Plan Review Details - Permit 07040727
Plan Review Stops For Permit 07040727
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-01-15 Cont ID  
Sent By shill Date 2009-01-15 Time 17:33 Rev Time 0.00
Received By shill Date 2009-01-15 Time 17:33 Sent To  
Notes
2009-01-15 17:33:36REVISION E7, F1, D3, F4

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-12-08 Cont ID  
Sent By shill Date 2008-12-08 Time 13:37 Rev Time 0.00
Received By shill Date 2008-12-08 Time 13:37 Sent To M
Notes
2008-12-08 13:42:13****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. FIXED GLASS PRODUCT APPROVALS SUBMITTED, NONE SHOWN
 ON PLAN, SEE F1.
  
 2. THE DOUBLE SH24 WINDOWS WERE CLOUDED, WHAT CHANGED?
 THE LOCATION WHERE THE DOOR IS ELIMINATED WAS NOT
 CLOUDED. ALL CHANGES TO BE CLEARLY INDICATED. FBC*106
  
 3. WALL AREA ON THE ENERGY CALCS HAS DECREASED, BUT THE
 WALLS ARE NOW TALLER. PLEASE EXPLAIN. FBC13
  
 4. NEW ENERGY CALCCS SHOWS A NEW WINDOW ON THE NORTH
 WALL, BUT THE NEW WINDOW IS ON THE SOUTH WALL. PLEASE
 REVISE. FBC13

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-06-21 Cont ID  
Sent By amorse Date 2008-06-21 Time 08:08 Rev Time 0.00
Received By amorse Date 2008-06-21 Time 08:08 Sent To PC
Notes
2008-06-21 08:09:04 
  
 FINAL PROCESSING OF PERMIT (NEW PAGES)

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-05-27 Cont ID  
Sent By amorse Date 2008-05-27 Time 18:31 Rev Time 0.00
Received By amorse Date 2008-05-27 Time 18:31 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-03-08 Cont ID  
Sent By amorse Date 2008-03-08 Time 10:48 Rev Time 0.00
Received By amorse Date 2008-03-08 Time 10:48 Sent To PC
Notes
2008-03-08 11:26:00 
  
  
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED ON THE 1ST
 REVIEW
  
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES ******FEES ADDED
 DUE TO INCREASED SQUARE FOOTAGE******
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*. FEES ARE DUE FOR THE STATE RADON AND
 THE INCREASED PERMIT VALUE IN THE AMOUNT OF $718.85
 THIS MUST BE PAID BEFORE FURTHER PLAN REVIEW IS
 PERFORMED.********THE INCREASE IN VALUE IS DUE TO
 ADDED SQUARE FOOTAGE, VALUE BASED ON BUILDING VALUATION
 DATA FROM FEB 2007 WHEN FIRST PERMITTED*********
  
 5)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD. ******THIS MAY BY
 DELIVERED TO SITE INSPECTOR PRIOR TO ROOF FRAMING
 INSPECTION******
  
 10)THE FOLLOWING CORRECTIONS ARE REQUIRED FOR THE
 PRODUCT APPROVALS:
 A)PRODUCT APPROVALS ARE REQUIRED FOR CASTCRETE
 LINTELS OR THE FLORIDA STATEWIDE APPROVAL NUMBER ADDED
 TO THE LINTEL SCHEDULE
 B)PRODUCT APPROVALS ARE REQUIRED FOR SIMPSON/USP
 CONNECTOR OR THE STATEWIDE APPROVAL NUMBERS MAY BE
 ADDED TO THE CONNECTOR SCHEDULE ******* IN LUE OF
 PRODUCT APPROVALS STRAPS/CONNECTORS MAY BE LISTED IN A
 SCHEDULE ON THE DRAWINGS COMPLETE WITH THE STATEWIDE
 PRODUCT APPROVAL NUMBERS OR SUBMIT SIMPSON TIE?S
 COMPLETE FLORIDA INDEX WITH CONNECTORS TO BE USED
 HIGHLIGHTED*********
  
 2ND REVIEW COMMENTS
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 2)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES.
  
