Plan Review Details - Permit 07040469
Plan Review Stops For Permit 07040469
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-05-15 Cont ID  
Sent By mwennerg Date 2007-05-15 Time 10:35 Rev Time 0.00
Received By mwennerg Date 2007-05-15 Time 10:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-20 Cont ID  
Sent By mwennerg Date 2007-04-20 Time 13:48 Rev Time 0.00
Received By mwennerg Date 2007-04-20 Time 13:48 Sent To  
Notes
2007-04-20 14:00:18***DENIED***
  
 1) DRAWINGS SHALL COMPLY WITH FBC 106.1.1. PLEASE
 PROVIDE MORE INFORMATION REGARDING PROPERTY TO BE
 PROTECTED, SQUARE FOOTAGE, OCCUPANCY TYPE ETC.
  
 2) IT WOULD APPEAR THAT FIRE ALARM WILL BE SUPERVISING
 AN EXISTING SPRINKLER SYSTEM. NEW FIRE ALARM SYSTEMS
 THAT SUPERVISE AN AUTOMATIC FIRE SPRINKLER SYSTEM SHALL
 BE UL CERTIFIED FOR CENTRAL STATION SERVICE.
  
 3) FIRE ALARM TO BE CLASS A OR FULLY ADDRESSABLE.
  
 4) DRAWINGS ILLUSTRATE A SMOKE DETECTOR NEAR THE FRONT
 ENTRANCE. PLEASE CLARIFY IF THIS IS THE LOCATION OF
 FACP AS IT IS NOT IDENTIFIED AS SUCH.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-03 Cont ID  
Sent By shill Date 2007-05-03 Time 10:20 Rev Time 0.00
Received By shill Date 2007-05-03 Time 10:20 Sent To FIRE
Notes
2007-05-03 10:20:15TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-20 Cont ID  
Sent By mwennerg Date 2007-04-20 Time 14:01 Rev Time 0.00
Received By mwennerg Date 2007-04-16 Time 14:36 Sent To  
Notes
2007-04-16 14:36:26TO "F" BOX