Plan Review Details - Permit 07040513
Plan Review Stops For Permit 07040513
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-10-10 Cont ID  
Sent By jwitmer Date 2007-10-10 Time 12:53 Rev Time 0.55
Received By jwitmer Date 2007-10-10 Time 12:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-06-20 Cont ID  
Sent By jwitmer Date 2007-06-13 Time 10:43 Rev Time 0.00
Received By jwitmer Date 2007-06-13 Time 09:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-01 Cont ID  
Sent By dpalmer Date 2007-10-01 Time 12:59 Rev Time 0.00
Received By dpalmer Date 2007-10-01 Time 12:59 Sent To  
Notes
2007-10-01 12:59:22** PROVISO/REVISION REQUIRED ***
  
 1) NOTE: PLEASE KNOW SINCE THE DATE OF THE PREVIOUS
 REVIEW IT HAS BEEN CONFIRMEDWITH THE STATE OF FLORIDA
 AND BY THE DEFINITIONS SET FORTH IN FBC CHAPTER 13 AND
 FBC, THAT THE METHOD *A* AS SUBMITTED CAN NOT BE USED.
  
 THE CALCULATIONS SUBMITTED ARE FOR *WHOLE BUILDING *
 WHICH THIS TENANT BUILD OUT SPACE IS NOT.
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2
 PLEASE KNOW THESE WILL BE REQUIRED BEFORE ANY ROUGH
 ELECTRICAL INSPECTION. LIGHTING LEVELS HAVE NOT BEEN
 CONFIRMED BASED ON USE OF ROOMS OR AREAS AND ANY
 INSTALLATION OF NEW LIGHTING FIXTURES WILL BE *AT RISK*
 UNTIL LIGHTING LEVELS CAN BE CONFIRMED TO COMPLY.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW, IF
 THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-01 Cont ID  
Sent By dpalmer Date 2007-08-01 Time 11:10 Rev Time 0.00
Received By dpalmer Date 2007-07-31 Time 20:26 Sent To  
Notes
2007-08-01 11:11:06** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING ALONG WITH NEW COMMENTS
 WITH RESPECT TO CHANGES MADE TO PLANS.
  
  
 1) NOTE: PLEASE SEE THE RESPONSE LETTER MENTIONS TO SEE
 E1.2 FOR NOTES PERTAINING TO ADA LEVELS FOR HORNS AND
 STROBES, HOWEVER ONLY A NOTE FOR THE DB LEVELS COULD BE
 LOCATED ON THIS PAGE.
 PLEASE SEE THE SYMBOL LEGEND DOES CONTAIN THE LEVELS OF
 75 CD FOR THE STROBES, HOWEVER ALSO STATES UNLESS OTHER
 WISE NOTED. PLEASE VERIFY IF INDEED THERE WAS GOING TO
 BE A NOTE PLACE ON E1.2 FOR CD LEVELS?
 FBC 11-4.28.1, .2 AND .3(4) FOR ANY FA DEVICES FOR ADA
 COMPLIANCE WHICH MAY BE REQUIRED TO BE CHANGED OR
 INSTALLED.
  
 3) NOTE: PLEASE SEE THERE ARE A FEW *SEPARATE SPACES*
 AND WHAT APPEARS AS ACCENT LIGHTING IN ONE ROOM. PLEASE
 SEE REDLINED PLANS. 13-415.1.ABC.1.1, .1.2, .1.3.
 PLEASE SEE SOME OF THESE DEVICES ARE STILL BEING SHOWN
 AS STANDARD SWITCHES.
 PLEASE BE SURE THE *OWNER AGENT* IS SIGNED AND DATED ON
 THE CERTIFICATIONS SHEET OF THE ENERGY CALCULATIONS AS
 SUBMITTED.
 13-103.1.1.1.1.
  
