Plan Review Details - Permit 07040578
Plan Review Stops For Permit 07040578
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-09-05 Cont ID  
Sent By rmcdouga Date 2007-09-05 Time 15:16 Rev Time 0.00
Received By rmcdouga Date 2007-09-05 Time 15:16 Sent To  
Notes
2007-09-05 15:37:43TRUSS DRAWING SUBMITTAL
  
 DENIED BY BUILDING
  
 1) THE TRUSS DRAWING COVERSHEET REFERENCES THE 2001 FBC
 AND THE CORRECT CODE IS THE 2004 FBC.
  
 2) THE DESIGNER (ARCHITECT) OF RECORD FOR THE STRUCTURE
 CAN NOT SIGN AND SEAL THE TRUSS LAYOUT OR TRUSS
 DRAWINGS AS THE DESIGN OF THESE ARE THE RESPONSIBLITY
 OF THE TRUSS ENGINEER.THE DESIGNER OF RECORD IS ONLY
 REQUIRED TO REVIEW THE LAYOUT AND DRAWINGS FOR
 CONFORMANCE TO HIS DESIGN FOR THE STRUCTURAL LOADS. HE
 IS REQUIRED TO APPROVE IT OR SPECIFY CHANGES IN
 WRITING.A SHOP DRAWING REVIEW STAMP INITIALED BY THE
 DESIGNER OF RECORD IS ALL THAT IS REQUIRED.
  
 3) THE TRUSS DRAWINGS ARE NOT REQUIRED TO BE SUBMITTED
 FOR REVIEW FOR ONE AND TWO FAMILY STRUCTURES AND CAN BE
 GIVEN TO THE FIELD INSPECTOR AT TIME OF ROOF FRAMING
 INSPECTION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-29 Cont ID  
Sent By rmcdouga Date 2007-08-29 Time 17:08 Rev Time 0.00
Received By rmcdouga Date 2007-08-29 Time 17:08 Sent To  
Notes
2007-08-29 17:11:31LETTER FROM DESIGNER REVISING THE EXTERIOR WALL
 SHEATHING FROM 5/8 " OSB TO 1/2" CDX PLYWOOD IS OK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-07-10 Cont ID  
Sent By rmcdouga Date 2007-07-10 Time 10:48 Rev Time 0.00
Received By rmcdouga Date 2007-07-10 Time 10:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-01 Cont ID  
Sent By rmcdouga Date 2007-05-01 Time 11:03 Rev Time 0.00
Received By rmcdouga Date 2007-05-01 Time 06:36 Sent To  
Notes
2007-05-01 11:00:50DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PLANS ARE MISSING TITLE BLOCK INFORMATION
 REQUIRED BY FAC 61G1-16.004. THE ARCHITECT'S BUSINESS
 TELEPHONE NUMBER IS REQUIRED AND THE NAME OR
 IDENTIFICATION OF THE PROJECT IS NOT ADEQUATE. THE
 ADDRESS SHOULD BE INCLUDED IN THE IDENTIFICATION.
  
 3)INDICATE THE DISTANCE TO ADJACENT STRUCTURES. SHOW
 COMPLIANCE WITH R302.1 EXTERIOR WALLS.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL.
 EXCEPTION : DETACHED GARAGES ACCESSORY TO A DWELLING
 LOCATED WITHIN 2 FEET (610 MM) OF A LOT LINE SHALL BE
 PERMITTED TO HAVE ROOF EAVE PROJECTIONS NOT EXCEEDING 4
 INCHES (102 MM).
 PROJECTIONS EXTENDING INTO THE 6-FOOT (1829 MM)
 SEPARATION DISTANCE SHALL HAVE NOT LESS THAN 1-HOUR
 FIRE-RESISTIVE CONSTRUCTION ON THE UNDERSIDE. THE ABOVE
 PROVISIONS SHALL NOT APPLY TO WALLS WHICH ARE
 PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM
 WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING
 AND PARALLEL TO THE PROPERTY LINE.
 EXCEPTION: TOOL AND STORAGE SHEDS, PLAYHOUSES AND
 SIMILAR STRUCTURES ARE NOT REQUIRED TO PROVIDE WALL
 PROTECTION BASED ON LOCATION ON THE LOT.
  
 4) R302.2 OPENINGS.
 OPENINGS SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF
 A DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM
 AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET
 (1828 MM). THIS DISTANCE SHALL BE MEASURED
 PERPENDICULAR TO THE LINE USED TO DETERMINE THE
 SEPARATION DISTANCE.
 EXCEPTIONS:
 1.OPENINGS SHALL BE PERMITTED IN WALLS THAT ARE
 PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM
 WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING
 AND PARALLEL TO THE PROPERTY LINE.
 2.FOUNDATION VENTS INSTALLED IN COMPLIANCE WITH
 THIS CODE ARE PERMITTED.
  
 5) SUBMIT PRODUCT APPROVALS FOR THE OVERHEAD GARAGE
 DOOR, THE OUTSWING GARAGE DOOR, THE ROOF SHINGLES, THE
 TRUSS CONNECTORS, THE HARDIPLANK SIDING AND THE
 CUPOLA.
 IF THE CUPOLA IS TO BE CONSTRUCTED ON SITE, PROVIDE A
 STRUCTURAL DETAIL. SPECIFY THE MATERIALS, CONNECTORS
 AND THE ATTACHMENT TO THE GARAGE ROOF TRUSSES.
  
