Plan Review Details - Permit 07040664
Plan Review Stops For Permit 07040664
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2007-06-06 Cont ID  
Sent By lursu Date 2007-06-06 Time 11:42 Rev Time 0.00
Received By lursu Date 2007-06-06 Time 11:42 Sent To  
Notes
2007-06-06 11:43:46PERMIT ASSIGNED TO THE CORRECT PCN = 74 42 43 24 30 000
 2040.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2007-06-04 Cont ID  
Sent By lursu Date 2007-06-04 Time 09:21 Rev Time 0.00
Received By lursu Date 2007-06-04 Time 09:21 Sent To  
Notes
2007-06-04 09:24:08PLEASE SPECIFY THE JOB LOCATION TO BE DONE IS ONLY AT
 UNIT 204 ( ON ONE APPLICATION) OR ALL UNITS INVOLVED
 201 THRU 204 ?ALSO IF THESE UNITS ARE COMBINED THE
 UNITY OF TITLE IS NEEDED.PLEASE THE PREVIOUS COMMENTS
 .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-04-24 Cont ID  
Sent By lursu Date 2007-04-24 Time 13:26 Rev Time 0.00
Received By lursu Date 2007-04-20 Time 15:16 Sent To  
Notes
2007-05-03 13:53:36 
  
 APPLICATION FORM MUST STATE INTENT TO CREATE A NEW UNIT
 (UNIT # 204).
  
 ALSO, PLAN STATES "BAY 203 THRU 203 EXISTING".SHOULD
 THIS BE "BAY 202 THRU 203 EXISTING"?.PLEASE CORRECT.
2007-04-24 13:29:37PROOF OF OWNERSHIP IS REQUIRED FOR ALL THESE THREE
 UNITS 201,202 & 203 INVOLVED IN THIS PERMIT.ALSO THE
 UNITY OF TITLE FOR THESE THREE UNITS MUST BE SUBMITTED
 .
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
2007-04-20 15:17:24COPY OF APPL. SENT TO LILI FOR INDIVIDUAL SUITES

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-06-06 Cont ID  
Sent By mjacobs Date 2007-06-06 Time 12:21 Rev Time 0.00
Received By mjacobs Date 2007-06-06 Time 12:17 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-06-03 Cont ID  
Sent By mjacobs Date 2007-06-03 Time 14:07 Rev Time 0.00
Received By mjacobs Date 2007-06-03 Time 13:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-02 Cont ID  
Sent By mjacobs Date 2007-05-02 Time 18:20 Rev Time 0.00
Received By mjacobs Date 2007-05-02 Time 17:11 Sent To  
Notes
2007-05-02 18:20:19BUILDING PLAN REVIEW
 PERMIT: 07040664
 ADD: 4047- OKEECHOBEE BLVD. 201-202-203
 CONT: JBS CONSTRUCTION INC.
 TEL: (561)575-1977
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)11-4.17.3 EXCEPTION(1)THE NEW TOILET STALLSHALL
 SHOW THE CLEAR FLOOR SPACE AS SHOWN IN FIG. 30A AND
 FIG. 30E.
  
 2)11-4.17.2WATER CLOSETS IN ACCESSIBLE STALLS SHALL
 COMPLY WITH SECTION 11-4.16.
  
 3)INDICATE ON THE DRAWINGS WHAT TYPE OF BACKING WILL
 BE USED FOR THE GRAB BARS, ANDWILL ALSO MEET THE
 REQUIREMENTS OF SECTION 11-4.26.3.
  
 4)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-03 Cont ID  
Sent By dpalmer Date 2007-06-03 Time 12:40 Rev Time 0.00
Received By dpalmer Date 2007-06-03 Time 12:28 Sent To  
Notes
2007-06-03 12:42:17REDLINED PLANS.
  
 AS PREVIOULSY NOTED, CIRCUITING FOR EM/EXT LTS ARE TO
 BE PER 700.12F TO LOCAL LIGHTING CIRCUIT. THIS IS TO BE
 VERIFIED.
 ELECTRICAL ONLY PERTAINS TO BATH ROOM ONLY. PLANS
 CLEARLY STATE NO OTHER ELECTRICAL WORK IS BEING DONE
 AND THAT ALL ELECTRICAL FROM EACH BAY IS ALREADY
 SEPARATED TO EACH PANEL AND NO CIRCUITS CROSS OVER.
  
