Plan Review Details - Permit 07040546
Plan Review Stops For Permit 07040546
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-15 Cont ID  
Sent By amorse Date 2007-09-15 Time 13:56 Rev Time 0.00
Received By amorse Date 2007-09-15 Time 13:56 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-04 Cont ID  
Sent By amorse Date 2007-08-04 Time 09:13 Rev Time 0.00
Received By amorse Date 2007-08-04 Time 09:13 Sent To PC
Notes
2007-08-04 09:17:11 
  
 DENIED
  
 THE FOLLOWING COMMENTS FROM REVIEW #1 WERE NOT
 ADDRESSED
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 ******* NOTE: FEES DUE FOR STATE RADON FEE AND
 INCREASED VALUE ARE $ 188.46. THESE FEES ARE DUE BEFORE
 FURTHER PLAN REVIEW*******
  
 10)DETAIL #2 ON PAGE 5 SHOWS #5 ANCHOR BARS INTO THE
 BLOCK STEM WALL BUT NO LOCATION IS GIVEN ON THE
 FOUNDATION PLAN. ALSO IS THE STEM WALL FULLY GROUTED AS
 ANCHOR BOLTS ARE ALSO PROVIDED TO ATTACH FRAMED WALL.
  
 *******NOTE:PLEASE SEE THAT PAGES 5 & 6 PLANS REFER TO
 1/2" BOLTS, IS THE FOUNDATION PLAN LAYOUT THE #5
 REINFORCING BARS THAT I AM REFERING TO IN THE ABOVE
 COMMENT AS THEY ARE AT 32" O/C AND THE BOLTS ON PAGE 6
 ARE 24" O/C. ALSO THE DETAILS ON PAGE 5DIFFER AS TO
 THE O/C PLACEMENT ? PLEASE CLARIFY*******
  
 NEW COMMENTS
  
 1)THE ROOF DECK ON THE DRAWINGS IS NOT AN INSULATED
 DECK BUT THE SUPPLIED PRODUCT APPROVAL IS. THE NON
 INSULATED SYSTEMS SHOULD BE CHOSEN FROM PAGES 39-43 OF
 THE PRODUCT APPROVAL. ALSO THE GENERAL LIMITATIONS PAGE
 # 44 IS MISSING, PLEASE NOTE THAT LIMITATION #7
 REQUIRES ENGINEERED CALCULATIONS FOR THE ENHANCED
 FASTENING REQUIRED FOR THE PERIMETER AND CORNER ZONES
 OF THE ROOF. PLEASE PROVIDE THIS WITH THE ROOF PRODUCT
 APPROVAL.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-11 Cont ID  
Sent By amorse Date 2007-06-11 Time 17:08 Rev Time 0.00
Received By amorse Date 2007-06-11 Time 17:08 Sent To PC
Notes
2007-06-11 16:46:19 
  
 DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MOREINFORMATION.
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*.
 FEES DUE FOR STATE RADON FEE AND INCREASED VALUE ARE $
 188.46. THESE FEES ARE DUE BEFORE FURTHER PLAN REVIEW.
  
 4)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD INCLUDE THE FLORIDA
 STATE APPROVAL COVER PAGES, AND THE PRODUCT NOA THAT
 LISTS THE SYSTEM COMPONENTS/ FASTENER LIST PAGES, THE
 PAGES WITH THE CHOSEN ASSEMBLY/ SYSTEM TO BE USED AND
 THE GENERAL LIMITATIONS PAGE. ALL CAN BE FOUND ON
 WWW.FLORIDABUILDING.ORG
  
 5)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 6)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 7)THE FOLLOWING CORRECTIONS ARE REQUIRED FOR THE
 PRODUCT APPROVALS THAT WERE SUBMITTED
 A)THE PGT NOA HAS EXPIRED PLEASE CHECK THE FLORIDA
 SITE UNDER FL# 242-R5WITH THE ACCOMPANYING APPROVAL
 WITCH IS MIAMI-DADE NOA 06-0405.06
 B)THE JELD-WEN DOOR NOA HAS ALSO EXPIRED , PLEASE
 FIND UNDER FL# 539 WITH MIAMI-DADE NOA 02-1211.13 C)
 THE JELD-WEN GLAZED STEEL DOOR (FRENCH DOOR) IS NOT
 IMPACT RATED AS REQUIRED ON THE DRAWING IF THIS DOOR IS
 USED, OPENING PROTECTION IS REQUIRED
  
 8)DRAWINGS SHALL SHOW THE MINIMUM DEPTH OF FOUNDATION
 ON THE WALL/FOUNDATION SECTIONS PER R403.1.4 FBC RES.
 NOTE FOUNDATION DETAIL #1 SHOWS A 16" DEEP FOUNDATION
 AND THE FOUNDATION PLAN HAS A 6" DROP TO FINISH GRADE
 (FOUNDATION DEPTH 10")
  
 9)PROVIDE SITE PLAN 2 COPIES OF A RECENT SURVEY
 SHOWING THE PROPOSED BUILDING/ADDITION WITH ALL SIDE
 AND REAR SETBACKS
  
 10)DETAIL #2 ON PAGE 5 SHOWS #5 ANCHOR BARS INTO THE
 BLOCK STEM WALL BUT NO LOCATION IS GIVEN ON THE
 FOUNDATION PLAN. ALSO IS THE STEM WALL FULLY GROUTED AS
 ANCHOR BOLTS ARE ALSO PROVIDED TO ATTACH FRAMED WALL.
  
 11)PLEASE NOTE THAT DETAILS 1,3 AND4 ON PAGE 6 ARE
 NOT SECTIONS AS DEPICTED BY SECTION SYMBOLS BUT
 STRUCTURAL ELEVATIONS OF WALLS
  
 12)WINDOW SCHEDULE ON PAGE 2 CALLS FOR CONCRETE
 LINTEL IN FRAMED WALL WHILE FRAMING DETAIL ON PAGE 6
 SHOWS WOOD HEADER PLEASE CLARIFY
  
 13)PROVIDE PRODUCT APPROVAL FOR ROOFING MATERIAL THAT
 WILL BE USED
  
 14)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 15)PROVIDE ANCHOR/STRAP/TIEDOWN SCHEDULE COMPLETE
 WITH APPLICABLE STATE OF FLORIDA NUMBERS OR SUBMIT
 PRODUCT APPROVALS FOR THEM.
  
 16)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-08-29 Cont ID  
Sent By btrobaug Date 2007-08-29 Time 15:32 Rev Time 0.00
Received By btrobaug Date 2007-08-29 Time 14:04 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-04-27 Cont ID  
Sent By btrobaug Date 2007-04-27 Time 07:47 Rev Time 0.50
Received By btrobaug Date 2007-04-27 Time 07:24 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 15:06 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 15:06 Sent To E
Notes
2007-08-27 15:07:02TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-08-23 Cont ID  
Sent By adarroug Date 2007-08-23 Time 15:11 Rev Time 0.00
Received By adarroug Date 2007-08-23 Time 15:11 Sent To Z
Notes
2007-08-23 15:13:27TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-07-20 Cont ID  
Sent By adarroug Date 2007-07-20 Time 11:05 Rev Time 0.00
Received By adarroug Date 2007-07-20 Time 11:05 Sent To M
Notes
2007-07-20 11:06:08TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-19 Cont ID  
Sent By adarroug Date 2007-07-19 Time 13:58 Rev Time 0.00
Received By adarroug Date 2007-07-19 Time 13:58 Sent To Z
Notes
2007-07-19 13:59:15TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-12 Cont ID  
Sent By adarroug Date 2007-07-12 Time 14:03 Rev Time 0.00
Received By adarroug Date 2007-07-12 Time 14:03 Sent To Z
Notes
2007-07-12 14:03:48TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-26 Cont ID  
Sent By adarroug Date 2007-04-26 Time 09:15 Rev Time 0.00
Received By adarroug Date 2007-04-26 Time 09:15 Sent To E
Notes
2007-04-26 09:15:20TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-06-11 Time   Rev Time 0.00
Received By adarroug Date 2007-04-19 Time 08:52 Sent To  
Notes
2007-04-19 08:53:18TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-08-30 Cont ID  
Sent By tgordon Date 2007-08-30 Time 08:30 Rev Time 0.20
Received By tgordon Date 2007-08-30 Time 08:16 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-07-20 Cont ID  
Sent By tgordon Date 2007-07-20 Time 14:17 Rev Time 0.25
Received By tgordon Date 2007-07-20 Time 14:17 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-30 Cont ID  
Sent By tgordon Date 2007-04-30 Time 09:02 Rev Time 0.25
Received By tgordon Date 2007-04-30 Time 09:02 Sent To P
Notes
2007-04-30 09:07:47*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.2.
  
 2) PLEASE SHOW ON MECHANICAL PLANS THE SIZE OF THE NEW
 SUPPLY AIR DUCT (FLEX) TO THE FAMILY ROOM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-09-15 Cont ID  
Sent By jleech Date 2007-09-15 Time 12:43 Rev Time 0.00
Received By jleech Date 2007-09-15 Time 12:43 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-08-02 Cont ID  
Sent By jleech Date 2007-08-02 Time 13:40 Rev Time 0.00
Received By jleech Date 2007-08-02 Time 13:40 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-05-07 Cont ID  
Sent By jleech Date 2007-05-07 Time 07:26 Rev Time 0.00
Received By jleech Date 2007-05-07 Time 07:26 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2007-08-27 Cont ID  
Sent By kdfreema Date 2007-08-27 Time 14:52 Rev Time 0.00
Received By kdfreema Date 2007-08-27 Time 14:52 Sent To I
Notes
2007-08-27 14:54:23PROVISO: ALL ROOMS SHALL BE ACCESSIBLE FROM THE
 INTERIOR OF THE DWELLING.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-07-19 Cont ID  
Sent By kdfreema Date 2007-07-19 Time 16:39 Rev Time 0.00
Received By kdfreema Date 2007-07-19 Time 16:39 Sent To I
Notes
2007-07-19 16:41:44***FAILED***
  
 1. ZONING COMMENTS WERE NOT ADDRESSED. ALL ROOMS MUST
 BE ACCESSIBLE FROM THE INTERIOR OF THE DWELLING UNIT.
  
 2. PLUMBING PLANS SHOW BATHROOMS IN WHAT THE MECHANICAL
 PLANS SHOW AS CLOSETS. PLEASE MAKE SURE THAT ALL PLANS
 ARE CONSISTENT.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 822-1435 WITH
 QUESTIONS.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-07-12 Cont ID  
Sent By kdfreema Date 2007-07-12 Time 17:14 Rev Time 0.00
Received By kdfreema Date 2007-07-12 Time 17:14 Sent To  
Notes
2007-07-13 08:12:40***FAILED***
  
 ALL ROOMS MUST BE ACCESSIBLE FROM THE INTERIOR OF THE
 DWELLING UNIT.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-24 Cont ID  
Sent By kdfreema Date 2007-04-24 Time 18:42 Rev Time 0.00
Received By kdfreema Date 2007-04-24 Time 18:42 Sent To I
Notes
2007-04-24 18:45:13PLEASE PROVIDE A PROPERTY SURVEY.
  
 CONTACT KELLY FREEMAN, PLANNER, AT 822-1435 WITH
 QUESTIONS.