAIN ENERGIZED). |
| | |
| | PLEASE SEE DISCONNECT #22 INDICATES A NEUTRAL ON THE |
| | LINE SIDE OF THE TRANSFORMER? IF THIS IS SUPPOSED TO BE |
| | A SEPARATELY DERIVED SYSTEM, THEN A NEUTRAL CONDUCTOR |
| | WOULD NOT BE INSTALLED TO THE TRANSFORMER FROM THIS |
| | DISCONNECT NOTED AS #22. SEE NOTE #15 FOR CONDUCTORS. |
| | THE RISER IS NOT CLEAR FOR VOLTAGES, SERVICES, CROSSING |
| | OVER OF SYSTEMS, WHAT IS OR IS NOT SEPARATELY DERIVED |
| | ETC. THESE ITEMS CAN NOT BE ASSUMED. |
| | PLEASE CLARIFY PANELS 3LA AND 3LB AS BOTH ARE SHOWN AS |
| | 100AMP MCB, HOWEVER THIS IS BEING NOTED AND SHOWN ON |
| | RISER THAT EACH PANEL CONTAINS THIS AS PART OF THE |
| | EQUIPMENT, YET PANEL 3LB ALSO INDICATES THE PANEL |
| | CONTAINING A BACK FED BREAKER? IF THIS IS THE CASE, |
| | PLEASE NOTE REJECTION CLIP REQUIRED. 408.36F PLEASE SEE |
| | NEC 2005. |
| | FBC 106.3.5.1.2, 106.1.2. |
| | |
| | 9) NOTE: PLEASE SEE THE NEW 1MA WHICH IS NOW SHOWN AS A |
| | 500AMP MCB/MAIN CIRCUIT BREAKER PANEL WHICH CONTAINS AS |
| | BUS RATED AT 225AMPS. |
| | PLEASE EXPLAIN HOW THIS IS POSSIBLE. |
| | PLEASE SEE THE LOAD CALCULATIONS FOR THIS SAME PANEL |
| | INDICATES THE LOAD AT 297AMPS, AND THE BUS/SERVICE |
| | BEING RATED FOR 225AMPS. |
| | (ALSO LABELED AS 3MA)?? |
| | THIS RISER IS STILL UNCLEAR FOR VOLTAGES AND |
| | INSTALLATION OF THE EQUIPMENT. |
| | PLEASE SEE THE 2005 NEC. PANELS AND EQUIPMENT MUST BE |
| | RATED FOR THE LOADS, ETC. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | ** PLEASE KNOW THAT AT THIS TIME THE RISER IS VERY |
| | CONFUSING AS THERE ARE MANY ITEMS THAT DO NOT CORRELATE |
| | OR ARE MISSING AT THIS TIME. |
| | |
| | 10) NOTE:NOTE TO REMAIN AS RISER IS THE SAME OF THAT |
| | ON 07011148PLEASE INDICATE ANY GROUNDING ATTACHMENTS |
| | AND SIZES FOR SD SYSTEMS PER 250.20, 250.30, 250.66, |
| | AND 250.50 |
| | THIS WAS NOTED ON PREVIOUS REVIEW. INDICATE THE |
| | ATTACHMENT LOCATIONS. |
| | |
| | 11) NOTE: PLEASE SUBMIT AND SHOW LOAD CALCULATIONS ON |
| | ALL EXISTING WITH NEW LOADS BEING ADDED. |
| | THIS IS NOT ONLY FOR THE PANELS SHOWN, BUT FOR ALL |
| | EQUIPMENT WHICH LOADS, PANELS ETC ARE BEING ADDED. |
| | PLEASE SEE NOTE # 9 ABOVE WITH RESPECT TO 1MA. PLEASE |
| | SEE 220.10, 220.12, 220.14, 220.42, ETC, CONTINUOUS |
| | LOADS AT 125% PER 215.3, 230.42 ETC. |
| | |
| | 12) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS |
| | ONLY NOTED AT THIS TIME. |
| | ** ONE SET OF EACH OF THE SETS OF PLANS SUBMITTED WILL |
| | BE RETAINED BY THIS OFFICE. |
| | |
| | ** PLEASE KNOW AT THIS TIME DUE TO SOME INFORMATION NOT |
| | YET AVAILABLE FOR REVIEW, THERE MAY BE NEW COMMENTS ON |
| | THE NEXT REVIEW WHICH HAVE NOT YET BEEN MADE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |