Plan Review Details - Permit 07040489
Plan Review Stops For Permit 07040489
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-03 Cont ID  
Sent By jgomez Date 2007-05-03 Time 16:59 Rev Time 0.00
Received By jgomez Date 2007-05-03 Time 16:59 Sent To PC
Notes
2007-05-03 16:59:49BUILDING REVIEW CHECKLIST:
 1- PROVIDERECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
  
 2- PAY IMPACT FEES TO PALM BEACH COUNTY.AFTER PLANS
 ARE REVISED, BRING THEM TO PALM BEACH COUNTY,
 (561)233-5115,BRING BACK STAMPED PLANS AND COPY OF
 PAID RECEIPT.
  
 3- SOIL TEST REPORT:
 A) PROVIDE TWO COPIES WITH ORIGINAL SEAL, SIGNATURE
 AND DATE AS REQUIRED BY SEC.61G15-23.002 OF FLORIDA
 ADMINISTRATIVE CODE.
  
 B) INDICATE IN ALL SHEETS ENGINEERING FIRM
 CERTIFICATE OFAUTHORIZATION NUMBER AS REQUIRED BY
 SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE CODE.
  
 4- PROVIDE DRAINAGE PLAN AS REQUIRED BY SEC. R401.3 OF
 2004 FLORIDA RESIDENTIAL CODE.
 ***NOTE: WATER SHALL BE DIVERTED AWAY FROMNEIGHBOR'S
 PROPERTY.
  
 5- PROVIDE COMPLETE DETAILS AND SPECS SHOWING HOW TO
 KEEP CONTINUITY OF TIE BEAMAT WINDOW OPENING LOCATED
 IN THE STAIRWAY. SEE LEFT SIDE ELEVATION ON SHEET A-2.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 6- AFTER PLANS ARE REVISED, BRING THEM BACK TO FIFTH
 FLOOR FOR HISTORICAL APPROVAL STAMP PRIOR TO SUBMITTAL
 TO THIS OFFICE.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) CUSTOM ENTRY DOOR AS SHOWN ON PLANS. SEE PLANS
 FOR HEIGHT AND SHAPE.
  
 B) FRENCH DOORS. INFORMATIONSUBMITTED IS MISSING
 THE DRAWINGS.
  
 C) PRECAST LINTELS.
  
 D) EXTERIOR SIDE GARAGE SWING DOOR.
  
 E) GARAGE DOOR.INFORMATIONSUBMITTED IS MISSING
 THE DRAWINGS.
  
 F) FLAT ROOF:
 * NEED TO SPECIFY SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED.CIRCLED ASSEMBLY ON PAGE 18 OF 19 IF FOR
 TILE UNDERLAYMENT ONLY. NEED SPECIFIC ASSEMBLY FOR FLAT
 ROOF INSTALLATION.
 ** IF MORE THAN ONE FASTENING OPTION IS SHOWN ON
 SELECTED ASSEMBLY, THEN SPECIFY FASTENING OPTION.
 *** PROVIDE RAS 117 CALCULATIONS FOR ENHANCED
 FASTENING AT PERIMETER AND CORNER AREAS AS REQUIRED BY
 GENERAL LIMITATION #7. SEE GENERAL LIMITATION #7 ON
 SHEET 19 OF 19 OF NOA 04-0506.03 SUBMITTED.
 **** NOTE: KEEP IN MIND THAT NOA 04-0506.03 EXPIRES ON
 MAY 23RD, 2007.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004
  
 9- ENERGY CALCULATIONS:
 A) NEED TO USE REVISED FORM 600A-2004 R.
  
 B) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP
 OF FORM.
  
 C) IF THIS IS NOT WORST CASE SCENARIO, THEN
 CALCULATIONS MUST BE DONE TO THE SPECIFIC ORIENTATION
 OF THE HOUSE. SEE SURVEY FOR CORRECT ORIENTATION AND
 REVISE AS REQUIRED.
  
 D) REVISE/CLARIFY WALL TYPES.WHICH ONE ARE THE
 CONCRETEINTERIOR WALLS AND WHICH ARE THE CONCRETE
 EXTERIOR WALLS. SEE PLANS.
  
 E) PROFESSIONAL WHO SIGNED AND SEALEDTHE ENERGY
 CALCULATIONS NEED TO PROVIDE ALL HIS/HERINFORMATION
 AS REQUIRED BY CHAPTER 481 AND CHAPTER 471 OF FLORIDA
 STATUTES.
  
 F) OVERHANG LENGTH AND HEIGHT IS INCORRECT. REVISE
 AS REQUIRED. IT CAN'T BE ZERO. SEE PLANS AND REVISE AS
 REQUIRED.
  
 10- SHEET T-1:
 A)BUCK DETAILS: SPECIFY HOW MUCH EMBEDMENT IS
 REQUIRED FOR SPECIFIED TAPCONS.SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 B) REVISE WINDOW BUCK DETAIL. SEE SEC. R613.6.2 OF
 2004 FLORIDARESIDENTIAL CODE FOR PROPER WAY OF
 INSTALLINGSTRUCTURAL BUCKS.
  
 C) REVISE PROJECT DESIGN INFORMATION. THERE IS NOT
 FBCSEC. 1606.1.7 . SEE FBC 2004 ALONG WITH REVISIONS.
 ON THE OTHER HAND,CODE TO REFERENCE IS THE FLORIDA
 RESIDENTIAL CODE OF 2004.SEE SEC. R301 AND TABLE
 R301.5 OF FLORIDA RESIDENTIAL CODE 2004 AND SPECIFY ALL
 LOADS, INCLUDING LIVE AND DEAD LOADS.
 ALSO, WHAT'S WIND SPEED (V)?.
  
 11- BEDROOM WINDOW SINGLE HUNG 24 DOESN'TCOMPLY WITH
 EGRESS REQUIREMENTS OF SEC. R310.1 OF 2004 FLORIDA
 RESIDENTIAL CODE. REVISE AS REQUIRED.
  
 12- STAIRCASE:
 A) PROVIDE COMPLETE INFORMATION AS REQUIRED BY SEC
 R311.5.3 AND SEC. R311.6 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 B) SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R602.1.2
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 13- PROVIDE COMPLETE INFORMATION FOR BALCONY GUARDRAIL
 AS REQUIRED BY SEC. R312 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 14- PROVIDE SPECIFICATIONS FOR GARAGE INTERIOR DOOR AND
 CEILING CONSTRUCTION AS REQUIRED BY SEC. R309 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 15- PROVIDE FIREPLACE SPECS AND LISTING AS REQUIRED BY
 SEC. R1002 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 16- PROVIDE DIMENSIONS FOR BALCONY.
  
 17- SHEET A-2:
 A) CLARIFY CONSTRUCTION AT BOTTOM OF CHIMNEY.LEFT
 SIDE ELEVATION SHOWS CANTILEVERED FIREPLACE.REVISE AS
 REQUIRED.
  
 B) PROVIDE COMPLETE INFORMATION ON SECTION AT GARAGE
 ROOF. NEED TO SPECIFY ALL FASTENERS. IS THIS A
 CANTILEVERED ROOF? . SECTION 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 18- SPECIFY HOW MANY NAILS ARE REQUIRED FOR THE ROOF
 TILE.ALSO, CLARIFY IF SUING POLY FOAM OR NAILS OR
 BOTH. THERE WAS A PRODUCT APPROVAL SUBMITTED FOR
 POLYFOAM. CLARIFY AS REQUIRED.
  
 19- SHEET A-3:
 A) PROVIDE COMPLETE SPECS FOR BALCONY CONSTRUCTION.
 NEED HANDRAIL INFORMATION AND BALCONY FLOOR COMPLETE
 SPECIFICATIONS. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 B) PROVIDE COMPLETE SPECIFICATIONS FORFRAMED WALL
 AT ROOF AREA. SEE SECTION 11/A-3.SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 C) REVISE FURRING SPECS ON WALL SECTIONS TO MATCH.
 SOME SECTIONS CALLS 16" O.C. SPACING WHILE OTHER
 SECTIONS CALL FOR 24"O.C. SPACING.
  
 20 PROVIDE COMPLETE SPECIFICATIONS SHOWING COMPLIANCE
 WITH VENTILATION REQUIREMENTSFOR FLAT AND PITCHED
 ROOF AS REQUIRED BY SEC. R806 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 21- PROVIDE COMPLETE DETAILS/SECTIONS FOR CONSTRUCTION
 OF ALL ARCHED OPENINGS. SEC. 106.1.2CITY AMENDMENTS
 TO FBC 2004.
  
 22- OWES $2568.10 FOR UPDATED VALUATION,RADON FEES
 AND BALANCE ON PERMIT APPLICATION.
  
 23- CONTRACTOR TO UPDATE INSURANCE WITH PERMIT CLERK.
  
 24- SHEET S-1:
 A) PROVIDE COMPLETE DETAILS AND SPECS FOR COLUMNS
 WC1 AND WC2. SPECIFY ALL FASTENERS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 B) SPECIFY SIZE OF SPANSION ANCHOR IN DETAIL 1/S-1.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 C) TRUSS CONNECTOR SPECIFIEDDOESN'T WORK FOR
 PROPOSED INSTALLATION.SEE CATALOG FOR PROPER
 CONNECTOR AND REVISE AS REQUIRED.SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 ALSO, SPECIFY ON PLANS TRUSS CONNECTOR. NONE WAS
 KEYED.
  
