Plan Review Details - Permit 07040545
Plan Review Stops For Permit 07040545
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-04-17 Cont ID  
Sent By jgomez Date 2008-04-17 Time 14:40 Rev Time 0.00
Received By jgomez Date 2008-04-17 Time 14:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-03-04 Cont ID  
Sent By jgomez Date 2008-03-04 Time 11:15 Rev Time 0.00
Received By jgomez Date 2008-03-04 Time 11:15 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-11-16 Cont ID  
Sent By jgomez Date 2007-11-16 Time 14:56 Rev Time 0.00
Received By jgomez Date 2007-11-16 Time 14:56 Sent To PC
Notes
2007-11-16 15:27:00RESIDENTIAL REPAIRS BUILDING REVIEW SECOND CHECKLIST.
 REVIEW DONE UNDER EXISTING BUILDING CODE 2004, FLORIDA
 RESIDENTIAL CODE 2004 WITH 2007 REVISIONS.
  
 1- PLANS SUBMITTED DON'T SHOW ANY WORK TO BE PERFORMED
 OTHER THAN ELECTRICAL, PLUMBING AND MECHANICAL.PLANS
 NEED TO SPECIFY EXTENT OF WORK AND SPECIFIC LOCATION OF
 WORK TO BE PERFORMED AS CALLED FOR IN THE PERMIT
 APPLICATION. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 2- NOWIS NOT CLEAR WHAT'S THE REAL SCOPE OF WORK TO
 BE PERFORMED. PERMIT APPLICATION CALLS FOR "R/R
 DRYWALL, INSULATION, ELECTRIC, R/R
 TUB/TOILET/SINK/VANITY".OWNER RESPONSE LETTER STATES
 THATNO WINDOWS ARE TO BE REPLACED (COMMENT FROM
 PREVIOUS CHECKLIST),ONLY THE WINDOW A/C UNITS ARE TO
 BE REPLACED. NOW IT'S NOT CLEAR WHY REPLACING THE
 WINDOW UNITS AND ALSOSHOWING A/C PLANS?. IN ADDITION,
 OWNER STATES THAT THERE ARE SOME WALLS THAT NEED THE
 WOODSTUDS TO BE REPLACED.PLANS DON'T SHOW ANY OF
 THIS WORK OR ANY SPECIFIC LOCATION FOR THIS WORK TO BE
 PERFORMED.
 PLEASE,COORDINATE ALL WORK TO BE PERFORMED IN THIS
 HOUSE AND PROVIDE SUCH INFORMATION IN THE PLANS DRAWN
 BY THE CERTIFIED BUILDING CONTRACTOR(SANTORO
 CONSTRUCTION, INC.) WHO DREW THE PLANS.
  
 3- UPDATE VALUATION TO INCLUDE ALL WORK TO BE PERFORMED
 IN ALL TRADES AS REQUIRED BY SEC. 108.3 CITY AMENDMENTS
 TO FBC 2004.REVISED VALUE OF $11,000 DOESN'T COVER
 ALL PROPOSED SCOPE OF WORK.
  
 4- PLANS NEED TO HAVE THE NAME AND ORIGINAL SIGNATURE
 OF THE CERTIFIED BUILDING CONTRACTOR WHO DESIGNED THE
 THE PLANS AS REQUIRED BY SEC. 106.3.4.3CITY
 AMENDMENTS TO FBC 2004.
  
 5- NEED RECORDED NOTICE OF COMMENCEMENT. ONE PROVIDED
 WAS RECORDED ON 04/19/2007. NOTICE OF COMMENCEMENT IS
 EXPIRED AFTER 90 DAYSIF WORK IS NOT STARTED AFTER IT
 WAS RECORDED. NEED TO PROVIDE RE-RECORDED NOTICE OF
 COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-27 Cont ID  
Sent By jgomez Date 2007-06-27 Time 11:13 Rev Time 0.00
Received By jgomez Date 2007-06-27 Time 11:13 Sent To PC
Notes
2007-06-27 12:33:43BUILDING REVIEW CHECKLIST:
 1- ATTACHED LETTER STATES REPLACING THREE EXISTING
 WINDOWS. NEED TO PROVIDE2 COPIES OF PRODUCT APPROVALS
 FOR THE WINDOWS AS REQUIRED BY DCA RULE 9B-72. SPECIFY
 TYPE AND SIZE OF EXISTING WINDOW AND TYPE AND SIZE OF
 PROPOSED WINDOW TO VERIFY COMPLIANCE WITH EGRESS
 REQUIREMENTS IF WINDOWS ARE LOCATED IN BEDROOMS.
  
 2- PERMIT APPLICATION CALLS FOR DRYWALL AND INSULATION
 INSTALLATION. NEED TO PROVIDE THE ENERGY CALCULATIONS
 AS REQUIRED BY CHAPTER 13 FBC 2004.COMPLETELY FILL
 OUT BOTH SIDES OF ATTACHED ENERGY CALCULATIONS FORMS.
 INCLUDING TOP OF FORM AND BOTTOM OF FORM TO BE SIGNED
 AND DATED ACCORDINGLY.
  
 3- SKETCHES SUBMITTED TO SHOW AREAS WHERE DRYWALL ,
 INSULATION AND WINDOWS AREGOING TO BE INSTALLED.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 4- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION
 IS TOO LOW.PERMIT VALUATION NEEDS TO INCLUDE ALL
 MATERIALS AND LABOR FOR ALL THE WORK TO BE PERFORMED,
 INCLUDING ALL ELECTRICAL AND PLUMBING WORK.UPDATE
 PERMIT VALUATION AS REQUIRED BY SEC. 108.3 CITY
 AMENDMENTS TO FBC 2004.
  
 5- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-24 Cont ID  
Sent By kconrad Date 2007-04-24 Time 19:40 Rev Time 0.00
Received By kconrad Date 2007-04-24 Time 19:40 Sent To I
Notes
2007-04-24 19:41:04REQUIRE PLANS/ELECTRICAL AND PLUMBING PERMITS.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-04-10 Cont ID  
Sent By dpalmer Date 2008-04-10 Time 14:55 Rev Time 0.00
Received By dpalmer Date 2008-04-10 Time 14:55 Sent To M
Notes
2008-04-10 14:58:56** REDLINED ELECTRICAL PLANS.
 THE OCP SHOWN ON AHU DOES STILL NOT MEET 424.3B. MIN
 OCP 60AMPS.
 ** PLANS ROUTED TO MECH AS NEW SHEETS WERE SUBMITTED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-03-03 Cont ID  
Sent By dpalmer Date 2008-03-03 Time 09:52 Rev Time 0.00
Received By dpalmer Date 2008-03-03 Time 09:52 Sent To M
Notes
2008-03-03 09:52:13** DENIED 3RD REVIEW **
  
 ** MANY COMMENTS ARE NEW AS THESE THINGS ARE JUST NOW
 BEING SHOWN.
  
 1) NOTE: PLEASE SEE 424.3B AS THE MINIMUM OVER CURRENT
 PROTECTION FOR THE AHU NEEDS TO BE AT 125%. SHOWS 30AMP
 ON 10KW HEAT WHICH IS NOT PERMITTED.
 PLEASE ALSO COORDINATE THE AHU HEAT ON CALCULATIONS
 WITH THE MECHANICAL PLANS AS MECHANICAL SHOWS 10KW AND
 ELECTRICAL CALCULATIONS SHOWS 8KW AND 9KW.
  
 2) NOTE: PLEASE INCLUDE DETAILS FOR GROUNDING ELECTRODE
 SYSTEM.PLEASE SEE 250.50, 250.56, 250.52(5) PLEASE
 INCLUDE 2-GRND RODS, AND COLD WATER PIPE (METAL).
 MAY NOT QUOTE 250 AS GENERAL IN LIEU OF DETAILS.
  