 4) NOTE:PLEASE SEE THE RISER HAS NOW CHANGED. PLEASE
 SEE THE RISER NOW SHOWS TAPPED CONDUCTORS FOR THE
 200AMP MAIN. PLEASE SEE THE LOCATION OF THE PANELS
 WHICH THE TAPPED CONDUCTORS ARE FEEDING EXCEED THE
 DISTANCE PERMITTED OF TAPPED CONDUCTORS PER 240.21.
 PLEASE ALSO SEE THAT ANY TAPPED CONDUCTORS MUST
 TERMINATE IN OVER CURRENT PROTECTION ALSO AS REQUIRED
 IN 240.21.
 THESE PANELS ARE BOTH SHOWN AS MLO AND DO NOT CONTAIN
 OCP AND ARE TOO FAR WAY.
 PLEASE SEE 240.4, 310.16, AND 240.21 ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 5) NOTE:PLEASE KNOW THAT CLARIFICATION IS STILL
 NEEDED ON THE *TELCO* ROOM. RESPONSE LETTER MENTIONS
 THIS IS NOT CONSIDERED AS IT IS A SINGLE TENANT HOWEVER
 THE CLASSIFICATIONS ARE BASED ON SEVERAL OTHER FACTORS
 IN NFPA-75 AND NEC 645.
 PLEASE PROVIDE MORE INFORMATION ON EQUIPMENT WHICH IS
 BEING INSTALLED IN ROOM.
 PLEASE SEE THE DISCONNECTING MEANS WHICH WAS ADDED TO
 THE AC EQUIPMENT HOWEVER 645 REQUIRES A CERTAIN TYPE OF
 SHUT OFF. PLEASE ALSO CLARIFY THE DISCONNECTING MEANS
 WHICH MAY BE REQUIRED FOR THE OTHER OUTLETS WHICH FEEDS
 UNKNOWN EQUIPMENT AT THIS TIME.
 PLEASE KNOW THAT THE ROOM MAY BE REQUIRED TO CONTAIN A
 MINIMUM RATING OF 1HR IF APPLICABLE.
  
 ** PREVIOUS NOTE FOR REFERENCE ONLY.**
 PLEASE SEE PLANS INDICATE A NEW *TELCO* ROOM WITH NEW
 DEDICATED A/C BEING INSTALLED FOR THIS ROOM. 645.4,
 645.5 ETC.
 PLEASE CLARIFY USE AND NFPA-75 FOR IT ROOMS AND
 REQUIRED DISCONNECTING MEANS FOR EQUIPMENT PER 645.10?
 WHAT EQUIPMENT WILL BE LOCATED IN THIS ROOM?
 RISK CONSIDERATIONS PER CHAPTER 2 OF NFPA-75
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-31 20:26:22IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-22 Cont ID  
Sent By dpalmer Date 2007-04-22 Time 08:31 Rev Time 0.00
Received By dpalmer Date 2007-04-22 Time 07:48 Sent To  
Notes
2007-04-22 08:32:23** UNSAT **
  
 ** PLEASE SEE ANY REFERENCES TO CHAPTER 1 OF THE FBC
 ARE THE ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY
 OF WEST PALM BEACH.
  
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. THIS
 WOULD INCLUDE REQUIRED CODES ON TRADE SHEETS. PLEASE
 KNOW THERE ARE CHANGES IN THE FBC WHICH MAY AFFECT
 DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3(4) FOR ANY
 FA DEVICES FOR ADA COMPLIANCE WHICH MAY BE REQUIRED TO
 BE CHANGED OR INSTALLED.
 PLEASE SEE REVIEWS FROM OTHER TRADES,( FIRE MARSHAL) IF
 ANY WORK TO THESE EXISTING SYSTEMS ARE TAKING PLACE,
 THIS BASE INFORMATION SHALL BE INCLUDE ON THESE BASE
 PLANS EVEN WHEN THESE SYSTEMS ARE UNDER SEPARATE
 PERMIT.
 FBC 106.3.5.1.2
  
