| Plan Review Stops For Permit 07040618 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-07-09 |
|
|
Cont ID |
|
| Sent By |
kconrad |
Date |
2007-07-09 |
Time |
17:31 |
Rev Time |
0.00 |
| Received By |
kconrad |
Date |
2007-07-09 |
Time |
15:53 |
Sent To |
I |
|
| Notes |
| 2007-07-09 17:25:33 | PROJECT: 1700 PALM BEACH LAKES BLVD. / 6TH FLOOR | | | | | | PROJECT DETAIL: REVISIONS FOR PHASED INTEROR DEMOLITION | | | ONLY /SHEET 3/A-210 | | | | | | PLAN REVIEW: 2004 FLORIDA BUILDING CODE (EXISTING) WITH | | | 2006 REVISIONS | | | | | | STATUS: APPROVED | | | | | | | | | COMMENTS: | | | | | | 1) THE PROPOSED WORK IS FOR PHASED INTERIOR DEMOLITION | | | ONLY. | | | | | | 2)SAFETY REQUIREMENTS MUST BE MAINTAINED AS PER | | | FEBC, SECTION 1302: | | | | | | SECTION 1302 | | | CONSTRUCTION SAFEGUARDS | | | 1302.1REMODELING AND ADDITIONS. | | | REQUIRED EXITS, EXISTING STRUCTURAL ELEMENTS, FIRE | | | PROTECTION DEVICES AND SANITARY SAFEGUARDS SHALL BE | | | MAINTAINED AT ALL TIMES DURING REMODELING, ALTERATIONS, | | | REPAIRS OR ADDITIONS TO ANY BUILDING OR STRUCTURE. | | | EXCEPTIONS: | | | 1. WHEN SUCH REQUIRED ELEMENTS OR DEVICES ARE BEING | | | REMODELED, ALTERED OR REPAIRED, ADEQUATE SUBSTITUTE | | | PROVISIONS SHALL BE MADE. | | | 2. WHEN THE EXISTING BUILDING IS NOT OCCUPIED. 1302.2 | | | MANNER OF REMOVAL. | | | WASTE MATERIALS SHALL BE REMOVED IN A MANNER WHICH | | | PREVENTS INJURY OR DAMAGE TO PERSONS, ADJOINING | | | PROPERTIES AND PUBLIC RIGHTS-OF-WAY. | | | | | | | | | 3)PLEASE CONTACT MR. ALEX ORTEGAWITH THE DEP PRIOR | | | TO DEMOLIITON AT 355-3023, EXT. 1148. AN APPROVAL FROM | | | THIS AGENCY MUST BE OBTAINED AS PER THE FOLLOWING: | | | | | | 105.9 ASBESTOS. | | | THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT | | | FOR THE DEMOLITION OR RENOVATION OF AN EXISTING | | | STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT | | | WHICH INDICATES THE OWNER?S OR OPERATOR?S | | | RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION | | | 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT | | | OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO | | | REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH | | | STATE AND FEDERAL LAW. | | | | | | 4) OBTAIN SEPARATE ELECTRICAL AND PLUMBING PERMITS IF | | | APPLICABLE. | | | | | | PLAN REVIEW: KEN CONRAD | | | PHONE: 561.805.6666 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-06-22 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-22 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-22 |
Time |
13:33 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-06-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-03 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-03 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2007-06-03 10:12:51 | | | | BUILDING PLAN REVIEW | | | PERMIT: | | | ADD: | | | CONT: | | | TEL: (561)###-#### | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 2ND | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FBC SEC.106.FLORIDA STATUTES 481.221(3)EACH | | | REGISTERED INTERIOR DESIGNER SHALL OBTAIN A SEAL AS | | | PRESCRIBED BY THE BOARD, AND ALL DRAWINGS, PLANS, | | | SPECIFICATIONS, OR REPORTS PREPARED OR ISSUED BY THE | | | REGISTERED INTERIOR DESIGNER AND BEING FILED FOR PUBLIC | | | RECORD SHALL BEAR THE SIGNATURE AND SEAL OF THE | | | REGISTERED INTERIOR DESIGNER WHO PREPARED OR APPROVED | | | THE DOCUMENT AND THE DATE ON WHICH THEY WERE SEALED. | | | THE SIGNATURE, DATE AND SEAL SHALL BE EVIDENCE OF THE | | | AUTHENTICITY OF THAT TO WHICH THEY ARE AFFIXED. THE | | | CERTIFICATE OF AUTHORIZATION NUMBER FOR A E S | | | INTERIORS ASSOCIATES INC SHALL ALSO BE INDICATED. SHEET | | | ID-1 IS MISSING THIS INFORMATION SEE PREVIOUS NOTE IN | | | RREFERENCE TO TITLE BLOCK. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-04-24 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-24 |