 6)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 7)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 8) ON SHEET 3 SPECIFY THE BUILDING DESIGN AS ENCLOSED
 OR OPEN.
  
 9) ON SHEET 3 THE INTERNAL PRESSURE COEFFICIENT IS
 POSITIVE OR NEGATIVE (+ OR -) 0.18.
  
 10) SPECIFY THE BASIC WIND SPEED UNDER DESIGN
 PARAMETERS ON SHEET 3.
  
 11) THE GARAGE DOES NOT HAVE ANY WINDOWS. PLEASE REMOVE
 THE WINDOW BUCK DETAIL ON SHEET 3.
  
 12) SPECIFY THE NUMBER OF HEADER STUDS SUPPORTING THE
 HEADER (2) AND THE NUMBER OF FULL LENGTH STUDS (3)
 REQUIRED AT EACH END OF THE 10' GARAGE DOOR HEADER. SEE
 IBHS GUIDELINES FOR HURRICANE RESISTANT CONSTRUCTION.
 R301.2.1.1.
  
 13) SHOW COMPLIANCE WITH R704 INSPECTION FOR TERMITES.
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES.
  
 14) SPECIFY THE NAIL SIZE NUMBER FOR THE DOOR BUCK
 FASTENERS ON THE DETAIL ON SHEET 3. CHECK THE FASTENER
 DIAMETER THAT WAS SPECIFIED, .0126 APPEARS TO BE
 INCORRECT.
  
 15) REVISE ROOF SHEATHING FASTENING SPECIFIED ON SHEET
 3 TO 8D RING SHANK NAILS AS REQUIRED BY R803.2.3.1 OF
 THE 2006 AMENDMENTS TO THE FBC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-20 Cont ID  
Sent By btrobaug Date 2007-06-20 Time 07:20 Rev Time 0.00
Received By btrobaug Date 2007-06-20 Time 07:02 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-27 Cont ID  
Sent By btrobaug Date 2007-04-27 Time 08:04 Rev Time 0.50
Received By btrobaug Date 2007-04-27 Time 07:53 Sent To B
Notes
2007-04-27 08:04:24 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} INDICATE DISCONNECTING MEANS PER 225.31, LOCATION
 225.32 AND GROUNDING PER 250.32.
  
 2} SHEET 4 SHOWS A RISER DIAGRAM. INDICATE IF PART OF
 THIS APPLICATION IS FOR NEW SERVICE EQUUIPMENT.
  
 3} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 4} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS."
  
 5} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 AFTER SUBMITTING THE ABOVE FOR REVIEW THERE MAY BE
 OTHER COMMENTS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-31 Cont ID  
Sent By adarroug Date 2007-08-31 Time 12:30 Rev Time 0.00
Received By adarroug Date 2007-08-31 Time 12:30 Sent To B
Notes
2007-08-31 12:30:53TO "RMCDOUGAL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-19 Cont ID  
Sent By adarroug Date 2007-06-19 Time 09:30 Rev Time 0.00
Received By adarroug Date 2007-06-19 Time 09:30 Sent To E
Notes
2007-06-19 09:30:37TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-07 Cont ID  
Sent By adarroug Date 2007-06-07 Time 16:35 Rev Time 0.00
Received By adarroug Date 2007-06-07 Time 16:35 Sent To Z
Notes
2007-06-07 16:43:11TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-26 Cont ID  
Sent By adarroug Date 2007-04-26 Time 08:58 Rev Time 0.00
Received By adarroug Date 2007-04-26 Time 08:58 Sent To E
Notes
2007-04-26 08:58:51TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-01 Cont ID  
Sent By rmcdouga Date 2007-05-01 Time 11:03 Rev Time 0.00
Received By rmcdouga Date 2007-04-18 Time 16:30 Sent To  
Notes
2007-04-18 16:31:09TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2007-06-19 Cont ID  
Sent By jroach Date 2007-06-19 Time 09:12 Rev Time 0.00
Received By jroach Date 2007-06-19 Time 09:12 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-25 Cont ID  
Sent By jroach Date 2007-04-25 Time 17:44 Rev Time 0.00
Received By jroach Date 2007-04-25 Time 17:44 Sent To I
Notes
2007-04-25 17:49:11***FAILED***
  
 1) DIMENSIONS OF THE PROPOSED DRIVEWAY SHALL BE
 PROVIDED.
  
 2) THE HEIGHT OF THE NEW GARAGE SHALL BE PROVIDED.
 HEIGHT SHALL BE MEASURED FROM GRADE TO THE MEAN POINT
 OF THE ROOF PITCH.AN ADDITIONAL MEASUREMENT SHALL BE
 PROVIDED FROM GRADE TO THE TOP OF THE DECORATIVE
 CUPOLA.
  
 3) PLEASE PROVIDE THE DISTANCE SEPARATION BETWEEN THE
 RESIDENCE AND THE DETACHED GARAGE.IT SHALL BE A
 MINIMUM OF SIX (6) FEET.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.