Plan Review Details - Permit 07040635
Plan Review Stops For Permit 07040635
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-11 Cont ID  
Sent By adarroug Date 2007-05-11 Time 11:12 Rev Time 0.00
Received By adarroug Date 2007-05-11 Time 11:12 Sent To M
Notes
2007-05-11 11:12:22TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-23 Cont ID  
Sent By tgordon Date 2007-04-23 Time 09:41 Rev Time 0.00
Received By tgordon Date 2007-04-20 Time 11:37 Sent To  
Notes
2007-04-20 11:37:52TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-05-11 Cont ID  
Sent By tgordon Date 2007-05-11 Time 14:39 Rev Time 0.25
Received By tgordon Date 2007-05-11 Time 14:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-23 Cont ID  
Sent By tgordon Date 2007-04-23 Time 09:20 Rev Time 0.45
Received By tgordon Date 2007-04-23 Time 09:20 Sent To  
Notes
2007-04-23 09:37:52*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, SEE 2004 FBC 13-600.3.ABC.2.
  
 2) SHOW ON PLANS TOTAL AND SENSIBLE BTU'S. OF COOLING
 EQUIPMENT.
  
 3) BUILDING PLANS ON FILE SHOW 8 FOOT HIGH CEILINGS,
 COOLING LOAD CALCULATIONS SUBMITTED SHOW 10 FOOT HIGH
 CEILINGS, PLEASE CORRECT COOLING LOAD CAL'S.
  
 4) BUILDING PLANS ON FILE SHOW A POCKET DOOR BETWEEN
 THE FAMILY ROOM AND THE MASTER SUITE ( M.BED, M.BATH,
 M.CLOSET) THEIR FOR THE 12" RETURN AIR TRANSFER DUCT
 FROM THE MASTER BEDROOM TO THE FAMILY ROOM NEEDS TO BE
 16", SEE 2004 FBC/R M1602.4 (C) EXCEPT, PLEASE
 CORRECT.
  
 5) THE 8" RETURN AIR TRANSFER DUCT FROM BEDROOM #3 TO
 THE HALL NEEDS TO BE 10", SEE 2004 FBC/R M1602.4 (A),
 PLEASE CORRECT.
  
 *** 2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.