 ** SUITE TO BE VERIFIED, AS APPLIED, IS SWHON FOR 201,
 WHEN PLANS SHOW 204.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-27 Cont ID  
Sent By dpalmer Date 2007-04-27 Time 11:11 Rev Time 0.00
Received By dpalmer Date 2007-04-27 Time 10:44 Sent To  
Notes
2007-04-27 11:11:35** UNSAT **
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 1) NOTE: PLEASE SEE MISSING CIRCUITING FOR NEW
 ELECTRICAL WHICH IS TO BE SHOWN. PLEASE CORRELATE WITH
 A PANEL SCHEDULE TO BE SUBMITTED. PLEASE SHOW ON PLANS
 HOW CIRCUITING IS BEING SEPARATED FROM THE SPACES AND
 PLEASE INDICATE CIRCUITING FOR EM/EXT LTS 700.12E.
 PLEASE INCLUDE CONDUCTOR SIZES ALONG WITH OVER CURRENT
 PROTECTION DEVICES.
 FBC 106.3.5.1.2
 408.4, 310.16, 240.4
  
 2) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 3) NOTE: PLEASE INDICATE LIGHTING FOR NEW BATHROOM.
 LS 101,7.8
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-06-05 Cont ID  
Sent By mawillia Date 2007-06-05 Time 11:10 Rev Time 0.00
Received By mawillia Date 2007-05-30 Time 14:55 Sent To  
Notes
2007-05-30 15:05:37*****PROVISO*****
  
 **CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITY NFPA 241.
  
 **CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY ACCESS TO THE PROPERTY OR VICINITY
 THEROF (INCLUDING FIRE LANES).
  
 **COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 **MAINTAIN ALL EXIT COMPONENTS.
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-05-03 Cont ID  
Sent By mawillia Date 2007-05-03 Time 14:49 Rev Time 0.00
Received By mawillia Date 2007-05-03 Time 13:04 Sent To  
Notes
2007-05-03 13:21:11*****DENIED*****
  
  
 1.THE APPROPIATE SUITE NUMBER(S) SHALL BE INCLUDED
 WITH THE ADDRESS LOCATED IN THE TITLE OF BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITY NFPA 241.
  
 3.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY ACCESS TO THE PROPERTY OR VICINITY
 THEROF (INCLUDING FIRE LANES).
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.MAINTAIN ALL EXIT COMPONENTS.
  
 6..THE PLANS DO NOT INDICATE IF THE BUILDING IS FIRE
 SPRINKLERED,IF SO, SEPARTE PLANS AND PERMIT WILL BE
 REQUIRED IF THE SCOPE OF WORK CAUSES THE FIRE SPRINKLER
 HEADS/DEVICES TO BE ALTERED OR MODIFIED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-17 Cont ID  
Sent By adarroug Date 2007-05-17 Time 13:39 Rev Time 0.00
Received By adarroug Date 2007-05-17 Time 13:39 Sent To  
Notes
2007-05-29 14:01:32TO "BOB"#1
2007-05-17 13:40:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-03 Cont ID  
Sent By mawillia Date 2007-05-03 Time 13:04 Rev Time 0.00
Received By mawillia Date 2007-04-20 Time 15:03 Sent To  
Notes
2007-04-20 15:16:07TO "BOB"#14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-05-29 Cont ID  
Sent By tgordon Date 2007-05-29 Time 15:35 Rev Time 0.20
Received By tgordon Date 2007-05-29 Time 15:35 Sent To  
Notes
2007-05-29 15:36:12BATHROOM EXHAUST FAN ONLY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-25 Cont ID  
Sent By tgordon Date 2007-04-25 Time 11:47 Rev Time 0.30
Received By tgordon Date 2007-04-25 Time 11:46 Sent To  
Notes
2007-04-25 12:00:37*** DENIED ***
 1) TWO DIFFERENT PLANS WERE SUBMITTED, ONE SHOWS ONE
 H.C. BATHROOM THE OTHER SHOWS THREE H.C. BATHROOMS. IS
 THIS A BEFORE AND AFTER? IF SO PLEASE STATE SO ON
 PLANS.
  
 2) AN EXHAUST FAN IS REQUIRED IN THE BATHROOMS, PLEASE
 SHOW ON PLANS, SEE 2004 FBC/M 403.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-06-04 Cont ID  
Sent By jleech Date 2007-06-04 Time 07:32 Rev Time 0.00
Received By jleech Date 2007-06-04 Time 07:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-05-01 Cont ID  
Sent By jleech Date 2007-05-01 Time 07:55 Rev Time 0.00
Received By jleech Date 2007-05-01 Time 07:55 Sent To  
Notes
2007-05-30 15:24:29*****PROVISO*****
  
 PLAN SHEET STAMPED, INITIALED, AND DATED WITH THE
 FOLLOWING:
  
  
  
 **CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITY NFPA 241.
  
 **CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR
 HINDER EMERGENCY ACCESS TO THE PROPERTY OR VICINITY
 THEROF (INCLUDING FIRE LANES).
  
 ** COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 ** MAINTAIN ALL EXIT COMPONENTS.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722