Plan Review Details - Permit 07040606
Plan Review Stops For Permit 07040606
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-12 Cont ID  
Sent By amorse Date 2007-05-12 Time 10:38 Rev Time 0.00
Received By amorse Date 2007-05-12 Time 10:38 Sent To PC
Notes
2007-05-12 10:52:29 
  
 DENIED
  
 1)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES,
 AND THE PRODUCT NOA THAT LISTS THE SYSTEM COMPONENTS/
 FASTENER LIST PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE GENERAL LIMITATIONS
 PAGE. ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG.
 ****PLEASE NOTE THAT THE NOA SUBMITTED DOES NOT INCLUDE
 THE DOORS THEY ARE UNDER SEPARATE NOA.****
  
 2)PROVIDE 2 COPIES OF LAYOUT AND INCLUDE THE WIDTH OF
 EACH UNIT BETWEEN MULLIONS IN ORDER TO ESTABLISH DESIGN
 PRESSURE.
  
 3)DESIGN PRESSURE IN THE 2004 FBC HAVE BEEN UPDATED
 WITH THE 2006 AMENDMENTS, ANY BUILDING IN A NORMALLY
 EXPOSURE BCATEGORY THAT HAS OPEN TERRAIN (INCLUDES
 BODIES OF WATER) IN ANY QUADRANT FOR A DISTANCE OF 600
 FT WILL BE CONSIDERED EXPOSURE C.
  
 4)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT IS
 REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-05-12 Time   Rev Time 0.00
Received By adarroug Date 2007-04-19 Time 10:28 Sent To  
Notes
2007-04-19 10:28:55TO "MISC" BOX#1