 3) NOTE: PLEASE SEE 13-101.
 PLEASE SEE MANY SEPARATE SPACE AREAS DO NOT INDICATE
 ANY REQUIRED LIGHTING CONTROL PER 13-415.1.ABC.1.1,
 .1.2.
 PLEASE INDICATE TIMES ON ALL DEVICES BEING USED TO
 CONTROL OR OVER RIDE LIGHTING. PLEASE SEE SOME OF THE
 DEVICES AS SHOWN ARE OK, HOWEVER PLEASE ALSO INDICATE
 TIMES ON SYMBOL LEGEND FOR SPECIFIC DEVICE.(TIME AS
 NOTED ON 2.1 DETAIL)
 PLEASE CLARIFY FIXTURES, AS PLANS SHOW THAT THESE ARE
 NEW TO BE INSTALLED, HOWEVER NO INFORMATION FOR TYPE,
 WATTAGE ETC IS SHOWN. PLEASE SEE 13-415.1.ABC.3. ONE
 NOTE ON PLANS MENTIONS TO RE-LAMP EXISTING AND TO SEE
 THE FIXTURE SCHEDULE FOR DETAILS, HOWEVER NO FIXTURE
 SCHEDULE ETC WAS SUBMITTED TO VERIFY COMPLIANCE. PLEASE
 INDICATE THE NUMBER OF FIXTURES IN THE FIXTURE LEGEND
 FOR EACH AND COORDINATE WITH THE PERFORMANCE
 CALCULATIONS WHICH ARE TO BE SUBMITTED.
 FBC CHAPTER 13, 13-415.2, 13-415.1.AB.1.1, 13-415.1.C ?
 ETC
  
 4) NOTE:PLEASE SEE PERMIT APPLICATION IS ONLY FOR
 TENANT SPACE 212, HOWEVER ELECTRICAL RISER SHOWS WORK
 FOR SPACE 220, OR RATHER SOME OF THE ELECTRICAL FEEDING
 SPACE 220 BEING LOCATED IN THIS TENANT SPACE WHICH IS
 NOT PERMITTED.
 PLEASE ALSO SEE THE TITLE BLOCKS INDICATE UNIT/SUITE
 #20? (MISPRINT)
 PLEASE SEE AS PERMIT APPLICATION IS FOR SUITE #212 AND
 PLANS INDICATE 210, 20 AND 220, LOCATION FOR SCOPE IS
 NOT CLEAR.
 PLEASE CLARIFY SERVICE.
 IF THIS WAS TWO TENANT SPACES BEING MADE INTO ONE, THEN
 ONLY ONE METER WILL BE PERMITTED AND SERVICE WILL BE
 FROM ONE METER ONLY.
 PLEASE SEE THE LOCATIONS OF THE TRANSFORMERS ARE NOT
 SHOWN TO VERIFY COMPLIANCE FOR SPACE INSTALLATIONS PER
 450.9, 450.13, 110.26, ETC.
 CAN NOT VERIFY TAPS PER 240.21
 PLEASE SEE THE #8 AS SHOWN ARE NOT OF SUFFICIENT SIZE
 FOR THE 60AMP DISCONNECTS AND OVER CURRENT PROTECTION
 AS SHOWN.240.4, 310.16, 110.14
 PLEASE SEE THAT RISER MAY BE CHANGING AS COMPLETE SCOPE
 OF WORK ETC IS NOT CLEAR AT THIS TIME.
  
 5) NOTE: PLEASE SEE PLANS INDICATE A NEW *TELCO* ROOM
 WITH NEW DEDICATED A/C BEING INSTALLED FOR THIS ROOM.
 645.4, 645.5 ETC.
 PLEASE CLARIFY USE AND NFPA-75 FOR IT ROOMS AND
 REQUIRED DISCONNECTING MEANS FOR EQUIPMENT PER 645.10?
 WHAT EQUIPMENT WILL BE LOCATED IN THIS ROOM?
 RISK CONSIDERATIONS PER CHAPTER 2 OF NFPA-75
  
  
 ** PLEASE PROVIDE MORE DETAIL AS THERE ARE SOME ITEMS
 NOT CLEAR AT THIS TIME ON PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-10-10 Cont ID  
Sent By mawillia Date 2007-10-10 Time 13:41 Rev Time 0.00
Received By mawillia Date 2007-10-10 Time 13:23 Sent To  
Notes
2007-10-10 13:41:37*****APPROVED******
  
  
 PLAN SHEETS A-1, E1.1, AND E1.2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-08-30 Cont ID  
Sent By mawillia Date 2007-08-30 Time 14:59 Rev Time 0.00
Received By mawillia Date 2007-08-30 Time 14:45 Sent To  
Notes
2007-08-30 14:57:11*****PROVISO******
  
  
 THE APPROPIATE PLAN SHEETS (A-1, E1.1, AND E1.2) TO BE
 FIRE-STAMPED WHEN ALL OTHER REVIEWS HAVE BEEN
 SATISFIED.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-14 Cont ID  
Sent By mcarsill Date 2007-06-14 Time 10:56 Rev Time 0.00
Received By mcarsill Date 2007-06-14 Time 10:41 Sent To  
Notes
2007-06-14 10:56:101. CONSTRUCTION AND RENOVATION WORK TO COMPLY WITH NFPA
 241.
  