Time |
12:02 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-24 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2007-04-24 12:01:43 | BUILDING PLAN REVIEW | | | PERMIT: 07040618 | | | ADD: 1700 PBL BLVD. | | | CONT: ANDERSON MOORE CONST. | | | TEL: (561)753-7400 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 1ST. | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)61G1-16.004 TITLE BLOCK. | | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | | (2) FIRM LICENSE NUMBER. | | | (3) NAME OR IDENTIFICATION OF PROJECT. | | | (4) DATE PREPARED. | | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | | THE DOCUMENT. | | | THE INFORMATION ON THE ARCHITECT'S SEAL IS NOT | | | LEGIGLE. | | | | | | 3)FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT. | | | NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE | | | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: | | | 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT | | | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-06-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-06-18 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-06-18 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2007-06-18 09:03:44 | STAMPED ELECTRICAL PLANS. | | | INFORMATION ADDED TO TITLE BLOCKS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-06-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-06-03 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-06-03 |
Time |
12:10 |
Sent To |
PC |
|
| Notes |
| 2007-06-03 12:21:50 | ** UNSAT 2ND REVIEW ** | | | | | | 1) NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS REVIEW. TITLE | | | BLOCKS ARE STILL MISSING THE REQUIRED INFORMATION FOR | | | ARCHITECT, ARCHITECTURAL FIRM. | | | THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES | | | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. PLEASE | | | ALSO SEE THE ARCHITECT SEEMS TO HAVE SIGNED THE | | | ELECTRICAL SHEETS WHICH ARE SIGNED, DATED AND SEALED BY | | | THE ENGINEER OF RECORD. IF THE ENGINEER IS THE | | | REPSONSIBLE DESIGNER OF RECORD, THE ARCHITECT SHOULD | | | NOT BE SIGNING THESE SHEETS. | | | FAC 61G1-16.004, FS 481.219 | | | | | | ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH MAY | | | AFFECTPLANS. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-04-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-04-27 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-04-27 |
Time |
12:01 |
Sent To |
|
|
| Notes |
| 2007-04-27 12:19:02 | ** UNSAT ** | | | | | | ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1 | | | ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF | | | WEST PALM BEACH. | | | | | | | | | 1) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS | | | FOR ARCHITECTURAL FIRM AS REQUIRED PER FAC 61G1-16.004, | | | FS 481.219. | | | *PLEASE ALSO SEE THE SEAL ON ARCHITECTURAL SHEETS ARE | | | VERY FAINT AND INFORMATION ON SAID SEALS IS NOT EASILY | | | READ OR VISIBLE. | | | PLEASE SEE FAC 61G1-16 | | | | | | 2) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH | | | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS | | | UNDER THE NEW CODES ADOPTED BY THE STATE. | | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | | AFFECT DESIGNS FOR ALL TRADES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | | REVIEWER AT A MINIMUM. | | | 2004 FBC W/ 2006 REVISIONS | | | 2005 NFPA-70 | | | 2002 NFPA-72 | | | 2003 NFPA-101 | | | PLEASE SEE THE LS CODE SHOWN IS NOT YET ADOPTED. | | | | | | 3) NOTE: PLEASE SEE THE LIGHTING CONTROLS BEING | | | REPLACED WILL BE REQUIRED TO COMPLY WITH THE FBC | | | CHAPTER 13. 13-415.1.ABC.1.1. | | | PLEASE ADJUST TYPES OF DEVICES AND SYMBOL LEGEND. | | | 13-101.0 | | | | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-06-21 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-06-21 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-06-21 |
Time |
