| 2007-04-22 08:32:23 | ** UNSAT ** |
| | |
| | ** PLEASE SEE ANY REFERENCES TO CHAPTER 1 OF THE FBC |
| | ARE THE ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY |
| | OF WEST PALM BEACH. |
| | |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. THIS |
| | WOULD INCLUDE REQUIRED CODES ON TRADE SHEETS. PLEASE |
| | KNOW THERE ARE CHANGES IN THE FBC WHICH MAY AFFECT |
| | DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3(4) FOR ANY |
| | FA DEVICES FOR ADA COMPLIANCE WHICH MAY BE REQUIRED TO |
| | BE CHANGED OR INSTALLED. |
| | PLEASE SEE REVIEWS FROM OTHER TRADES,( FIRE MARSHAL) IF |
| | ANY WORK TO THESE EXISTING SYSTEMS ARE TAKING PLACE, |
| | THIS BASE INFORMATION SHALL BE INCLUDE ON THESE BASE |
| | PLANS EVEN WHEN THESE SYSTEMS ARE UNDER SEPARATE |
| | PERMIT. |
| | FBC 106.3.5.1.2 |
| | |
| | 3) NOTE: PLEASE SEE 13-101. |
| | PLEASE SEE MANY SEPARATE SPACE AREAS DO NOT INDICATE |
| | ANY REQUIRED LIGHTING CONTROL PER 13-415.1.ABC.1.1, |
| | .1.2. |
| | PLEASE INDICATE TIMES ON ALL DEVICES BEING USED TO |
| | CONTROL OR OVER RIDE LIGHTING. PLEASE SEE SOME OF THE |
| | DEVICES AS SHOWN ARE OK, HOWEVER PLEASE ALSO INDICATE |
| | TIMES ON SYMBOL LEGEND FOR SPECIFIC DEVICE.(TIME AS |
| | NOTED ON 2.1 DETAIL) |
| | PLEASE CLARIFY FIXTURES, AS PLANS SHOW THAT THESE ARE |
| | NEW TO BE INSTALLED, HOWEVER NO INFORMATION FOR TYPE, |
| | WATTAGE ETC IS SHOWN. PLEASE SEE 13-415.1.ABC.3. ONE |
| | NOTE ON PLANS MENTIONS TO RE-LAMP EXISTING AND TO SEE |
| | THE FIXTURE SCHEDULE FOR DETAILS, HOWEVER NO FIXTURE |
| | SCHEDULE ETC WAS SUBMITTED TO VERIFY COMPLIANCE. PLEASE |
| | INDICATE THE NUMBER OF FIXTURES IN THE FIXTURE LEGEND |
| | FOR EACH AND COORDINATE WITH THE PERFORMANCE |
| | CALCULATIONS WHICH ARE TO BE SUBMITTED. |
| | FBC CHAPTER 13, 13-415.2, 13-415.1.AB.1.1, 13-415.1.C ? |
| | ETC |
| | |
| | 4) NOTE:PLEASE SEE PERMIT APPLICATION IS ONLY FOR |
| | TENANT SPACE 212, HOWEVER ELECTRICAL RISER SHOWS WORK |
| | FOR SPACE 220, OR RATHER SOME OF THE ELECTRICAL FEEDING |
| | SPACE 220 BEING LOCATED IN THIS TENANT SPACE WHICH IS |
| | NOT PERMITTED. |
| | PLEASE ALSO SEE THE TITLE BLOCKS INDICATE UNIT/SUITE |
| | #20? (MISPRINT) |
| | PLEASE SEE AS PERMIT APPLICATION IS FOR SUITE #212 AND |
| | PLANS INDICATE 210, 20 AND 220, LOCATION FOR SCOPE IS |
| | NOT CLEAR. |
| | PLEASE CLARIFY SERVICE. |
| | IF THIS WAS TWO TENANT SPACES BEING MADE INTO ONE, THEN |
| | ONLY ONE METER WILL BE PERMITTED AND SERVICE WILL BE |
| | FROM ONE METER ONLY. |
| | PLEASE SEE THE LOCATIONS OF THE TRANSFORMERS ARE NOT |
| | SHOWN TO VERIFY COMPLIANCE FOR SPACE INSTALLATIONS PER |
| | 450.9, 450.13, 110.26, ETC. |
| | CAN NOT VERIFY TAPS PER 240.21 |
| | PLEASE SEE THE #8 AS SHOWN ARE NOT OF SUFFICIENT SIZE |
| | FOR THE 60AMP DISCONNECTS AND OVER CURRENT PROTECTION |
| | AS SHOWN.240.4, 310.16, 110.14 |
| | PLEASE SEE THAT RISER MAY BE CHANGING AS COMPLETE SCOPE |
| | OF WORK ETC IS NOT CLEAR AT THIS TIME. |
| | |
| | 5) NOTE: PLEASE SEE PLANS INDICATE A NEW *TELCO* ROOM |
| | WITH NEW DEDICATED A/C BEING INSTALLED FOR THIS ROOM. |
| | 645.4, 645.5 ETC. |
| | PLEASE CLARIFY USE AND NFPA-75 FOR IT ROOMS AND |
| | REQUIRED DISCONNECTING MEANS FOR EQUIPMENT PER 645.10? |
| | WHAT EQUIPMENT WILL BE LOCATED IN THIS ROOM? |
| | RISK CONSIDERATIONS PER CHAPTER 2 OF NFPA-75 |
| | |
| | |
| | ** PLEASE PROVIDE MORE DETAIL AS THERE ARE SOME ITEMS |
| | NOT CLEAR AT THIS TIME ON PLANS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |