| 2007-05-01 11:00:50 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE PLANS ARE MISSING TITLE BLOCK INFORMATION |
| | REQUIRED BY FAC 61G1-16.004. THE ARCHITECT'S BUSINESS |
| | TELEPHONE NUMBER IS REQUIRED AND THE NAME OR |
| | IDENTIFICATION OF THE PROJECT IS NOT ADEQUATE. THE |
| | ADDRESS SHOULD BE INCLUDED IN THE IDENTIFICATION. |
| | |
| | 3)INDICATE THE DISTANCE TO ADJACENT STRUCTURES. SHOW |
| | COMPLIANCE WITH R302.1 EXTERIOR WALLS. |
| | EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) |
| | SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE |
| | RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL |
| | NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM |
| | AN ADJACENT PROJECTION OR WALL. |
| | EXCEPTION : DETACHED GARAGES ACCESSORY TO A DWELLING |
| | LOCATED WITHIN 2 FEET (610 MM) OF A LOT LINE SHALL BE |
| | PERMITTED TO HAVE ROOF EAVE PROJECTIONS NOT EXCEEDING 4 |
| | INCHES (102 MM). |
| | PROJECTIONS EXTENDING INTO THE 6-FOOT (1829 MM) |
| | SEPARATION DISTANCE SHALL HAVE NOT LESS THAN 1-HOUR |
| | FIRE-RESISTIVE CONSTRUCTION ON THE UNDERSIDE. THE ABOVE |
| | PROVISIONS SHALL NOT APPLY TO WALLS WHICH ARE |
| | PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM |
| | WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING |
| | AND PARALLEL TO THE PROPERTY LINE. |
| | EXCEPTION: TOOL AND STORAGE SHEDS, PLAYHOUSES AND |
| | SIMILAR STRUCTURES ARE NOT REQUIRED TO PROVIDE WALL |
| | PROTECTION BASED ON LOCATION ON THE LOT. |
| | |
| | 4) R302.2 OPENINGS. |
| | OPENINGS SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF |
| | A DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM |
| | AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET |
| | (1828 MM). THIS DISTANCE SHALL BE MEASURED |
| | PERPENDICULAR TO THE LINE USED TO DETERMINE THE |
| | SEPARATION DISTANCE. |
| | EXCEPTIONS: |
| | 1.OPENINGS SHALL BE PERMITTED IN WALLS THAT ARE |
| | PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM |
| | WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING |
| | AND PARALLEL TO THE PROPERTY LINE. |
| | 2.FOUNDATION VENTS INSTALLED IN COMPLIANCE WITH |
| | THIS CODE ARE PERMITTED. |
| | |
| | 5) SUBMIT PRODUCT APPROVALS FOR THE OVERHEAD GARAGE |
| | DOOR, THE OUTSWING GARAGE DOOR, THE ROOF SHINGLES, THE |
| | TRUSS CONNECTORS, THE HARDIPLANK SIDING AND THE |
| | CUPOLA. |
| | IF THE CUPOLA IS TO BE CONSTRUCTED ON SITE, PROVIDE A |
| | STRUCTURAL DETAIL. SPECIFY THE MATERIALS, CONNECTORS |
| | AND THE ATTACHMENT TO THE GARAGE ROOF TRUSSES. |
| | |
| | 6)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. |
| | |
| | 7)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 8) ON SHEET 3 SPECIFY THE BUILDING DESIGN AS ENCLOSED |
| | OR OPEN. |
| | |
| | 9) ON SHEET 3 THE INTERNAL PRESSURE COEFFICIENT IS |
| | POSITIVE OR NEGATIVE (+ OR -) 0.18. |
| | |
| | 10) SPECIFY THE BASIC WIND SPEED UNDER DESIGN |
| | PARAMETERS ON SHEET 3. |
| | |
| | 11) THE GARAGE DOES NOT HAVE ANY WINDOWS. PLEASE REMOVE |
| | THE WINDOW BUCK DETAIL ON SHEET 3. |
| | |
| | 12) SPECIFY THE NUMBER OF HEADER STUDS SUPPORTING THE |
| | HEADER (2) AND THE NUMBER OF FULL LENGTH STUDS (3) |
| | REQUIRED AT EACH END OF THE 10' GARAGE DOOR HEADER. SEE |
| | IBHS GUIDELINES FOR HURRICANE RESISTANT CONSTRUCTION. |
| | R301.2.1.1. |
| | |
| | 13) SHOW COMPLIANCE WITH R704 INSPECTION FOR TERMITES. |
| | IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE |
| | INFESTION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS |
| | AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING |
| | SHALL NOT BE LESS THAN 6 INCHES. |
| | |
| | 14) SPECIFY THE NAIL SIZE NUMBER FOR THE DOOR BUCK |
| | FASTENERS ON THE DETAIL ON SHEET 3. CHECK THE FASTENER |
| | DIAMETER THAT WAS SPECIFIED, .0126 APPEARS TO BE |
| | INCORRECT. |
| | |
| | 15) REVISE ROOF SHEATHING FASTENING SPECIFIED ON SHEET |
| | 3 TO 8D RING SHANK NAILS AS REQUIRED BY R803.2.3.1 OF |
| | THE 2006 AMENDMENTS TO THE FBC. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |
| | |