 2. NO FIRE SPRINKLER PLANS PROVIDED WITH DRAWINGS.
  
 3. NOTES ON PLANS ARE TO BE FOLLOWED WITH REGARDS TO
 SAFETY CONSTRUCTION RELATED TO CONSTRUCTION
 ACTIVITIES.
  
 4. AS NOTED ON THE DRAWINGS, SEPERATE PLANS AND PERMITS
 REQUIRED FOR FIRE ALARM SYSTEM ADDITIONS.
  
 5. ALL WORK SUBJECT TO FIELD INSPECTION AND APPROVAL.
  
 MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-10 Cont ID  
Sent By adarroug Date 2007-09-10 Time 10:23 Rev Time 0.00
Received By adarroug Date 2007-09-10 Time 10:23 Sent To  
Notes
2007-10-01 09:40:36TO "COMM" BD#29
2007-09-10 10:23:34WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-18 Cont ID  
Sent By adarroug Date 2007-07-18 Time 10:50 Rev Time 0.00
Received By adarroug Date 2007-07-18 Time 10:50 Sent To  
Notes
2007-07-27 11:53:18TO "COMM" BD#1
2007-07-18 10:50:21WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-20 Cont ID  
Sent By jwitmer Date 2007-06-14 Time 10:43 Rev Time 0.00
Received By jwitmer Date 2007-04-17 Time 14:53 Sent To  
Notes
2007-04-17 14:55:17TO "COMM" BD#22

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-10-09 Cont ID  
Sent By rregueir Date 2007-10-09 Time 10:40 Rev Time 0.00
Received By rregueir Date 2007-10-09 Time 10:01 Sent To  
Notes
2007-10-09 10:40:14REVIEW #: 3
 ACTION: PASSED
  
 CONTRACTOR CAME IN AND REPLACED MECHANICAL AND
 ELECTRICAL SHEETS WHICH WERE NOT SIGNED, SEALED AND
 DATED BY THE DESIGNERS OF RECORD.
  
 RJR

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-08-05 Cont ID  
Sent By rregueir Date 2007-08-05 Time 11:02 Rev Time 0.00
Received By rregueir Date 2007-08-05 Time 10:25 Sent To  
Notes
2007-08-05 11:02:13--------------DENIED-----------------
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 REVISIONS
 FBC CH. AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 2ND REVIEW:
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS FOR THE PURPOSE OF CONTNUITY.
  
 1. FIRE DAMPERS ARE TO BE INSTALLED IN ACCORDANCE WITH
 THE REQUIREMENTS OF FBC,M SEC 607 AND THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AND LISTING.
 ALSO, PLAN INDICATES 6 INCH ROUND FLEX DUCT ATTACHING
 TO FIRE DAMPER AT NEW TENANT SEPARATION WALL. THIS
 SCENARIO IS NOT ADDRESSED IN INSTALLATION DETAIL AS
 SHOWN ON PLANS AND IS LIKELY NOT ALLOWED PER
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. ALSO, THIS
 WOULD NOT ALLOW FOR A DUCT ACCESS DOOR AS REQUIRED PER
 FBC,M 607.4. PLEASE CLARIFY HOW THIS DAMPER IS TO BE
 INSTALLED AND CONNECTED TO DUCT IN A MANNER WHICH IS IN
 COMPLIANCE WITH FIRE DAMPER INSTALLATION ISTRUCTIONS
 AND THIS SECTION OF THE CODE.
  