 3) NOTE: PLEASE INCLUDE THE ACTUAL AIC RATING OF MAIN.
 PLANS INCLUDE A LETTER FROM FPL WHICH GIVES AVAILABLE
 FAULT CURRENT HOWEVER THIS DOES NOT GIVE THE RATING OF
 WHAT THE MAINS/EQUIPMENT WILL BE. THE SELECTION OF THE
 AIC OF EQUIPMENT IS DETERMINED FROM THE AVAILABLE FAULT
 CURRENT HOWEVER THE SELECTION IS NOT DONE BY FPL.
 110.9
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 DINING ROOM LOADS. THE PANEL SCHEDULE SHOWS TWO
 DEDICATE CIRCUITS WHICH REQUIRES THE LOAD TO BE FIGURED
 FOR DINING ROOM RECEPTACLE CIRCUITS ARE TO BE FIGURED
 IN ADDITION TO THE TWO SMALL APPLIANCE CIRCUITS.
 210.52B1, 210.11C1, 220.53
  
 5) NOTE: PLEASE SEE MECHANICAL REVIEW COMMENTS WITH
 RESPECT TO RETURN AIR.
 ELECTRICAL PLANS SHOWS AHU BEING OPEN TO CLOSET YET THE
 OTHER TWO SHEETS SHOWS THE AHU AS CLOSED IN.
 PLEASE KNOW THAT THE AHU MAY NOT CONTAIN OVER CURRENT
 PROTECTION IN A CLOSET IN CLOSE PROXIMITY TO EASILY
 IGNITABLE MATERIALS.
 240.24, 110.26
  
 6) NOTE: PLEASE SEE THE LOAD FOR THE DISPOSAL IS NOT
 FIGURED INTO THE LOAD CALCULATIONS. THIS CIRCUIT IS
 SHOWN ON PANEL SCHEDULE.
 220
 PLEASE ALSO SEE THE KITCHEN ELECTRICAL PLANS DO NOT
 INCLUDE THE RECEPTACLE FOR THIS DISPOSAL. WILL IT BE
 SWITCHED? OR SELF STARTING?
  
 7) NOTE: PLEASE COORDINATE THE SUB PANELS AS THE RISER
 SHOWS THESE A MLO WHICH IS CORRECT AND THE PANEL
 SCHEDULES SHOW THESE AS MDO?
 SEEMS TO BE A MISPRINT.
 FBC 106.1.2 FOR COORDINATION.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-09 Cont ID  
Sent By dpalmer Date 2007-11-09 Time 16:12 Rev Time 0.00
Received By dpalmer Date 2007-11-09 Time 16:12 Sent To M
Notes
2007-11-09 16:12:45** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME CODE SECTIONS FROM PREVIOUS REVIEW
 ARE STILL IN NEED OF ADDRESSING.
 PLEASE ALSO SEE SEVERAL NEW COMMENTS DUE TO NEW PLANS
 BEING SUBMITTED FOR REVIEW.
  
 1) NOTE:PLEASE REFERENCE ALL CODES ON PLANS AS
 PREVIOUSLY STATED AND REQUIRED BY FBC.
 2004 FBC/W2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE KNOW THAT INFORMATION AND PAPER
 DOCUMENTATION MAY NOT BE TAPED ONTO PLANS.
 PLEASE COPY AND PRINT SHEETS.
 PLEASE BE SURE THE PRINTED NAME AND SIGNATURE OF THE
 PERSON TAKING RESPONSIBILITY FOR PLANS IS DONE ON NEW
 SHEETS.
 FBC 106.1.2, 106.5
  
 3) NOTE: PLEASE SEE PLANS ARE MISSING RECEPTACLES PER
 210.52.
 FOR EXAMPLE: WALL SPACES IN KITCHEN.
  
 4) NOTE: PLEASE SEE 210.52B1, 210.11C2, 220.53 AS 1500
 VA IS REQUIRED FOR ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS. THIS COMMENT IS FOR THE DINIGN ROOM
 CIRCUITED.
  
 5) NOTE: PANEL SCHEDULE SHOWS JACUZZI TUB GFI CIRCUIT
 YET PLANS DO NOT SHOW ANY ELECTRICAL.
 THIS IS THE SAME FOR OTHER ITEMS WHICH ARE MISSING
 ELECTRICAL OUTLETS/RECEPTACLES ON PLANS.
 WASHER, DRYER, DISHWASHER ETC.
 PLEASE COMPLETE PLANS WITH ALL ELECTRICAL FOR MINIMUM
 NEC COMPLIANCE AND ELECTRICAL WHICH IS LISTED ON PANEL
 SCHEDULE.
 FBC 106.3.5.4
  
 6) NOTE: PLEASE SEE 210.52D, 210.11C3 AS ALL DEDICATED
 BATH RECEPTACLE CIRCUITS SHALL BE 20AMP AND #12 AWG.
 PANEL SCHEDULE SHOWS 15AMP BREAKERS.
  
 7) NOTE: PLEASE SEE 230.70, AS NO MORE THAN 8FT OF
 UNPROTECTED CONDUCTORS ARE PERMITTED INSIDE DWELLING.
 PLEASE KNOW AS THIS IS AN EXISTING DWELLING, THESE
 WOULD NOT BE IN THE SLAB AND BASED ON LOCATION AND
 SCALE ON PLANS, A MAIN WITH OCP WOULD BE REQUIRED
 OUTSIDE.
 THE OTHER OPTION WOULD BE TO RELOCATE PANEL FROM
 LOCATION SHOWN TO DECREASE UNPROTECTED CONDUCTOR
 LENGTH.
  
 8) NOTE: PLEASE SUBMIT REVISED COMPLETED PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTIONS SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-17 Cont ID  
Sent By dpalmer Date 2007-05-17 Time 14:42 Rev Time 0.00
Received By dpalmer Date 2007-05-17 Time 14:31 Sent To M
Notes
2007-05-17 14:43:22** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
  
  
 1) NOTE:PLEASE SEE PLANS MUST REFLECT CURRENT CODES
 IN EFFECT AND ADOPTED BY THE STATE IN THE SCOPE OF WORK
 AS SHOWN.
 PLEASE KNOW HOWEVER AT THIS TIME AND AS OF DECEMBER
 8TH, 2006 THE STATE IS UNDER THE 2004 FBC W/2006
 REVISIONS. THESE ARE ONLY REVISIONS TO THE 2004 FBC.
 SOME OF THESE ARE STATED ON ELECTRICAL HOWEVER SHOULD
 ALSO BE ON COVER SHEETS.
 WE ARE UNDER THE 2005 NFPA-70. (NEC).
 PLEASE ALSO LIST THE FOLLOWING.
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE FBC R313 AS THE EXISTING DWELLING
 IS REQUIRED TO BE BROUGHT UP TO CODE OR THE EXISTING IS
 TO SHOW MEETING THE CURRENT CODE FOR SMOKE
 DETECTION/SOUNDING DEVICES. PLEASE SHOW A LAYOUT OF THE
 EXISTING DWELLING WHICH WILL REQUIRE SMOKE DEVICES
 INSIDE AND OUTSIDE ALL BEDROOMS AND ON EACH LEVEL IF A
 MULTI-LEVEL BUILDING.
 PLEASE SHOW THE SMOKE DEVICES AS SA OR SD DEPENDING ON
 THE TYPE OF DEVICE. PLEASE SEE THE DEFINITIONS IN
 NFPA-72 OR CALL TO GO OVER.
 NFPA-72 11.5.1.1, 11.8.3
  
