Plan Review Details - Permit 07040518
Plan Review Stops For Permit 07040518
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-30 Cont ID  
Sent By mjacobs Date 2007-04-30 Time 15:24 Rev Time 0.00
Received By mjacobs Date 2007-04-30 Time 07:28 Sent To  
Notes
2007-04-30 15:24:15BUILDING PLAN REVIEW
 PERMIT: 07040518
 ADD: 719 EXECUTIVE CENTRE DR.
 CONT: BORAN CRAIG BARBER ENGEL CONST. CO.
 TEL: (239)643-3343
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)PROVIDE DETAIL ELEVATION DRAWINGS OF THE
 STAIRS/RAMP AND PLATFORM OF THE STRUCTURE. ALSO PROVIDE
 THE CROSS SECTION DETAILS.
 FBC. 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED. (SECTION106.3.5)
  
 3)11-4.8.2 SLOPE & RISE. THE LEAST
 POSSIBLE SLOPE SHALL BE USED FOR ANY
 RAMP. THE MAXIMUM SLOPE FOR A RAMP IN
 NEW CONSTRUCTION SHALL BE 1 TO 12. THE
 MAXIMUM RISE FOR RUN SHALL BE 30" (SEE
 FIGURE 16).
 11-4.8.3. CLEAR WIDTH. THE MINIMUM
 CLEAR WIDTH OF A RAMP SHALL BE 36".
 EXCEPTION: RAMPS THAT ARE PART OF A
 REQUIRED MEANS OF EGRESS SHALL NOT BE
 LESS THAN 44 INCHES WIDE.
 11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE.
 11-4.8.4(3) IF RAMPS CHANGE DIREC-
 TION AT LANDINGS, THE MINIMUM LANDING
 SIZE SHALL BE 60" X 60".
 11.4.8.5. HANDRAILS: IF A RAMP HAS
 A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 4)11-4.6.2ACCESSIBLE PARKING SPACES SERVING A
 PARTICULAR BUILDING SHALL BE LOCATED ON THE SHORTEST
 SAFELY ACCESSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING
 TO AN ACCESSIBLE ENTRANCE. THE HANDICAP PARKING IS
 LOCATED WHERE THE PERSON WILL HAVE TO TRAVEL ACCROSS
 TRAFFIC.
  
 5)THE APPLICATION IS FOR A TEMPORARY SALET TRAILER.
 NOTE: PERMITS FOR TEMPORARY STRUCTURES SHALL NOT PE
 PEMITTED FOR MORE THAN 180 DAYS. FBC. 107.1
 107.2 TEMPORARY STRUCTURES AND USES SHALL COMFORM TO
 THE STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS,
 ACCESSIBILITY, LIGHT, VENTILATION AND SANITARY
 REQUIREMENTS OF THIS CODE AS NECESSARY TO ENSURE THE
 PUBLIC HEALTH, SAFETY AND GENERAL WELFARE.
  
 6)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 7)FBC. 1805.4.3 THE DESIGN, MATERIALS AND
 CONSTRUCTION OF MASONRY-UNIT FOOTINGS SHALL COMPLY WITH
 SECTIONS 1805.4.3.1 AND 1805.4.3.2 AND THE PROVIXIONS
 OF CH.21. THE THICKNESS OF THE MASONTY-UNIT FOOTING
 SHALL NOT BE LESS THAN 6 INCHES.
  
 8)1802.2.1 WHERE THE SAFE-SUSTAINING POWER OF THE
 SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6
 .
  
 1804.3 LATERAL SLIDING RESISTANCE.
 THE RESISTANCE OF STRUCTURAL WALLS TO LATERAL SLIDING
 SHALL BE CALCULATED BY COMBINING THE VALUES DERIVED
 FROM THE LATERAL BEARING AND THE LATERAL SLIDING
 RESISTANCE SHOWN IN TABLE 1804.2 UNLESS DATA TO
 SUBSTANTIATE THE USE OF HIGHER VALUES ARE SUBMITTED FOR
 APPROVAL.
  
 9)THE SIGNATURE ON THE ENERGY EFFICIENCY REPORT IS A
 PHOTO- COPY.ALL INFORMATION BEING FILED FOR PUBLIC
 RECORS SHALL CONTAIN THE ORIGINAL DATE AND SIGNATURE OF
 THE PERSON RESPONSIBLE. FS 481.221/471.025 AND F.A.C.
 61G15-23.002 FOR MORE INFORMATION.
  
 10)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 11)11-4.1.2(1)AT LEAST ONE ACCESSIBLE ROUTE
 COMPLYING WITH SECTION 11-4.3 SHALL BE PROVIDED WITHIN
 THE BOUNDARY OF THE SITE FROM PUBLIC TRANSPORTATION
 STOPS, ACCESSIBLE PARKING SPACES, PASSENGER LOADING
 ZONES IF PROVIDED, AND PUBLIC STREETS OR SIDEWALKS, TO
 AN ACCESSIBLE BUILDING ENTRANCE.
  
 NOTE: ON SHEET A-1 (2)REMOVE THE CODE REVIEW-
 HIGHRISE INFORMATION FROM THE DRAWINGS. THIS
 INFORMATION HAS NOTHING TO DO WITH THIS PROJECT
 THEREFORE IS SHALL BE REMOVED FROM THE DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-21 Cont ID  
Sent By dpalmer Date 2007-04-21 Time 13:59 Rev Time 0.00
Received By dpalmer Date 2007-04-21 Time 13:36 Sent To  
Notes
2007-04-21 13:59:50** UNSAT **
  
 1) NOTE: PLEASE STATE ON PLANS ALL UPDATED DATED
 ADOPTED CODES AS OF DECEMBER 8TH, 2006 WHICH MUST
 INCLUDE THE FOLLOWING AT A MINIMUM FOR ELECTRICAL.
 PERMIT APPLICATIONS AFTER THIS DATE FALLS UNDER THE NEW
 CODES.
 NFPA-70 2005, 2004 FBC W/ 2006 REVISIONS.
 1999 CODE SHOWN FOR NEC.
 ** SEE OTHER TRADE REVIEWS FOR ANY OTHER CODES.
  
 2) NOTE: PLEASE SEE PLANS DO NOT INDICATE CODE
 COMPLIANCE FOR THE LOCATION OF THE WATER HEATER OR ANY
 DISCONNECTING MEANS REQUIRED PER 422.30/31.
 PLEASE SEE 422.13 AS THE LOADS MUST BE SHOWN AT 125%
 ALONG WITH THE MINIMUM SIZE OF THE CIRCUIT.
 PLEASE REVISE.
  
 3) NOTE: PLEASE SEE THE ATTACHED ENERGY CALCULATIONS
 CONTAIN A RAISED SEAL OVER A PHOTO-0COPIED SIGNATURE
 WHICH IS NOT PERMITTED UNDER FS 471.025.
 WHEN AN ENGINEER AFFIX?S HIS/HER SEAL TO ANY DOCUMENT,
 THE SIGNATURE AND DATE MUST BE ORIGINAL.
 PLEASE VERIFY THE CODE/METHOD FOR ENERGY CALCULATIONS.
  
  
 4) NOTE: PLEASE PROVIDE AN ELECTRICAL RISER DIAGRAM
 INDICATING THE SERVICE WHICH WILL BE FEEDING THIS NEW
 TRAILER ALONG WITH SERVICE CONDUCTORS, OVER CURRENT
 PROTECTION, MAINS, GROUNDING AT SERVICE AND TRAILER,
 CONDUITS, ETC.
 COMPLETE RISER.
 310.16, 230.70, 230.71, 250.50 ETC.
  
 ** PLEASE SEE ANY FIRE REVIEW COMMENTS FOR REQUIRED
 EMERGENCY LIGHTING WHICH MAY BE REQUIRED PER 2003 LS
 7.8/7.9
 THIS WOULD AFFECT PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-26 Cont ID  
Sent By mawillia Date 2007-04-26 Time 18:11 Rev Time 0.00
Received By mawillia Date 2007-04-26 Time 17:11 Sent To  
Notes
2007-04-26 18:09:43*****DENIED*****
  
  
 1.FIRE DEPARTMENT ACCESS ROAD SHALL BE DESIGNED AND
 MAINTAINED TO SUPPORT THE IMPOSED LOADS OF FIRE
 APPARATUS AND SHALL BE PROVIDED WITH A SURFACE SUITABLE
 FOR ALL-WEATHER DRIVING CAPABILITIES.
  
 2.DEAD-END FIRE DEPARTMENT ACCESS ROADS IN EXCESS OF
 150 FEET IN LENGHT SHALL BE PROVIDED WITH APPROVED
 PROVISIONS FOR TURNING THE APPARATUS AROUND.
  
 3.SHOW THE LOCATION OT THE NEAREST FIRE HYDRANT TO
 THIS STRUCTURE.
  
 4.THE INSTALLATION AND/OR ERECTING OF THE TEMPORARY
 STRUCTURE SHALL IN NO WAY HINDER OR OBSTRUCT EMERGENCY
 RESPONSE ACCESS TO THE SAID PROPERTY OR VICINITY
 THEREOF (INCLUDING ROADS, STREETS, AND FIRE LANES).
  
 5.THE STRUCTURE SHALL HAVE APPROVED ADDRESS NUMBERS
 PLACED IN A POSITION TO BE PLANILY LEGIBLE AND VISIBLE
 FROM THE STREET OR ROAD FRONTING THE PROPERTY.AS PER
 WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH. IN THE
 EVENT THAT THE ADDRESS CANNOT BE SEEN FROM EXECUTIVE
 CENTER DRIVE (DUE TO THE STRUCTURE'S SET-BACK), A
 MARKEE WITH THE ADDRESS WILL BE REQUIRED IN ADDITION TO
 THAT ON THE STRUCTURE.
  
 6.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) FOR THE STRUCTURE.
  
 7.NO EMERGENCY LIGHTING NOTED.ALTHOUGH NOT A
 REQUIREMENT DUE TO THE SIZE OF THE STRUCTURE, IT IS
 RECOMMENDED THAT EMERGENCY LIGHTING BE PROVIDED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2007-04-17 Time 13:57 Sent To  
Notes
2007-04-17 14:01:40TO "COMM" BD#17

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-30 Cont ID  
Sent By mperson Date 2007-04-30 Time 16:18 Rev Time 0.00
Received By mperson Date 2007-04-30 Time 16:18 Sent To  
Notes
2007-04-30 16:40:55DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTION/INFORMATION IS REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 1 OF 1 IS INDICATING A 250 GAL. WASTE WATER
 HOLDING TANK. PLEASE SUBMIT APPROVAL FROM PALM BEACH
 COUNTY HEALTH DEPARTMENT OF SAID HOLDING TANK.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-02 Cont ID  
Sent By jroach Date 2007-05-02 Time 15:02 Rev Time 0.00
Received By jroach Date 2007-05-02 Time 14:58 Sent To  
Notes
2007-05-02 15:14:17***FAILED***
  
 1) STRIPING DETAIL SHALL BE PROVIDED FOR THE REGULAR
 AND HANDICAP PARKING SPACE.STRIPING SHALL CONFORM TO
 THE REQUIREMENTS OF ARTICLE XV OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS
  
 2) THE ACCESS DRIVE FROM EXECUTIVE CENTER DRIVE SHALL
 BE CONSTRUCTED OF RECYCLED CONCRETE, IN ACCORDANCE WITH
 PLANNING BOARD CASE NO. 1242F (MINOR AMENDMENT).
  
 3) THE PROPOSED SIGN SHALL BE SUBMITTED UNDER A
 SEPARATE PERMIT.
  
 AS REQUIRED BY SECTION 94-273 OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS, THE FOLLOWING SHALL BE
 NOTED AND WILL BE CONDITIONS ASSOCIATED WITH THE
 PERMIT:
  
 1) SALES OFFICES NOT LOCATED IN MODEL HOMES ARE
 PERMITTED BUT SHALL BE USED ONLY BY THE FIRMS AND THEIR
 AGENTS CONSTRUCTING OR MARKETING DWELLING UNITS WITHIN
 A DEVELOPMENT OR PROJECT.
  
 2) TEMPORARY SALES OFFICES NOT IN MODEL DWELLING UNITS
 SHALL NOT BE USED FOR MORE THAN 18 MONTHS AND SHALL BE
 REMOVED AT THE END OF THAT PERIOD.
  
 3) TEMPORARY MODEL DWELLING UNITS, SALES OFFICES AND
 SIGN SHALL NOT BE ILLUMINATED OR USED FOR ANY BUSINESS
 ACTIVITY LATER THAN 9:00 P.M.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  