 2. OK
  
 3. OK
  
 4. OK
  
 5. MANUFACTURER'S INSTALLATION INSTRUCTIONS WERE
 REQUESTED ON PREVIOUS REVIEW. HOWEVER, THEY WERE NOT
 PROVIDED WITH THIS SUBMITTAL. PLEASE PROVIDED ALL
 REQUESTED SUPPORTING DOCUMENTATION FOR REVIEW WITH NEXT
 SUBMITTAL PER FBC 106.1.1 THROUGH 106.1.3.
  
 IF YOU HAVE ANY QUESTION PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-02 Cont ID  
Sent By rregueir Date 2007-05-02 Time 08:25 Rev Time 0.00
Received By rregueir Date 2007-05-01 Time 14:24 Sent To  
Notes
2007-05-02 08:25:06-------------DENIED--------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
 FBC CHAPTER 1 AS AMENDED BY THE CITY OF WEST PALM
 BEACH
  
  
 1. PLEASE SHOW DUCTS WHICH WILL PENETRATE NEW TENANT
 SEPARATION WALL TO BE PROTECTED BY FIRE DAMPERS OR AN
 APPROVED THROUGH-PENETRATION FIRESTOP SYSTEM (SEE FBC
 712.3.3) IN ACCORDANCE WITH FBC,M 607 5.3.
  
 2. RETURN GRILL ON SCHEDULE CALLS FOR NOTE (10) BUT
 NOTE (10) IS NOT GIVEN ON PLAN. PLEASE CLARIFY.
  
 3. SPLIT SYSTEM SCHEDULE: AHU-T/CU-T CALLS FOR NOTES
 (1)(2)(3). ONLY NOTE (1) IS GIVEN. PLEASE CLARIFY.
  
 4. THREE FIRE DAMPERS WHICH APPEAR ON DEMOLITION PLAN
 DO NOT APPEAR ON NEW PLAN. PLEASE COORDINATE DRAWINGS,
 SHOWING ALL ITEMS TO BE REMOVED ON DEMOLITION PLAN.
  
 5. PLEASE PROVIDE INSTALLATION INSTRUCTIONS FOR
 MINI-SPLIT SYSTEM SHOWING MAXIMUM ALLOWED LENGTH AND
 REQUIRED SIZE OF COPPER LINES. ALSO PLEASE VERIFY
 MAXIMUM ALLOWED ELEVATION DIFFERENCE BETWEEN AHU AND
 CU. PLEASE SHOW LOCATION/ROUTING OF REFRIGERANT LINES
 FROM SPACE TO ROOF. FBC 106.1.1, FBC 106.1.3
  
 REVIEWED BY: RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-08-28 Cont ID  
Sent By kstevens Date 2007-08-28 Time 12:17 Rev Time 0.00
Received By kstevens Date 2007-08-28 Time 12:17 Sent To  
Notes
2007-08-28 12:18:56 
  
 PASSED/PROVISO
 WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES, NOT IN THE CEILING AS SHOWN. PDI-WH 201 &
 MANUF. INSTALLATION INSTRUCTIONS.

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-05-31 Cont ID  
Sent By kstevens Date 2007-05-31 Time 10:24 Rev Time 0.00
Received By kstevens Date 2007-05-31 Time 10:24 Sent To  
Notes
2007-05-31 10:25:27 
  
  
 PASSED/PROVISO
  
 THE APPLICATION SHALL INDICATE THE SUITE NUMBER SHOWN
 ON THE PLANS

Review Stop Z ZONING
Rev No 3 Status P Date 2007-09-24 Cont ID  
Sent By jroach Date 2007-09-24 Time 22:34 Rev Time 0.00
Received By jroach Date 2007-09-24 Time 22:33 Sent To  
Notes
2007-09-24 22:36:19***PASSED***
  
 1) SCOPE OF WORK IS NOT AFFECTING ANY ZONING
 ISSUES...THEREFORE THE PLANS DO NOT REQUIRE A ZONING
 STAMP.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-08-13 Cont ID  
Sent By jroach Date 2007-08-13 Time 09:24 Rev Time 0.00
Received By jroach Date 2007-08-13 Time 09:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2007-05-03 Cont ID  
Sent By jroach Date 2007-05-03 Time 16:51 Rev Time 0.00
Received By jroach Date 2007-05-03 Time 16:51 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved