Plan Review Details - Permit 07040533
Plan Review Stops For Permit 07040533
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-13 Cont ID  
Sent By jwitmer Date 2007-06-13 Time 16:43 Rev Time 1.22
Received By jwitmer Date 2007-06-13 Time 16:32 Sent To PC
Notes
2007-06-13 16:49:54BUILDING PLAN REVIEW
 PERMIT: 07040533
 ADD: 900 SOUTH DIXIE HWY
 CONT: PEMBERTON BUILDERS
 TEL: (561)744-3399
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET M3.0 PROVIDES A CURB DETAIL BUT INDICATES THIS
 IS FOR REFRENENCE ONLY REQUIRES STRUCTURAL ENGINEER,
 PLEASE PROVIDE DERTAIL AND WIND REQUIREMENTS FOR
 DESIGN, 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4)CHANGE IN OCCUPANCY.BEFORE A PERMIT TO CONSTRUCT,
 MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED
 BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-23 Cont ID  
Sent By dpalmer Date 2007-04-23 Time 13:07 Rev Time 0.00
Received By dpalmer Date 2007-04-22 Time 14:26 Sent To  
Notes
2007-04-23 13:07:49 
 *** UNSAT ***
  
 1) NOTE: PLEASE INDICATE THE FOLLOWING CODES ON
 ELECTRICAL PLANS.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 ** PLEASE KNOW THAT ANY OTHER CODES FOR OTHER TRADES
 MAY BE REQUIRED.
  
 2) NOTE: PLEASE SEE PLAN NOTES MENTIONS THAT THERE WILL
 BE A * DRIVE-THRU* HOWEVER THIS COULD NOT BE LOCATED ON
 PLANS.?
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 3) NOTE: PLEASE SEE THE LOCATION OF THE SERVICE ON THE
 EAST SIDE OF THE BUILDING CONTAINSA DRIVEWAY/PARKING
 LOT AREA WHICH IS SUBJECT TO TRUCK AND VEHICLE TRAFFIC.
 PLEASE INDICATE THE HEIGHT OF THE RISER AS REQUIRED PER
 230.24B4.
 PLEASE ALSO PLACE A NOTE ON PLANS FOR REQUIRED BOLLARDS
 FOR PROTECTION OF THE SERVICE EQUIPMENT PER 110.26(F)2
  
 4) NOTE: PLEASE CORRELATE ENERGY CALCULATIONS WITH THAT
 OF THE ELECTRICAL LIGHTING FIXTURES ON PLANS. PLEASE
 SEE PLANS INDICATE EXTERIOR LIGHTING FIXTURES, YET
 CALCULATIONS DO NOT INDICATE ANY.
 PLEASE SEE THE WATTAGE, TYPES OF FIXTURES ON PLANS DO
 NOT COORDINATE WITH THE ENERGY CALCULATIONS. PLEASE SEE
 13-415.1.AB.1, 13-415.2, PLEASE BE SURE TO SEE
 13-415.2.ABC.1.2 FOR TRACK LIGHTING.
 PLEASE SEE THAT FOUR COPIES WERE SUBMITTED WHEN ONLY
 TWO COPIES ARE NEEDED.
  
 5) NOTE: PLEASE SUBMIT AIC RATING FOR ALL SERVICE
 EQUIPMENT INCLUDING MAIN.
 110.9,
 FBC 106.3.5.1.2
  
 6) NOTE: PLEASE SEE THE GROUNDING ELECTRODE RISER
 MENTIONS CONNECTION TO THE FOOTER STEEL, HOWEVER AS
 THIS IS AN EXISTING BUILDING, FOOTER STEEL MAY OR MAY
 NOT BE AVAILABLE. IN THE INTEREST OF AFFECTING THE
 STRUCTURAL STABILITY OF THE EXISTING FOOTER 250.50 DOES
 NOT REQUIRE ATTACHMENT WHEN THE EXISTING IS NOT
 AVAILABLE.
 PLEASE KNOW THAT IF SHOWN PART OF THE GE SYSTEM ON
 PLANS, CONNECTION WILL BE REQUIRED.
  
