Plan Review Details - Permit 07040768
Plan Review Stops For Permit 07040768
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-30 Cont ID  
Sent By btrobaug Date 2007-04-30 Time 11:28 Rev Time 0.50
Received By btrobaug Date 2007-04-30 Time 11:19 Sent To I
Notes
2007-04-30 11:27:56 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, 106.3.5.4 FBC.
  
 3} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66. INDICATE SIZE AND SYSTEM ON THE PLAN.
  
 4} GIVE PANEL SPECIFICATIONS, NUMBER OF SPACES, VOLTAGE
 AND AMPERE RATING, MAIN LUG OR MAIN BREAKER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-30 Cont ID  
Sent By btrobaug Date 2007-04-30 Time 11:28 Rev Time 0.00
Received By btrobaug Date 2007-04-30 Time 11:14 Sent To PC
Notes
2007-04-30 11:15:23TO "BTROBAUG" DESK--PLANS LOCATED TODAY