 3)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER
 R313.1.1 FBC RES.
  
 4)PROVIDE MIN ROOF SHEATHING ATTACHMENT PER
 R803.2.3.1 FBC RES. ***** REQUIRES 8D RING SHANK AND A
 4" O/C PATTERN IN ZONE 3 OF ROOF IN AREAS WHERE DESIGN
 WIND SPEEDS ARE 130 MPH OR GREATER
  
 5)SUBMIT A COPY OF THE RECORDED NOTICE OF
 COMMENCEMENT TO THE CONSTRUCTION SERVICES DEPARTMENT.
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-12 Cont ID  
Sent By amorse Date 2007-06-12 Time 17:14 Rev Time 0.00
Received By amorse Date 2007-06-12 Time 17:14 Sent To PC
Notes
2007-06-12 17:54:04 
  
 DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MOREINFORMATION.
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*. FEES ARE DUE FOR THE STATE RADON AND
 THE INCREASED PERMIT VALUE IN THE AMOUNT OF $ 241.32
 THIS MUST BE PAID BEFORE FURTHER PLAN REVIEW IS MADE.
  
 4)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
  
 5)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD. PLEASE SEE THAT
 FOUNDATION PLAN HAS AN OUT TO OUT MEASUREMENT OF 17'-2"
 AND THE TRUSS ENGINEERING STATES 18'-2"ALSO PER
 106.1.3 FBC* THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS "NO WHITE OUT, PENCIL OR INK"
  
 6)AN ENGINEER PRACTICING THROUGH A DULYAUTHORIZED
 ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND
 LICENSE #, AS WELL AS THE NAME, ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER
 61G15-23.002 (2) FAC
  
 7)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 8)PLEASE CORRECT THE DISCREPANCY BETWEEN THE
 FOUNDATION PLAN OVERALL MEASUREMENT OF 52'-0" AND THE
 FLOOR PLAN OF 51'-11"
  
 9)TRUSS LAYOUT ON T/1 HAS NOTES FOR MARK "C" THAT
 CALL FOR META12 STRAPS BUT THE UPLIFT TABLE HAS TYPE D
 WHICH IS A HETA20. THE META12 DOES NOT MEET THE UPLIFT
 VALUE FROM THE TABLE. PLEASE CLARIFY
  
 10)THE FOLLOWING CORRECTIONS ARE REQUIRED FOR THE
 PRODUCT APPROVALS:
 A)PRODUCT APPROVALS ARE REQUIRED FOR CASTCRETE
 LINTELS OR THE FLORIDA STATEWIDE APPROVAL NUMBER ADDED
 TO THE LINTEL SCHEDULE
 B)PRODUCT APPROVALS ARE REQUIRED FOR SIMPSON/USP
 CONNECTOR OR THE STATEWIDE APPROVAL NUMBERS MAY BE
 ADDED TO THE CONNECTOR SCHEDULE
 C)PROVIDE THE TYPE OF ASSEMBLY FROM THE GAF RUBEROID
 PRODUCT APPROVAL THAT WILL BE USED ON THE ROOF. PLEASE
 NOTE THAT IN 140 MPH EXP B THE ZONE 3 AREA OF THE ROOF
 HAS A PSF VALUE OF -89.0, MOST ASSEMBLIES MAX OUT AT
 -75 PSF WITH A LIMITATION #7 (SEE PAGE32) THAT REQUIRES
 CALCULATIONS TO ENHANCE THE FASTENERS TO MEET THE ZONE
 3 REQUIREMENTS. HAVE DESIGNER OF RECORD PROVIDE THESE
 CALC'S.
 D)POMA STORM PANEL NOA HAS EXPIRED, NEW NOA NUMBER IS
 NOW POSTED ON MIAMI-DADE SITE BUT NOT UNDER POMA
  
 11)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL. MAKE CORRECTIONS FOR FLAT ROOF TYPE
  
 12)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-12-29 Cont ID  
Sent By btrobaug Date 2008-12-29 Time 17:00 Rev Time 0.00
Received By btrobaug Date 2008-12-29 Time 15:56 Sent To M
Notes
2008-12-29 17:01:39 
  
  
 TO MECH ON THE RESIDENTIAL RACK./WRT.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-12-02 Cont ID  
Sent By btrobaug Date 2008-12-02 Time 10:55 Rev Time 0.00
Received By btrobaug Date 2008-12-02 Time 10:07 Sent To B
Notes
2008-12-02 10:53:22 
  
 REVISION DENIED
  
 THE PERMIT SET OF PLANS WERE ISSUED UNDER PROVISO'S TO
 BE CORRECTED ON THE FIRST REVISION. THE FOLLOWING HAVE
 NOT BEEN CORRECTED ON THE ELECTRICAL PLAN SHEET E2.
  
 1} BATH CIRCUITS PER 210.11(C)(3)*** BATHROOM BRANCH
 CIRCUITS IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS
 REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE
 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY
 BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE
 NO OTHER OUTLETS.***CIRCUIT #10 LABELED "FLORIDA ROOM
 RECEPTACLES" SERVE THE BATH RECEPTACLES IN VIOLATION OF
 THIS ARTICLE. INDICATE BATH CIRCUIT ON THE PANEL
 SCHEDULE PER 408.4.
  
 2} .R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED.*** THE
 NOTE (#9) REQUIRING THAT ARTICLE WAS REMOVED FROM THE
 PLAN. ALSO SEE THAT EACH SMOKE ALARM (MISMARKED
 "DETECTORS") IS ON A DIFFERENT CIRCUIT THEREFORE NOT
 INTERCONNECTED PER MANUFACTURE SPECIFICATION.
  
 NEW COMMENT:
  
 3} THE DESIGNER OF RECORD IS THE ONLY PERSON AUTHORIZED
 TO REVISE HIS/HER PLAN. PER 481.229(1)(B) JOSEPH
 DRAGONMUST MAKE ANY CHANGES TO THIS SHEET.
  
 NOTE: THE PANEL LOCATION SUBMITTED IS CODE COMPLIANT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-05-21 Cont ID  
Sent By btrobaug Date 2008-05-21 Time 15:02 Rev Time 0.00
Received By btrobaug Date 2008-05-21 Time 13:36 Sent To P
Notes
2008-05-21 15:02:38 
  
  
 SEE PROVISO ON PLAN./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-02-27 Cont ID  
Sent By btrobaug Date 2008-02-27 Time 11:51 Rev Time 0.00
Received By btrobaug Date 2008-02-27 Time 07:08 Sent To P
Notes
2008-02-27 07:59:37 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 2} THE LOAD CALCULATIONS SUBMITTED DO NOT MEET THE
 REQUIREMENTS OF THE NEC. PROVIDE LOAD CALCULATIONS PER
 ARTICLE 220 PART III, STANDARD OR PART IV OPTIONAL,
 INDICATE METHOD USED. SEE 220.1.
  
 3}} PROVIDE PANEL SCHEDULES PER 408.4. INCLUDE OCP
 AND CONDUCTOR SIZES. PLEASE SEE NEW VERBAGE FOR 2005
 NEC: "THE IDENTIFICATION SHALL INCLUDE SUFFICIENT
 DETAIL TO ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM
 ALL OTHERS."
  
 4} THE RISER DIAGRAM INDICATES A METER/MAIN TYPE OF
 SERVICE EQUIPMENT. INDICATE THE SIZE OF THE MAIN
 BREAKER (DETERMINED BY THE LOAD CALCULATION) SO THE
 CORRECT SIZE OF THE GROUNDING ELECTRODE MAY BE
 DETERMINED PER 250.66.
  
 5} AN EQUIPMENT GROUND PER 250.122 MUST BE RAN WITH THE
 FEEDER CONDUCTOR TO THE PROPOSED PANEL. VERIFY THAT
 NONE WERE RAN WITH THE EXISTING FEEDER RUNS AS THEY ARE
 REQUIRED PER THAT ARTICLE.
  
