| Plan Review Stops For Permit 07040768 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-04-30 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-04-30 |
Time |
11:28 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2007-04-30 |
Time |
11:19 |
Sent To |
I |
|
| Notes |
| 2007-04-30 11:27:56 | | | | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | 1} PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. | | | | | | 2} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT | | | SIZE AND TYPE, 106.3.5.4 FBC. | | | | | | 3} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH | | | 250.66. INDICATE SIZE AND SYSTEM ON THE PLAN. | | | | | | 4} GIVE PANEL SPECIFICATIONS, NUMBER OF SPACES, VOLTAGE | | | AND AMPERE RATING, MAIN LUG OR MAIN BREAKER. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|