 7) NOTE: PLEASE SEE THE RISER IS MISSING THE TAP
 CONDUCTORS FROM THE GUTTER TO PANELS.
 240.21, 408.36, 240.4, 310.16 ETC CAN NOT BE VERIFIED
 AT THIS TIME.
 PLEASE ALSO INDICATE CONDUIT SIZES.
  
 8) NOTE: PLEASE SEE 422.13 FOR WATER HEATER LOADS
 REQUIRED AT 125%.
  
 9) NOTE: PLEASE CLARIFY AND SHOW ALL CONTINUOUS LOADS
 AT 125%. 2215.3, 230.42 ETC.
  
 10) NOTE: PLEASE CLARIFY LOADS FOR TRACK LIGHTING AND
 SHOW WINDOWS PER 220.43 A AND B.
  
 11) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES
 ABOVE WEST WINDOW. MOST WINDOWS ARE SHOWN BUT NOT ALL.
 12) NOTE: ** PLEASE KNOW THAT THE BASE PLANS MAY BE
 USED AS REFERENCE FOR LOW VOLTAGE WORK AS SHOWN HOWEVER
 THE LV SECURITY AND OTHER LV SYSTEMS WILL BE REQUIRED
 TO BE UNDER SEPARATE PERMITS AND FEES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-04-22 14:47:20REVIEW TO CONTINUE ON 4/23
 NOTES TO FOLLOW ONCE REVIEW IS COMPLETE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-13 Cont ID  
Sent By mwennerg Date 2007-06-13 Time 10:56 Rev Time 0.00
Received By mwennerg Date 2007-06-13 Time 10:56 Sent To  
Notes
2007-06-13 11:08:39***DENIED***
  
 1) OUTSIDE SEATING SHALL NOT INTERFERE WITH EXIT
 DISCHARGE FROM BUILDING.
  
 2) IN ADDITION TO THE FLORIDA FIRE PREVENTION CODE
 2004, LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 3) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 4) ADDRESS TO BE A MINIMUM OF 6" IN HEIGHT FOR
 COMMERCIAL BUILDINGS, AND CONTRASTING TO THE
 BACKGROUND. (SHEET A1.0 NOTE #2)
  
 5) PLEASE PROVIDE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING.
  
 6) OCCUPANT NOTIFICATION WILL BE REQUIRED IN AREA OF
 DUCT SMOKE DETECTOR(S).
  
 7) KNOX BOX TO BE INSTALLED FOR AFTER HOURS EMERGENCY
 ACCESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-13 Cont ID  
Sent By jwitmer Date 2007-06-13 Time 16:50 Rev Time 0.00
Received By jwitmer Date 2007-04-18 Time 09:45 Sent To  
Notes
2007-04-18 09:45:48TO "COMM" BD#35

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-04 Cont ID  
Sent By rregueir Date 2007-05-04 Time 15:07 Rev Time 0.00
Received By rregueir Date 2007-05-04 Time 12:46 Sent To  
Notes
2007-05-04 15:07:52--------------DENIED----------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. EF SCHEDULE: ACCESSORY NOTE #3 STATES "INTERLOCK PER
 EXHAUST FAN NOTES FOR CONTROL." NO SICH INFORMATION
 COULD BE LOCATED ON PLANS. HOW IS FAN TO BE
 CONTROLLED?
  
 2. A7.3 SHOWS WARMING OVENS WITH EXHAUST DUCTS. NO
 INFORMATION COULD BE FOUND ON MECHANICAL PLANS
 REGARDING THE LOCATION OR TERMINATION OF THIS DUCT.
  