 6} THEDISCONNECTING MEANS FOR THE WATER HEATER DOES
 NOT COMPLY WITH THE CLEARANCE REQUIREMENTS OF 110.26.
 SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS, AND
 422.31(B) FOR HARDWIRE REQUIREMENTS.
  
 7}COMPLIANCE WITH THE REQUIRED DISCONNECT PER 440.14,
 MUST ALSO COMPLY WITH 110.26 CLEARANCE REQUIREMENTS. A
 RECEPTACLE(S) ARE SHOWN AT THE CONDENSER LOCATIONS.
  
 8} THE SQUARE FOOTAGE OF THE ADDITION IS LISTED AS
 1,375 ON SHEET E2 AND F1, THE SQUARE FOOTAGE ON THE
 APPLICATION IS LISTED AS 750. CORRELATE SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-02 Cont ID  
Sent By btrobaug Date 2007-05-11 Time 09:58 Rev Time 0.50
Received By btrobaug Date 2007-05-11 Time 09:29 Sent To M
Notes
2007-05-11 09:58:03 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE VERIFY THE CONFIGURATION OF THE METER AND
 DISCONNECTS SHOWN. THEY WOULD APPEAR TO BE A
 METER/MAIN, RATHER THAN SEPARATE DISCONNECTS AS NOTED.
 CORRECT THE RISER.
  
 2} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3} PROVIDE A SITE PLAN INDICATING THE LOCATION OF ALL
 SERVICE EQUIPMENT SO THAT COMPLIANCE WITH ARTICLE 230
 CAN BE REVIEWED. THE "PROPOSED 100 AMP" PANEL MAY BE
 REQUIREED TO BE GROUNDED PER 250.32 AND HAVE A MAIN PER
 225.31, DEPENDING ON LOCATION.
  
 4 } 250.52(A)(3) CONCRETE-ENCASED ELECTRODE AN
 ELECTRODE ENCASED BY AT LEAST 50 MM (2 IN.) OF
 CONCRETE, LOCATED WITHIN AND NEAR THE BOTTOM OF A
 CONCRETE FOUNDATION OR FOOTING THAT IS IN DIRECT
 CONTACT WITH THE EARTH, CONSISTING OF AT LEAST 6.0 M
 (20 FT) OF ONE OR MORE BARE OR ZINC GALVANIZED OR OTHER
 ELECTRICALLY CONDUCTIVE COATED STEEL REINFORCING BARS
 OR RODS OF NOT LESS THAN 13 MM ( 1/ 2 IN.) IN DIAMETER,
 OR CONSISTING OF AT LEAST 6.0 M (20 FT) OF BARE COPPER
 CONDUCTOR NOT SMALLER THAN 4 AWG. REINFORCING BARS
 SHALL BE PERMITTED TO BE BONDED TOGETHER BY THE USUAL
 STEEL TIE WIRES OR OTHER EFFECTIVE MEANS. THIS IS
 AVAILABLE GIVEN A FOOTER IS BEING POURED. PLEASE ADD TO
 RISER.
  