 3) NOTE: PLEASE SUBMIT COMPLETED PLANS FOR 2005 NEC
 COMPLIANCE:
 PLEASE COMPLETE RISER WITH ALL MINIMUM CONDUCTOR
 SIZES.
 PLEASE INDICATE ALL OVER CURRENT PROTECTION DEVICES FOR
 SERVICE AND BRANCH CIRCUITS.
 PLEASE SUBMIT A COMPLETED PANEL SCHEDULE SHOWING ALL
 MINIMUM REQUIRED CIRCUITS AND OTHER DEDICATE CIRCUITS
 PER NEC.
 PLEASE COMPLETE PLANS WITH ALL ELECTRICAL.
 PLEASE COMPLETE KITCHEN LAY OUT.
 PLEASE SHOW ALL DISCONNECT LOCATIONS.
 PLEASE SUBMIT AIC RATINGS FOR NEW SERVICE EQUIPMENT.
 PLEASE COMPLETE CORRECT GROUNDING ELECTRODE SYSTEM.
 PLEASE COMPLETE FIXTURE LEGEND AND EGRESS LIGHT. PLEASE
 SUBMIT COMPLETED LOAD CALCULATIONS.
 PLEASE SEE FBC CHAPTER 13 FOR ENERGY EFFICIENCY
 COMPLIANCE FOR ANY RECESSED LIGHTING FIXTURES AND ALSO
 FOR A/C WORK ETC. SEE MECH REVIEW COMMENTS. 210.8A,
 210.52,210.11,220, 230, 240, 440,422, 424, 210.70
 310.16 ETC.
 ** PLEASE KNOW THERE ARE TOO MANY ITEMS MISSING FOR A
 CODE COMPLIANT REVIEW. PLEASE COMPLETE AS NOT
 EVERYTHING AS MENTIONED ABOVE IS ALL REQUIRED PER
 MINIMUM CODE.
  
 4) NOTE: PLEASE KNOW THAT PLANS MUST BE SUBMITTED IN A
 MINIMUM 1/8 SCALE, DRAFTSMAN?S QUALITY, MAY NOT BE IN
 PEN OR PENCIL.
 MUST CONTAIN PRINTED NAME AND SIGNATURE FROM THE DESIGN
 PROFESSIONAL.
 FS 481.229, 471.003
 FBC 106.1.3, 106.1.2, 106.3.5.4
  
 5) NOTE:VALUE FOR COMPLETE SCOPE OF WORK MUST INCLUDE
 FAIR MARKET VALUE AND INCLUDE ALL LABOR AND MATERIALS
 EVEN IF OWNER SUPPLIED AND NO COST FOR LABOR AS OWNER
 CONSTRUCTED.
 FBC 108.3
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-10 Cont ID  
Sent By adarroug Date 2008-04-10 Time 08:50 Rev Time 0.00
Received By adarroug Date 2008-04-10 Time 08:50 Sent To E
Notes
2008-04-10 08:50:40TO "DPALMER" DESK/-NEW SHEETS ALL TRADES

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-20 Cont ID  
Sent By adarroug Date 2008-02-20 Time 16:51 Rev Time 0.00
Received By adarroug Date 2008-02-20 Time 16:51 Sent To E
Notes
2008-02-20 16:51:35TO "E" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-08 Cont ID  
Sent By adarroug Date 2007-11-08 Time 11:04 Rev Time 0.00
Received By adarroug Date 2007-11-08 Time 11:04 Sent To E
Notes
2007-11-08 11:04:34TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-27 Cont ID  
Sent By jgomez Date 2007-06-27 Time 13:12 Rev Time 0.00
Received By jgomez Date 2007-05-14 Time 15:11 Sent To  
Notes
2007-05-14 15:11:48TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-04-11 Cont ID  
Sent By tgordon Date 2008-04-11 Time 09:40 Rev Time 0.30
Received By tgordon Date 2008-04-11 Time 09:40 Sent To P
Notes
2008-04-11 09:41:471/2 DOOR ABOVE RETURN AIR GRILL FOR SERVICE, PER GENE
 S.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-03-03 Cont ID  
Sent By tgordon Date 2008-03-03 Time 11:05 Rev Time 0.30
Received By tgordon Date 2008-03-03 Time 11:04 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-11-13 Cont ID  
Sent By tgordon Date 2007-11-13 Time 08:13 Rev Time 0.30
Received By tgordon Date 2007-11-13 Time 08:13 Sent To P
Notes
2007-11-13 08:27:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) THE MAIN TRUNK LINE (DUCT) STILL NEEDS TO BE SIZED,
 (SEE YELLOW HIGH LIGHT ON MECHANICAL PLAN), SEE WPB
 AMEND. 106.3.5.4 (10).
  
 2) THE RETURN AIR TRANSFER DUCT STILL NEEDS TO BE
 SIZED, (SEE YELLOW HIGH LIGHT ON MECHANICAL PLAN), SEE
 FBC/R M1602.4.
  
 3) SHOW THE MANUFACTURER'S NAME OF THE A/C SYSTEM ON
 THE PLAN.
  
 4) SHOW THE HEATER KW ON THE PLAN IF ONE IS TO BE
 INSTALLED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-21 Cont ID  
Sent By tgordon Date 2007-05-21 Time 10:27 Rev Time 0.30
Received By tgordon Date 2007-05-21 Time 10:27 Sent To P
Notes
2007-05-21 10:33:46*** DENIED ***
 1) PLEASE SHOW SIZE OF ALL SUPPLY AIR TRUNK LINES
 (DUCTS).
  
 2) PLEASE SHOW CFM'S. AT ALL SUPPLY AIR GRILLS.
  
 3) PLEASE SHOW SIZE OF RETURN AIR TRANSFER DUCT AND
 GRILLS.
  
 4) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-04-14 Cont ID  
Sent By mperson Date 2008-04-14 Time 16:08 Rev Time 0.00
Received By mperson Date 2008-04-14 Time 16:08 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-03-03 Cont ID  
Sent By mperson Date 2008-03-03 Time 16:07 Rev Time 0.00
Received By mperson Date 2008-03-03 Time 16:07 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-11-14 Cont ID  
Sent By mperson Date 2007-11-14 Time 13:25 Rev Time 0.00
Received By mperson Date 2007-11-14 Time 13:25 Sent To B
Notes
2007-11-14 13:41:09PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. NOTE: PER THE PLUMBING "COMMENTS RESUBMITTALS"
 PLEASE CLEARLY INDICATE ON FLOOR PLAN SHEET E-1REV
 EXACTLY WHAT IS BEING REPLACED. PER *106.1.2,
 ADDITIONAL INFORMATION REQUIRED.
  
 2. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
 **NOTE: THIS IS REQUIRED FOR THE SANITARY ISOMETRIC
 RISER DIAGRAM ATTACHED TO SHEET A/C.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-05 Cont ID  
Sent By mperson Date 2007-06-05 Time 09:50 Rev Time 0.45
Received By mperson Date 2007-06-05 Time 09:50 Sent To B
Notes
2007-06-05 10:22:52DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
 NOTE: THE SUBMITTED PLUMBING RISER IS NOT A SANITARY
 ISOMETRIC RISER DIAGRAM, DOES NOT REFLECT THE FLOOR
 PLAN AND NOT ALL PIPING IS SIZED. PLEASE REFERENCE THE
 ATTACHED SANITARY ISOMETRIC RISER DIAGRAM TO THE
 PLUMBING COMMENTS THAT IS CODE COMPLIANT AND REFLECTS
 THE FLOOR PLAN FOR THE RESUBMITTAL.
  
 2. PER FBC-2004 PLUMBING, SECTION 1002.1 A FIXTURE
 SHALL NOT BE DOUBLE TRAPPED. A WATER CLOSET HAS AN
 INTREGRAL TRAP THEREFORE A TRAP IS NOT REQUIRED FOR THE
 SANITARY ISOMETRIC RISER DIAGRAM.
  
 3. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 4. PER FBC-2004, CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721