| Plan Review Stops For Permit 07040749 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2008-05-06 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2008-05-06 |
Time |
18:13 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2008-05-06 |
Time |
18:13 |
Sent To |
PC |
|
| Notes |
| 2008-05-06 18:14:58 | | | | | | | PASSED | | | | | | ONE COPY OF NEW PRODUCT APPROVAL INSERTED WITH PERMIT | | | APPLICATION, REVISED DRAWING REQUIRES PLUMBING | | | CORRECTIONS | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-10-27 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2007-10-27 |
Time |
07:02 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2007-10-27 |
Time |
07:02 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-10-11 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2007-10-11 |
Time |
17:32 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2007-10-11 |
Time |
17:32 |
Sent To |
PC |
|
| Notes |
| 2007-10-11 17:40:18 | | | | | | | | | | DENIED 3RD REVIEW | | | | | | THE FOLLOWING REVIEW COMMENTS WERE NOT ADDRESSED FROM | | | THE FIRST AND SECOND REVIEW: | | | | | | | | | 1)BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH | | | COUNTY. THE ACTUAL PERMIT SETS OF PLANS MUST BE STAMPED | | | BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED | | | TO THE PERMIT APPLICATION. PLEASE CALL (561) 233-5025 | | | FOR MOREINFORMATION. | | | | | | *******STAMP MUST BE PRESENT ON THE DRAWINGS EVEN IF NO | | | FEE IS REQUIRED******* | | | | | | 3)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 | | | FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER | | | AND OWNER/AGENT PRIOR TO SUBMITTAL | | | | | | ******NOTE ENERGY CALC'S WERE NOT SIGNED BY THE | | | OWNER/AGENT, ALSO THE INFORMATION PROVIDED ON THE | | | ENERGY CALC'S DOES NOT MATCH DRAWINGS, THEWALLS ARE | | | SHOWN AS CONCRETE WITH R4.2 INSULATION AND ALL WALLS | | | ARE WOOD FRAME, ALSO ONLY ONE COPY WAS SUBMITTED**** | | | | | | 5)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE | | | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO | | | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* | | | | | | *******ALL PRODUCT APPROVALS SHALL BE REVIEWED AND | | | APPROVED FOR USE BY DESIGNER ONLY ROOFING WAS REVIEWED | | | AND APPROVED******* | | | | | | 12)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT IS REQUIRED PRIOR TO | | | A PERMIT BEING ISSUED | | | | | | NEW COMMENT | | | | | | 1) PLEASE HAVE ENGINEER SIGN AND SEAL NEW PAGE 001 ALSO | | | WHEN RESUBMITTED PLEASE SEND TO ZONING FOR RESTAMPING | | | OF NEW PAGE 001 | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2007-08-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2007-08-15 |
Time |
17:00 |
Sent To |
PC |
|
| Notes |
| 2007-08-15 17:53:30 | | | | | | | DENIED 2ND REVIEW | | | | | | THE FOLLOWING REVIEW COMMENTS WERE NOT ADDRESSED FROM | | | THE FIRST REVIEW: | | | | | | | | | 1)BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH | | | COUNTY. THE ACTUAL PERMIT SETS OF PLANS MUST BE STAMPED | | | BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED | | | TO THE PERMIT APPLICATION. PLEASE CALL (561) 233-5025 | | | FOR MOREINFORMATION. | | | | | | *******STAMP MUST BE PRESENT ON THE DRAWINGS EVEN IF NO | | | FEE IS REQUIRED******* | | | | | | 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON | | | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER | | | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE | | | ADDED TO THE PERMIT APPLICATION FEES. AMOUNT DUE $1.20 | | | | | | 3)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 | | | FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER | | | AND OWNER/AGENT PRIOR TO SUBMITTAL | | | | | | ******NOTE ENERGY CALC'S WERE NOT SIGNED BY THE | | | OWNER/AGENT, ALSO THE INFORMATION PROVIDED ON THE | | | ENERGY CALC'S DOES NOT MATCH DRAWINGS, THEWALLS ARE | | | SHOWN AS CONCRETE WITH R4.2 INSULATION BUT ARE WOOD | | | FRAME CONSTRUCTION AND NO INSULATION VALUE HAS BEEN | | | GIVEN ON THE DRAWINGS AND THE ROOF IS SHOWN AS R19 AND | | | THE CALC'S STATE R30. PLEASE MAKE CORRECTIONS TO | | | DRAWINGS AND ENERGY CALC'S****** | | | | | | 4)THE FOLLOWING CORRECTIONS ARE REQUIRED ON THE | | | PRODUCT APPROVALS | | | A)2 DIFFERENT ROOFING SYSTEMS ARE INCLUDED IN THE GAF | | | MODIFIED ROOFING PRODUCT APPROVAL ONE FOR COLD APPLIED | | | AND ONE FOR HEAT WELD, PLEASE CHOOSE THE METHOD THAT | | | WILL BE USED. | | | ******BOTH ROOFING SYSTEMS ARE STILL INCLUDED IN THE | | | PRODUCT APPROVAL******* | | | | | | 5)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE | | | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO | | | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* | | | | | | *******SHALL BE REVIEWED AND APPRVED FOR USE BY | | | DESIGNER******* | | | | | | 7)PROVIDE THE FOLLOWING INFORMATION ON THE DRAWINGS: | | | E)DRAWINGS SHALL SHOW THE MINIMUM DEPTH OF FOUNDATION | | | ON THE WALL SECTIONS PER R403.1.4 FBC RES. | | | | | | 12)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT IS REQUIRED PRIOR TO | | | A PERMIT BEING ISSUED | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-06-16 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2007-06-16 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2007-06-16 |
Time |
09:20 |
Sent To |
PC |
|
| Notes |
| 2007-06-16 09:51:51 | | | | | | | DENIED | | | | | | 1)BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH | | | COUNTY. THE ACTUAL PERMIT SETS OF PLANS MUST BE STAMPED | | | BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED | | | TO THE PERMIT APPLICATION. PLEASE CALL (561) 233-5025 | | | FOR MOREINFORMATION. | | | | | | 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON | | | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER | | | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE | | | ADDED TO THE PERMIT APPLICATION FEES. AMOUNT DUE $1.20 | | | | | | 3)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2 | | | FBC. BE SURE THAT THEY ARE SIGNED AND DATED BY PREPARER | | | AND OWNER/AGENT PRIOR TO SUBMITTAL | | | | | | 4)THE FOLLOWING CORRECTIONS ARE REQUIRED ON THE | | | PRODUCT APPROVALS | | | A)2 DIFFERENT ROOFING SYSTEMS ARE INCLUDED IN THE GAF | | | MODIFIED ROOFING PRODUCT APPROVAL ONE FOR COLD APPLIED | | | AND ONE FOR HEAT WELD, PLEASE CHOOSE THE METHOD THAT | | | WILL BE USED. | | | B)THE JELD-WEN PRODUCT APPROVAL CONTAINS SEVERAL | | | DIFFERENT DOOR TYPE PLEASE CHOOSE THE MODEL AND NOA# | | | THAT WILL BE USED. NOTE SOME ARE NOT IMPACT RATED AND | | | WOULD REQUIRE IMPACT PROTECTIVE COVERINGS. | | | | | | 5)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE | | | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO | | | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* | | | | | | 6)PROVIDE SITE PLAN 2 COPIES OF A RECENT SURVEY | | | SHOWING THE PROPOSED BUILDING/ADDITION WITH ALL SIDE | | | AND REAR SETBACKS | | | | | | 7)PROVIDE THE FOLLOWING INFORMATION ON THE DRAWINGS: | | | | | | A)PROVIDE SMOKE ALARMS PER R313.1.1 FBC RES. | | | B)PROVIDE NOTE FOR SHOWER DOORS TO BE SAFETY GLAZING | | | PER R308.4 FBC RES. | | | C)TERMITE TREATMENT IS REQUIRED ON ALL EXTERIOR | | | CONCRETE WITHIN 1 FOOT OF PRIMARY STRUCTURE PER | | | R320.1.6 FBC RES. | | | D)PROVIDE PROTECTION AGAINST DECAY BY USE OF PRESSURE | | | TREATED WOOD AT LOCATIONS PER R319 FBC RES. | | | E)DRAWINGS SHALL SHOW THE MINIMUM DEPTH OF FOUNDATION | | | ON THE WALL SECTIONS PER R403.1.4 FBC RES. | | | | | | 8)SHOW MORE DETAIL ON EXTERIOR BEARING WALL, PROVIDE | | | WALL FRAMING IN ELEVATION TO PROVIDE CLEAR DETAILS ON | | | THE CONNECTIONS BEING MADE AND THE SUPPORT OF THE (2) | | | 2X10 BEAM ETC. SECTION S/1 ONLY SHOWS 2X4 POST BUT HAS | | | 4X4 POST CONNECTORS. | | | | | | 9)ROOF FRAMING PLAN AND DETAIL S/1 SHOW DIFFERENT | | | RAFTER CONNECTORS (FRAMING PLAN ACE4 AND S/I HAS H14 | | | PLEASE MAKE CORRECTION. | | | | | | 10)DETAIL S/1 SHOWS GYPSUM AS EXTERIOR SHEATHING | | | | | | 11)PROVIDE NOTE FOR EXISTING EXTERIOR WINDOW THAT | | | WILL BECOME PART OF INTERIOR BATHROOM WALL (REMOVAL AND | | | INFILL REQUIREMENTS) | | | | | | 12)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT IS REQUIRED PRIOR TO | | | A PERMIT BEING ISSUED | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-04-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-04-28 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-04-28 |
Time |
13:14 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-08-15 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-08-15 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-08-15 |
Time |
10:28 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-05-07 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-05-07 |
Time |
07:11 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2007-05-07 |
Time |
06:38 |
Sent To |
P |
|
| Notes |
| 2007-05-07 07:11:12 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED | | | GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL | | | SWITCH?CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED TO | | | PROVIDE ILLUMINATION ON THE EXTERIOR SIDE OF OUTDOOR | | | ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS. A VEHICLE | | | DOOR IN A GARAGE SHALL NOT BE CONSIDERED AS AN OUTDOOR | | | ENTRANCE OR EXIT. 210.70(A)(20(B) PLEASE LOCATE SAME ON | | | THE PLAN. | | | | | | 2} .R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED | | | IN NEW DWELLINGS AND WHEN REPAIRS OR ADDITIONS | | | REQUIRING A PERMIT OCCUR. SEE ARTICLE FOR COMPLETE | | | TEXT. SHOW LOCATION ON PLANS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2008-09-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-16 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-16 |
Time |
16:53 |
Sent To |
E |
|
| Notes |
| 2008-09-16 16:54:05 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2008-04-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-28 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-28 |
Time |
11:11 |
Sent To |
E |
|
| Notes |
| 2008-04-28 11:11:35 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-10-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-24 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-24 |
Time |
11:56 |
Sent To |
Z |
|
| Notes |
| 2007-10-24 11:56:41 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-10-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-09 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-09 |
Time |
16:26 |
Sent To |
B |
|
| Notes |
| 2007-10-09 16:27:16 | TO "AMORSE" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-08-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-15 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-15 |
Time |
09:10 |
Sent To |
E |
|
| Notes |
| 2007-08-15 09:10:47 | TO "BTROBAUG" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-07-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-20 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-20 |
Time |
15:51 |
Sent To |
Z |
|
| Notes |
| 2007-07-20 15:51:45 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-05-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-04 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-04 |
Time |
15:11 |
Sent To |
E |
|
| Notes |
| 2007-05-04 15:11:26 | TO "SFR" "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2007-06-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-23 |
Time |
14:59 |
Sent To |
|
|
| Notes |
| 2007-04-23 15:00:11 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2007-05-08 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-05-08 |
Time |
09:12 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-05-08 |
Time |
09:12 |
Sent To |
B |
|
| Notes |
| 2007-05-08 09:13:23 | NO MECHANICAL PLANS SUBMITTED, AND NO | | | MECHANICAL PERMIT NUMBER APPLIED FOR AT | | | THIS TIME. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2008-10-03 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-10-03 |
Time |
14:31 |
Rev Time |
0.15 |
| Received By |
mperson |
Date |
2008-10-03 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2008-10-03 14:32:57 | T/A REVISION #2 (SEE FRONT SCREEN NO FEE): "OK" CHANGED | | | PLBG. REV. NUMBER FROM 1 TO 2. *MRPERSON. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2008-09-18 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-09-18 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-09-18 |
Time |
14:03 |
Sent To |
E |
|
| Notes |
| 2008-09-18 14:05:28 | REVISION #1 SHEET 002: "OK" CHANGED BATHROOM FLOOR PLAN | | | LAYOUT AND SUBMITTED NEW SANITARY ISOMETRIC RISER | | | DIAGRAM. *MRPERSON. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2008-04-29 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-04-29 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-04-29 |
Time |
14:45 |
Sent To |
B |
|
| Notes |
| 2008-04-29 14:52:32 | PLUMBING PLAN REVIEW: | | | REVISION DENIED: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. SHEET 002 SANITARY ISOMETRIC RISER DIAGRAM: THE | | | SHOWER REQUIRES A VENT. PER FBC-2004 PLUMBING SECTION | | | 901.2.1 VENTING REQUIRED. | | | | | | 2. SHEET 002 PLEASE CORRECT THE SPELLING OF | | | "SANITARIUM" TO BE SANITARY ON THE RESUBMITTED PLANS. | | | PER (W.P.B. AS AMENDED) SECTION 106.1.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS AND FBC-2004 PLUMBING SECTION | | | 701.1 SCOPE. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION | | | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | NOTE: THERE IS ONLY ONE CORRECTED DRAWING | | | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS | | | EXAMINER FOR REFERENCE FOR THE | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2007-08-15 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-08-15 |
Time |
11:35 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2007-08-15 |
Time |
11:34 |
Sent To |
B |
|
| Notes |
| 2007-08-15 12:06:46 | ****************PROVISO**************** | | | PER FBC-2004 PLUMBING, SECTION 405.3.1 A WATER CLOSET | | | OR LAVATORY SHALL NOT BE SET CLOSER THAN 15 INCHES FROM | | | ITS CENTER TO ANY SIDE WALL, PARTITION, VANITY OR OTHER | | | OBSTRUCTION, OR CLOSER THAN 30 INCHES CENTER-TO-CENTER | | | BETWEEN THE WATER CLOSETS OR ADJACENT FIXTURES. THERE | | | SHALL BE AT LEAST A 21 INCH CLEARANCE IN FRONT OF THE | | | WATER CLOSET OR LAVATORY TO ANY WALL, FIXTURE OR DOOR. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL= [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-05-07 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-05-07 |
Time |
15:36 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2007-05-07 |
Time |
15:36 |
Sent To |
M |
|
| Notes |
| 2007-05-07 15:54:41 | DENIED | | | REFERENCE: | | | ** FBC-2004 PLUMBING. | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. PER FBC-2004 PLUMBING, SECTION | | | 901.2.1 VENTING REQUIRED: EVERY TRAP AND | | | TRAPPED FIXTURE SHALL BE VENTED IN | | | ACCORDANCE WITH ONE OF THE VENTING | | | METHODS SPECIFIED IN THIS CHAPTER. | | | NOTE: A VENT IS REQUIRED FOR THE BATHROOM GROUP IN THE | | | PROPOSED BATHROOM ADDITION. PLEASE CORRECT ON THE | | | RESUBMITTAL. | | | | | | 2. PER FBC-2004 PLUMBING, SECTION 708.3.5 BUILDING | | | DRAIN AND BUILDING | | | SEWER JUNCTION. THERE SHALL BE A TWO-WAY | | | CLEANOUT NEAR THE JUNCTION OF THE | | | BUILDING DRAIN AND THE BUILDING SEWER. | | | NOTE: PLEASE INDICATE A TWO-WAY CLEANOUT FOR THE | | | PROPOSED BATHROOM ADDITION ON THE RESUBMITTAL. | | | | | | 3. PER FBC-2004 PLUMBING, SECTION 416 PLEASE CORRECTLY | | | IDENTIFY THE FIXTURE IN THE PROPOSED BATHROOM ADDITION | | | AS A LAVATORY (LAV) ON THE RESUBMITTAL. | | | | | | 4. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 | | | RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A | | | PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING | | | ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT | | | LOCATIONS. | | | NOTE: PLEASE CLEARLY SIZE THE LAV WASTE,VENT AND TRAP | | | ON THE RESUBMITTAL. | | | | | | ********IMPORTANT INFORMATION******** | | | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | | PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED, PLEASE INCLUDE A | | | TRANSMITTAL LETTER INDICATING HOW EACH | | | ITEM WAS ADDRESSED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. | | | NOTE: ONLY ONE CORRECTED DRAWING | | | IN RED INK FOR REFERENCE FOR | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2007-10-25 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-10-25 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2007-10-25 |
Time |
11:07 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2007-08-15 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-08-15 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2007-08-15 |
Time |
08:51 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-05-02 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-05-02 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2007-05-02 |
Time |
16:04 |
Sent To |
I |
|
| Notes |
| 2007-05-02 16:06:32 | ***FAILED*** | | | | | | 1) TWO (2) COPIES OF A CURRENT, ACCURATE SURVEY SHALL | | | BE PROVIDED.THE SURVEY SHALL ALSO SHOW THE LOCATION | | | AND SIZE OF THE PROPOSED ADDITION, WITH THE SETBACK | | | DIMENSIONS FROM THE ADDITION TO ALL PROPERTY LINES. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | | AT (561) 822-1435. |
|
|