 3. M3.0 ROOF CURB DETAIL STATES "FOR REFERENCE ONLY."
 WHERE IS THE VERIFICATION FROM STRUCTURAL ENGINEER TO
 BE FOUND? PROVIDE WIND LOAD CALCS FOR BUILDING PLAN
 REVIEW. FBC 106.1.2 AND 106.3.5.1.1(8)
  
 4. PLEASE SHOW LAYOUT OF ROOF EQUIPMENT AND ROOF
 PENETRATIONS TO SHOW COMPLIANCE WITH ALL OF FBC,M
 401.5.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805-6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-02 Cont ID  
Sent By kstevens Date 2007-06-02 Time 07:31 Rev Time 0.00
Received By kstevens Date 2007-06-01 Time 17:00 Sent To  
Notes
2007-06-02 07:46:17DENIED
 REFERENCE: FBC-2004 PLUMBING
 MUNICIPAL CODE WPB
  
 1. SHT A0.0 NOTE #8. IN THE REMOVAL OF ANY PART OF A
 DRAINAGE SYSTEM, DEAD ENDS SHALL BE PROHIBITED. SECTION
 704.5.
  
 2. SHTS P1.0 & P3.0 A GREASE INTERCEPTOR SHALL BE SIZED
 BY ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY
 COMPO, (561) 922-2272 OR CALVIN WILLIAMS, (561)
 722-2284. THEIR FAX NUMBER IS (561) 2287 & E-MAIL'S ARE
 [email protected] OR [email protected].
  
 3. SHTS P2.0 & P4.1 FIXTURE ADL24 & WATER ISOMETRIC
 RISER DIAGRAM. HOT WATER SHALL BE ON THE LEFT SIDE OF
 THE FIXTURE PER SECTION 607.4.
  
 4. SHTS P3.0 & P4.1 THE DISHWASHER SHALL DISCHARGE INTO
 THE SANITARY SYSTEM, NOT THE GREASE SYSTEM PER
 MUNICIPAL CODE SECTION 90-124(7)(B).
  
 5. SHT P4.0 EQUIPMENT AND FIXTURES UTILIZED FOR THE
 STORAGE, PREPARATION AND HANDLING OF FOOD SHALL
 DISCHARGE THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN
 AIR GAP, NOT AN AIR BREAK AS SHOWN IN DETAILS 1 & 8.
 SECTION 802.1.1. THE AIR GAP BETWEEN THE INDIRECT WASTE
 PIPE AND THE FLOOD LEVEL RIM OF THE WASTE RECEPTOR
 SHALL BE A MINIMUM OF TWICE THE EFFECTIVE OPENING OF
 THE INDIRECT WASTE PIPE. SECTION 802.2.1.
  
 6. SHT P4.1 THE WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES IN AN "EFFECTIVE RANGE", NOT IN THE
 CEILING AS SHOWN. PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
  
 7. THE REVERSE OSMOSIS DRINKING WATER TREATMENTS SHALL
 MEET THE REQUIREMENTS OF NSF-58, REVERSE OSMOSIS
 DRINKING WATER TREATMENT UNITS, OR WATER QUALITY
 ASSOCIATION STANDARD S-300, POINT-OF-USE LOW PRESSURE
 REVERSE OSMOSIS DRINKING WATER SYSTEMS. SECTION 611.2.
 PLEASE SUBMIT MANUF SPECIFICATION SHEETS INDICATING
 COMPLIANCE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE
 SET OF THEM LOOSELY ON TOP OF THE COLLATED
 PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-04 Cont ID  
Sent By bpowell Date 2007-05-04 Time 08:41 Rev Time 0.00
Received By bpowell Date 2007-05-04 Time 08:41 Sent To  
Notes
2007-05-04 08:47:171.TWO COPIES OF A SURVEY SHALL BE INCLUDED WITH THE
 PERMIT APPLICATION.
  
 2.PLEASE PROVIDE A SEPARATE SITE PLAN.
  
 3.PROPERTY LINES SHALL BE SHOWN ON THE SITE PLAN AS
 WELL AS THE FLOOR PLAN.
  
 4.ON THE ELEVATIONS SHEET PLEASE LABEL WHAT'S
 EXISTING AND WHAT'S NEW.
  
 *NOTE- SIGNAGE MUST BE UNDER A SEPARATE PERMIT
 FOR QUESTIONS OR COMMENTS CONTACT: BOBBY POWELL, JR.,
 (561) 822-1435, [email protected]
  