 25- SHEET S-2:
 A) REVISE TRUSS ANCHOR SCHEDULE. SEE CURRENT CATALOG
 FOR PUBLISHED LOADS AND FASTENERS. OTHERWISE, PROVIDE
 COMPLETE ENGINEERING ANALYSIS FOR NUMBERS AND LOADS
 THAT DIFFER FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 B) SPECIFY TRUSS CONNECTORS ON ROOF FRAMING PLAN.
 NONE WAS KEYED.
  
 C) REVISE CONNECTOR SPECIFIED FOR CUPOLA ROOF ON
 FRONT WALL.ROOF IS RESTING ON MASONRY WALL. NEED TO
 SPECIFY WOOD TO MASONRY CONNECTOR. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-27 Cont ID  
Sent By dpalmer Date 2007-04-27 Time 15:14 Rev Time 0.00
Received By dpalmer Date 2007-04-27 Time 12:34 Sent To M
Notes
2007-04-27 15:14:52** UNSAT **
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE MISSING AIC RATINGS FOR NEW SERVICE
 EQUIPMENT, MAINS, PANELS AND BREAKERS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 110.9
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE
 DEVICES. IF THE SMOKE DEVICES ARE 120V WHICH DETECT,
 SOUND AN ALARM AND ARE WIRED INLINE, THEN THESE DEVICES
 WOULD BE INDICATED AS SA FOR SMOKE ALARMS. PLEASE
 ADJUST.
 PLEASE KNOW IF THEY ARE INDEED SMOKE DETECTORS PLEASE
 INDICATE THE SOUNDING DEVICES.
 PLEASE SEE THE MISSING SMOKE DEVICE REQUIRED AT THE
 FIRST FLOOR LEVEL LEADING TO THE FLOOR ABOVE.
 NFPA-72 11.5.1.1.1, 11.8.3
  
 4) NOTE: PLEASE SEE 210.8A7 WHICH REQUIRES ALL
 RECEPTACLES LOCATED WITHIN 6FT OF SINKS TO BE GFI/GFI
 PROTECTED EVEN IF THEY ARE SINGLE DEDICATED POINT OF
 USE RECEPTACLES. THIS IS REQUIRED FOR 120V DEVICES.
  
 5) NOTE: PLEASE CORRELATE THE RISER AND PLANS AS THE
 PLANS SEEM TO INDICATE A SEPARATE METER AND MAIN
 DISCONNECT.
 106.1.2
  
 6) NOTE:PLEASE SEE 210.12 FOR REQUIRED ARC FAULT
 PROTECTION. PLAN NOTE MENTIONS FOR RECEPTACLES, WHICH
 CHANGED IN THE 2002 NEC TO REQUIRE ALL OUTLETS IN
 BEDROOM/SLEEPING ROOMS TO REQUIRED AFCI PROTECTION.
 THIS CHANGED IN THE 2002 AND IS THE SAME IN THE 2005.
 ** PLEASE SEE PANEL SCHEDULE(S) ONLY INDICATE ONE AFCI
 PROTECTED CIRCUIT WHICH IS NOT POSSIBLE.
  
 7) NOTE: PLEASE SEE MISSING FOOTER STEEL AS PART OF THE
 GROUNDING ELECTRODE SYSTEM PER 250.50.
  
 8) NOTE: PLEASE SEE 110.26 FOR THE MINIMUM CLEARANCE
 REQUIRED FOR DISCONNECTS SHOWN BEHIND A/C CU.
  
 9) NOTE: PLEASE CLARIFY DINING ROOM/BREAKFAST AREA
 CIRCUIT(S) AND THE LIKE AS REQUIRED PER 210.52B1,
 210.11C1, 220.52
  
 10) NOTE: PLEASE SEE SOME ROOMS WHICH INDICATE A
 SWITCH, BUT IT IS NOT SHOWN FEEDING ANYTHING.
 PLEASE ALSO SEE ROOMS WHERE ONLY A J-BOX IS SHOWN FOR A
 FAN WILL REQUIRE A LIGHT FIXTURE OF SOME TYOE FOR FINAL
 OR A SWITCHED RECEPTACLE WILL BE REQUIRED PER 210.70.
 LS 101 7.8
 PLEASE SEE SWITCHES WHICH ARE TIED TO WHAT IS SHOWN A
 3-WAY SWITCHING HOWEVER THE SWITCH IS NOT SHOWN AS A
 3-WAY SWITCH.
  