14:33 |
Sent To |
|
|
| Notes |
| 2007-06-21 14:43:17 | *****PROVISO***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ADDRESSED, HOWEVER THE APPROPIATE PLAN SHEET(S) TO | | | BE FIRE-STAMPED WHEN ALL REVIEWERS HAVE BEEN | | | SATISFIED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-05-30 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-05-30 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-05-30 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2007-05-30 09:59:16 | *****DENIED***** | | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD | | | COMMENT TO SHEET A-210 | | | | | | 5.ON SHEET ID-1, SPECIFY THE INTERIOR FINISH | | | CLASSIFICATION FOR THE WALLS AND CEILINGS.AS PER NFPA | | | 101, THE WALL AND CEILING FINISHES SHALL BE CLASS A OR | | | CLASS B IN EXITS AND EXIT CORRIDORS AND CLASS A, CLASS | | | B, OR CLASS C IN ALL OTHER AREAS.BE SPECIFIC | | | | | | NEW COMMENT | | | | | | 1.SHEET ID-1 SHALL BE SIGNED AND SEALED SINCE IT | | | CONTAINS CODE COMPLIANCE INFORMATION. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-04-30 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-04-30 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-04-30 |
Time |
12:37 |
Sent To |
|
|
| Notes |
| 2007-04-30 12:52:06 | *****DENIED***** | | | | | | | | | 1.ONTHE TITLE SHEET UNDER LIFE SAFETY CODE, MAKE | | | REFERENCE TO THE 2003 EDITION OF NFPA 101. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 4.ALL REQUIRED EXIT COMPONENTS SHALL BE MAINTAINED. | | | THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF NEW | | | BUILDING SUPPLIES & MATERIALS SHALL NOT INTERFERE OR | | | HINDER EGRESS TO OR EXIT FROM THE 6TH FLOOR OR ANY | | | OTHER FLOOR IN THE BUILDING. | | | | | | 5.ON SHEET ID-1, SPECIFY THE INTERIOR FINISH | | | CLASSIFICATION FOR THE WALLS AND CEILINGS.AS PER NFPA | | | 101, THE WALL AND CEILING FINISHES SHALL BE CLASS A OR | | | CLASS B IN EXITS AND EXIT CORRIDORS AND CLASS A, CLASS | | | B, OR CLASS C IN ALL OTHER AREAS. | | | | | | 6. SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | | FIRE SPRINKLER REMODEL. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HO/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-06-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-13 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-13 |
Time |
16:18 |
Sent To |
|
|
| Notes |
| 2007-06-14 14:31:35 | TO "BOB"#8 | | 2007-06-13 16:18:33 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-05-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-18 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-18 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2007-05-29 14:19:21 | TO "BOB"#17 | | 2007-05-18 14:31:42 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-04-30 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-04-30 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-04-19 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2007-04-19 11:47:29 | TO "BOB"#7 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-06-25 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-06-25 |
Time |
13:50 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-06-25 |
Time |
13:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-06-15 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-06-15 |
Time |
11:31 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-06-15 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2007-06-15 11:36:11 | *** DENIED *** | | | 1) NO NEW MECHANICAL PLANS SUBMITTED AND ONLY ONE COPY | | | OF THE PREVIOUSLY APPROVED MECHANICAL PLAN WAS | | | SUBMITTED. NEED TO SUBMIT TWO COPY'S OF THE MECHANICAL | | | PLANS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2007-04-25 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-04-25 |
Time |
09:25 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-04-25 |
Time |
09:25 |
Sent To |
|
|
| Notes |
|
|