 5} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG
 WITH OTHER INFORMATION REQUIRED BY 61G15-23.002
 FLORIDA ADMINISTRATIVE CODE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-12-22 Cont ID  
Sent By adarroug Date 2008-12-22 Time 10:25 Rev Time 0.00
Received By adarroug Date 2008-12-22 Time 10:25 Sent To E
Notes
2008-12-22 10:26:07TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-11-26 Cont ID  
Sent By adarroug Date 2008-11-26 Time 15:53 Rev Time 0.00
Received By adarroug Date 2008-11-26 Time 15:53 Sent To E
Notes
2008-11-26 15:53:53TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-06-10 Cont ID  
Sent By adarroug Date 2008-06-10 Time 13:48 Rev Time 0.00
Received By adarroug Date 2008-06-10 Time 13:48 Sent To B
Notes
2008-06-10 13:49:02TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-19 Cont ID  
Sent By adarroug Date 2008-05-19 Time 11:01 Rev Time 0.00
Received By adarroug Date 2008-05-19 Time 11:01 Sent To Z
Notes
2008-05-19 11:01:20TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-19 Cont ID  
Sent By adarroug Date 2008-05-19 Time 10:57 Rev Time 0.00
Received By adarroug Date 2008-05-19 Time 10:57 Sent To Z
Notes
2008-05-19 10:58:04TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-21 Cont ID  
Sent By adarroug Date 2008-02-21 Time 15:52 Rev Time 0.00
Received By adarroug Date 2008-02-21 Time 15:52 Sent To Z
Notes
2008-02-21 15:52:58TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-07 Cont ID  
Sent By adarroug Date 2007-05-07 Time 16:48 Rev Time 0.00
Received By adarroug Date 2007-05-07 Time 16:48 Sent To E
Notes
2007-05-07 16:48:25TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-06-12 Time   Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 14:32 Sent To  
Notes
2007-04-23 14:32:20TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-01-10 Cont ID  
Sent By rregueir Date 2009-01-10 Time 09:08 Rev Time 0.00
Received By rregueir Date 2009-01-10 Time 09:07 Sent To B
Notes
2009-01-10 09:08:23MECH PORTION OF E-CALCS OK PENDING BUILDING REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-12-14 Cont ID  
Sent By rregueir Date 2008-12-14 Time 13:52 Rev Time 0.00
Received By rregueir Date 2008-12-14 Time 13:50 Sent To PC
Notes
2008-12-14 13:52:18REVISED ENERGY AND COOLING LOAD CALCS WILL BE REVIEWED
 ONCE BUILDING REVIEW COMMENTS ARE ADDRESSED. PLEASE SEE
 SAMANTHA HILL'S REVIEW COMMENTS DATED 12/8/08.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-03-03 Cont ID  
Sent By tgordon Date 2008-03-03 Time 10:12 Rev Time 0.30
Received By tgordon Date 2008-03-03 Time 10:12 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-15 Cont ID  
Sent By btrobaug Date 2007-07-02 Time 16:44 Rev Time 0.30
Received By tgordon Date 2007-05-15 Time 08:40 Sent To P
Notes
2007-05-15 09:08:35*** DENIED ***
 1) INFORMATION MISSING FROM MECHANICAL (A/C) PLANS.
 (1) COMPANY NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) COMPANY LICENSE NUMBER (IF APPLICABLE)..
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB
 ADDRESS" SEE CITY WPB AMEND. 106.1.1).
  
 2) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 3) ENERGY CALCULATIONS ARE CALLING FOR A CONCRETE DECK
 ROOF, PLANS ARE CALLING FOR A RUBBERIZED FIBERGLASS
 ROOF AND A ASPHALT SHINGLE ROOF, PLEASE CORRECT ENERGY
 CALCULATIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-06-19 Cont ID  
Sent By mperson Date 2008-06-19 Time 14:13 Rev Time 0.00
Received By mperson Date 2008-06-19 Time 14:13 Sent To Z
Notes
2008-06-19 14:17:22****************PROVISO****************
 THE FOLLOWING IS REQUIRED FOR THE CLEANOUTS PER FBC -
 PLUMBING SECTIONS.
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A TWO-WAY
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-05-22 Cont ID  
Sent By mperson Date 2008-05-22 Time 10:50 Rev Time 0.00
Received By mperson Date 2008-05-22 Time 10:50 Sent To B
Notes
2008-05-22 11:04:32PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL FOLLOW THE PREVIOUS REVIEW COMMENTS.
 **NOTE: NO COMMENT RESPONSE FROM DESIGNER.
  
 1. SHEET D3, SANITARY ISOMETRIC RISER DOES NOT REFLECT
 THE FLOOR PLAN OF SHEET F1 AND IS NOT CODE COMPLIANT.
 PROVIDE THE FLAT PLAN SANITARY UNDERGROUND PLUMBING
 LAYOUT ON SHEET F1 AND REFLECT THAT ON THE RESUBMITTED
 SANITARY ISOMETRIC. PER FBC PLUMBING SECTION 701.1
 SCOPE.
  
 **THE RESUBMITTED SANITARY ISOMETRIC RISER DIAGRAM ON
 SHEET D-3 STILL DOES NOT REFLECT THE FLOOR PLAN OF
 SHEET F1. THE WASTE AND VENT PIPING FOR THE BATHTUB IS
 MISSING ON THE RESUBMITTED ISOMETRIC AND THE FLOOR
 PLAN. THE WASHING MACHINE AND BIDET DO NOT REFLECT THE
 FLOOR PLAN. PLEASE REFERENCE THE RED LINE CORRECTIONS
 ON SHEETS F1 AND D-3. PER FBC PLUMBING SECTION 701.1
 SCOPE.
  
 2. "OK" COMMENT ADDRESSED.
  
 3. "OK" COMMENT ADDRESSED.
  
 **THE FOLLOWING ARE NEW COMMENTS**
  
 4. SHEET D3 THE BIDET NEEDS A VENT. PER FBC-2004
 PLUMBING TABLE 906.1. THE MAXIMUM DISTANCE FOR 2 INCH
 TRAP FROM A VENT IS 6 FEET.
  
 5. SHEET D3 THE WATER CLOSET DOES NOT REQUIRE A TRAP
 DO TO THE FACT IT HAS AN INTEGRAL TRAP. A FIXTURE SHALL
 NOT BE DOUBLE TRAPPED. PER FBC-2004 PLUMBING SECTION
 1002.1 FIXTURE TRAPS.
  
 6. SHEET D3 THE RESUBMITTED SANITARY ISOMETRIC IS NOT
 SIZING ALL TRAPS. PER (W.P.B. AS AMENDED) SECTION
 106.3.5.4 RESIDENTIAL (9) PLUMBING.
  
 7. SHEET D3 THE RESUBMITTED SANITARY ISOMETRIC IS
 INCORRECTLY INDICATING CLEANOUT LOCATIONS OR NOT
 INDICATING THEM AT ALL PER THE FOLLOWING FBC-2004
 PLUMBING SECTIONS.
  
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK.
 **INCORRECTLY INDICATED ON PLANS.
  
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A TWO-WAY
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 **MISSING FROM PLANS
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM).
 NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE 3
 INCH.
 **MISSING FROM PLANS.
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE
 LOCATED 4' A.F.F.
 **MISSING FROM PLANS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-02-29 Cont ID  
Sent By mperson Date 2008-02-29 Time 15:59 Rev Time 0.00
Received By mperson Date 2008-02-29 Time 15:59 Sent To M
Notes
2008-02-29 16:13:41PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET D3, SANITARY ISOMETRIC RISER DOES NOT REFLECT
 THE FLOOR PLAN OF SHEET F1 AND IS NOT CODE COMPLIANT.
 PROVIDE THE FLAT PLAN SANITARY UNDERGROUND PLUMBING
 LAYOUT ON SHEET F1 AND REFLECT THAT ON THE RESUBMITTED
 SANITARY ISOMETRIC. PER FBC PLUMBING SECTION 701.1
 SCOPE.
  
 2. SHEET D3 SANITARY ISOMETRIC RISER DIAGRAM THE BAR
 SINK IS MISSING FROM THE RISER DIAGRAM. PER FBC
 PLUMBING SECTION 701.1 SCOPE.
  
 3. THE WASHING MACHINE CAN NOT DRAIN INTO THE WET
 VENTED BATHROOM GROUP. THE WASHING MACHINE MUST DRAIN
 DOWN STREAM OF THE BATHROOM GROUP. PER FBC PLUMBING
 SECTION 909.1 WET VENT PERMITTED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-05-17 Cont ID  
Sent By mperson Date 2007-05-17 Time 09:29 Rev Time 0.00
Received By mperson Date 2007-05-17 Time 09:29 Sent To B
Notes
2007-05-17 09:33:09NOTE: THERE IS NO PLUMBINGON THESE PLANS OR A
 PLUMBING PERMIT APPLIED FOR.