 11) NOTE: PLEASE KNOW THAT THE PLANS NEED TO LABEL AND
 PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES SHOWING ALL ROOMS
 AND AREAS IN WHICH CIRCUITS FEED WILL BE REQUIRED FOR
 EACH PANEL. PLEASE SEE TEXT WHICH IS TAKEN FROM
 COMMENTARY IN THE CODE WHICH STATES THE USE OF *GEN LT*
 ETC IS NOT ACCEPTABLE.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 12) NOTE: PLEASE SEE MISSING GFI RECEPTACLES ALONG
 KITCHEN COUNTER SPACES PER 210.52C1-5, 210.8A6.
 PLEASE SEE PENINSULAR AND AREA SEPARATED BY SINK.
  
 13) NOTE: PLEASE SEE THE LIGHT IN CLOSET DOES NOT MEET
 THE MINIMUM CLEARANCES PER 410.8
  
 14) NOTE: PLEASE SEE 422.13 AS THE LOADS SHALL BE SHOWN
 AT 125%.
  
 15) NOTE: PLEASE SEE 424.3B FOR THE MINIMUM OVER
 CURRENT PROTECTION FOR THE AHU #2. THIS IS SHOWN AT
 10KW W/ A 2-POLE 20AMP.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-27 Cont ID  
Sent By adarroug Date 2007-04-27 Time 10:22 Rev Time 0.00
Received By adarroug Date 2007-04-27 Time 10:22 Sent To E
Notes
2007-04-27 10:23:11TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-03 Cont ID  
Sent By choops Date 2007-04-26 Time 16:54 Rev Time 0.00
Received By jgomez Date 2007-04-17 Time 11:01 Sent To  
Notes
2007-04-17 11:01:19TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-30 Cont ID  
Sent By tgordon Date 2007-04-30 Time 08:01 Rev Time 0.35
Received By tgordon Date 2007-04-30 Time 08:00 Sent To P
Notes
2007-04-30 08:08:48*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM600A-04R,
 SEE 2004 FBC 13-600.3.A (12-8-06 REVISION).
  
 2) 8" RETURN AIR DUCT TO THE MASTER SUITE NEEDS TO BE
 10", SEE 2004 FBC/R M1602.4 (C) EXCEPT.
  
 *** 2004 FBC/R M1602.4. BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-01 Cont ID  
Sent By jleech Date 2007-05-01 Time 15:03 Rev Time 0.00
Received By jleech Date 2007-05-01 Time 15:03 Sent To B
Notes
2007-05-01 15:13:43DENIED;
 1. SHOW RAIN WATER CAULCULATIONS ON PLANS PER TABLE
 1106.2 AND 1106.3. SHOW SIZE OF EMERGENCY SCUPPERS USE
 TABLE 1106.7. SHOW MAX. HEIGHT OFF ROOF,( ABOVE ROOF
 DRAINS) FOR SCUPPERS (4").
 2. SANITARY RISER DIAGRAM, PAGE P-1. FIRST FLOOR 1/2
 BATH LAVATORY NOT PERMITED TO DUMP INTO THE VERTICAL
 STACK FOR THE 2ND FLOOR BATH #2 AND W/M DRAIN.
 SEE ONE SET OF PLANS MARKED IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-26 Cont ID  
Sent By choops Date 2007-04-26 Time 16:54 Rev Time 0.00
Received By choops Date 2007-04-26 Time 15:41 Sent To I
Notes
2007-04-26 15:48:25***FAILED***
  
  
 1) PLEASE PROVIDE UPDATED COPY OF THE SURVEY (WITHIN
 THE LAST YEAR)
  
 2) PLEASE PROVIDE 2 COPIES OF THE UPDATED SURVEY.
  
 3) MINIMUM FRONT SETBACK IS 25 FEET AS PER SECTION
 94-74(3)A OF THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS.
  
 4) REAR SETBACK IS 15' OR 10% OF LOT DEPTH, WHICHEVER
 IS LESS, AS PER SECTION 94-74(3)C OF THE CITY OF WEST
 PALM BEACH ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 5) PLEASE PROVIDE DIMENSIONS FROM FRONT AND SIDE
 PROPERTY LINES TO MECHANICAL EQUIPMENT.
  
 6) PLEASE PROVIDE ALL ELEVATIONS FROM GRADE NOT FROM
 SLAB
  
 7) PLEASE PROVIDE BUILDING HEIGHT FROM GRADE TO THE
 MIDPOINT OF THE TOWER'S ROOF PITCH.
  
 8) POOL MUST BE UNDER SEPERATE PERMIT
  
 9)PATIOS AND DRIVEWAY MUST BE UNDER SEPERATE PERMIT
  
 10) PLEASE PROVIDE DIMENSIONS OF CHIMNEY ENCROACHMENT
 INTO SETBACK (SHALL NOT EXCEED 18")
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720