Review Stop Z ZONING
Rev No 4 Status P Date 2008-06-19 Cont ID  
Sent By choops Date 2008-06-19 Time 14:55 Rev Time 0.00
Received By choops Date 2008-06-19 Time 14:55 Sent To B
Notes
2008-06-19 14:55:57***APPROVED - RESUB #3 (RESTAMPED PLANS)***
  
 PROVISO:
 1)NO SEPARATE DWELLING UNIT PERMITTED WITHIN THE
 SINGLE FAMILY LOW DENSITY (SF7) ZONING DESIGNATION.
 PROPOSED ADDITION SHALL NOT BE USED AS A SEPARATE
 DWELLING UNIT.
  
 2)AS THE VALUE OF THE PROPOSED WORK HAS BEEN
 INCREASED AND NOW EXCEEDS 50% OF THE STRUCTURE'S VALUE,
 ALL LANDSCAPING SHALL BE BROUGHT TO COMPLIANCE WITH
 SECTION 94-442 AND 94-445 OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS:
  
 FOR SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE SHADE,
 FLOWERING OR FRUIT TREE SHALL BE PLANTED FOR EACH 1,200
 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF. FOR
 SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE SHRUB SHALL
 BE PLANTED FOR EACH 500 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF.
  
  
  
  
 SENT TO "B" - AM

Review Stop Z ZONING
Rev No 3 Status P Date 2008-05-21 Cont ID  
Sent By choops Date 2008-05-21 Time 11:18 Rev Time 0.00
Received By choops Date 2008-05-21 Time 11:18 Sent To E
Notes
2008-05-21 11:19:38***APPROVED - RESUB #2***
  
 PROVISO:
 1)NO SEPARATE DWELLING UNIT PERMITTED WITHIN THE
 SINGLE FAMILY LOW DENSITY (SF7) ZONING DESIGNATION.
 PROPOSED ADDITION SHALL NOT BE USED AS A DWELLING
 UNIT.
  
 2)AS THE VALUE OF THE PROPOSED WORK HAS BEEN
 INCREASED AND NOW EXCEEDS 50% OF THE STRUCTURE'S VALUE,
 ALL LANDSCAPING SHALL BE BROUGHT TO COMPLIANCE WITH
 SECTION 94-442 AND 94-445 OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS:
  
 FOR SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE SHADE,
 FLOWERING OR FRUIT TREE SHALL BE PLANTED FOR EACH 1,200
 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF. FOR
 SINGLE-FAMILY DWELLING UNITS, AT LEAST ONE SHRUB SHALL
 BE PLANTED FOR EACH 500 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF.
  
  
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status F Date 2008-02-25 Cont ID  
Sent By choops Date 2008-02-25 Time 09:56 Rev Time 0.00
Received By choops Date 2008-02-25 Time 09:56 Sent To E
Notes
2008-02-25 09:58:11***FAILED - RESUB #1 (CHANGED SCOPE OF WORK FROM FIRST
 REVIEW)***
  
  
 1)INDICATE SETBACK DIMENSIONS TO EASTERN PORTION OF
 REAR PROPERTY LINE (SEE ATTACHED SURVEY WITH REQUIRED
 SETBACKS DRAWN IN).MUST MAINTAIN A MINIMUM REAR
 SETBACK OF 11' TO THE EASTERN PORTION OF THE REAR
 PROPERTY LINE.
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
  
 NOTE:NO SEPARATE DWELLING UNIT PERMITTED WITHIN THE
 SINGLE FAMILY LOW DENSITY (SF7) ZONING DESIGNATION.
 PROPOSED ADDITION SHALL NOT BE USED AS A DWELLING
 UNIT.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-07 Cont ID  
Sent By choops Date 2007-05-07 Time 14:48 Rev Time 0.00
Received By choops Date 2007-05-07 Time 14:48 Sent To I
Notes
2007-05-07 14:52:18***FAILED***
  
  
 1)**CANNOT BUILD WITHIN AN EASEMENT**MUST GO
 THROUGH THE EASEMENT ABANDONMENT PROCESS IF YOU WISH TO
 CONTINUE WITH PROJECT.FOR INFORMATION REGARDING
 EASEMENT ABANDONMENT PLEASE CONTACT THE PLANNING DEPT.
 561-822-1435
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720