Plan Review Details - Permit 07040466
Plan Review Stops For Permit 07040466
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-03-26 Cont ID  
Sent By mjacobs Date 2008-03-26 Time 11:31 Rev Time 0.00
Received By mjacobs Date 2008-03-26 Time 10:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-12-10 Cont ID  
Sent By mjacobs Date 2007-12-10 Time 12:42 Rev Time 0.00
Received By mjacobs Date 2007-12-10 Time 11:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-25 Cont ID  
Sent By mjacobs Date 2007-09-25 Time 12:37 Rev Time 0.00
Received By mjacobs Date 2007-09-25 Time 12:37 Sent To  
Notes
2007-09-25 12:39:28 
 BUILDING PLAN REVIEW
 PERMIT:07040466
 ADD: 1572 PBL BLVD
 CONT:KEDECO ENTERPRISES INC.
 TEL: (561)712-9733
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA
 STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC
 2004
 **NEW** THIS INFORMATION IS REQUIRED ON THE DRAWINGS.
 SHEET A- 1 IS NOT SIGNED OR SEALED.
 F.A.C. 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
  
 3)AN ENGINEER PRACTICING THROUGH A DULYAUTHORIZED
 ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND
 LICENCE #, AS WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER 61G15-23.002 (2)
 FAC. THE PERSON FROM HILLMAN ENGINEERING INC. WHO IS
 RESPONSIBLE FOR THE DRAWINGS NEEDS TO SIGN AND SEAL THE
 DRAWINGS.NOTE: THESE DRAWINGS ARE NOT SHOP DRAWINGS AS
 INDICATED.
  
 4)OK
  
 PARTIALLY CORRECT******
 5)THE NEW WALL SECTION DRAWINGS REQUIRE MORE
 INFORMATION. THE DRAWINGS SHALL BE SIGN/SEAL AND DATED
 BY THE DESIGN PROFESSIONAL. STATE THE BUILDING CODE
 UNDER WHICH THE DRAWINGS ARE DESIGNED AND THE WIND
 INFORMATION PER FBC. SECTION 1603.1.4 **NO RESPONSE NOT
 ADDRESSED**
 **NEW** THE INFORMATION BELOW SHALL BE INDICATED ON THE
 DRAWINGS.
 2004 FL. BLD CODE 1603.1.4 THE FOLLOWING INFORMATION
 RELATED TO WIND SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1) - BASIC WIND SPEED, MPH
 2) - WIND IMPORTANCE FACTOR, & BUILDING CATEGORY
 3) - WIND EXPOSURE
 4) - INTERNAL PRESSURE COEFFICIENT,
 5) - COMPONENTS & CLADDING, THE DESIGN WIND PRESSURES
 IN TERMS OF PSF.
  
 NOTE:THE DRAWINGS ARE NOT TO THE SCALE INDICATED. THE
 DRAWINGS NEEDS TO MATCH THE SCALE INDICATED.
 **NO RESPONSE NOT ADDRESS**
  
 6)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 SEE COMMENTS FROM THE OTHER TRADES. IS THE GENERATOR
 EXISTING OR NEW? CLARIFY.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
 [email protected].

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-30 Cont ID  
Sent By mjacobs Date 2007-07-30 Time 11:10 Rev Time 0.00
Received By mjacobs Date 2007-07-27 Time 15:38 Sent To  
Notes
2007-07-27 16:03:39BUILDING PLAN REVIEW
 PERMIT:07040466
 ADD: 1572 PBL BLVD
 CONT:KEDECO ENTERPRISES INC.
 TEL: (561)712-9733
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA
 STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC
 2004
  
 3)AN ENGINEER PRACTICING THROUGH A DULYAUTHORIZED
 ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND
 LICENCE #, AS WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER 61G15-23.002 (2)
 FAC. THE PERSON FROM HILLMAN ENGINEERING INC. WHO IS
 RESPONSIBLE FOR THE DRAWINGS NEEDS TO SIGN AND SEAL THE
 DRAWINGS.NOTE: THESE DRAWINGS ARE NOT SHOP DRAWINGS AS
 INDICATED.
  
 4)OK
  
 PARTIALLY CORRECT******
 5)THE NEW WALL SECTION DRAWINGS REQUIRE MORE
 INFORMATION. THE DRAWINGS SHALL BE SIGN/SEAL AND DATED
 BY THE DESIGN PROFESSIONAL. STATE THE BUILDING CODE
 UNDER WHICH THE DRAWINGS ARE DESIGNED AND THE WIND
 INFORMATION PER SECTION 1603.1.4
 NOTE:THE DRAWINGS ARE NOT TO THE SCALE INDICATED. THE
 DRAWINGS NEEDS TO MATCH THE SCALE INDICATED.
  
 6)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
 [email protected].
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-11 Cont ID  
Sent By mjacobs Date 2007-06-11 Time 09:43 Rev Time 0.00
Received By mjacobs Date 2007-06-11 Time 07:44 Sent To PC
Notes
2007-06-11 09:43:47BUILDING PLAN REVIEW
 PERMIT: 07040466
 ADD: 1572 PALM BEACH LAKES BLVD.
 CONT: KEDECO ENTERPRISES INC.
 TEL: (561)712-9733
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA
 STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC
 2004
  
 3)AN ENGINEER PRACTICING THROUGH A DULYAUTHORIZED
 ENGINEERING BUSINESS SHALL INDICATE THEIR NAME AND
 LICENCE #, AS WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER 61G15-23.002 (2)
 FAC.
  
 4)106.1.2. THE BUILDING OFFICIAL
 MAY SET STANDARDS THROUGH DEPARTMENTAL
 POLICY STANDARDS FOR PLANS AND SPRCIFICA
 TIONS. "NO WHITE OUT" "NO HANDWRITING.
  
 5)THE NEW WALL SECTION DRAWINGS REQUIRE MORE
 INFORMATION. THE DRAWINGS SHALL BE SIGN/SEAL AND DATED
 BY THE DESIGN PROFESSIONAL. STATE THE BUILDING CODE
 UNDER WHICH THE DRAWINGS ARE DESIGNED AND THE WIND
 INFORMATION PER SECTION 1603.1.4
  
 6)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-06-10 Cont ID  
Sent By dpalmer Date 2008-06-10 Time 15:05 Rev Time 0.00
Received By dpalmer Date 2008-06-10 Time 15:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-03-20 Cont ID  
Sent By dpalmer Date 2008-03-20 Time 15:24 Rev Time 0.00
Received By dpalmer Date 2008-03-20 Time 15:24 Sent To  
Notes
2008-03-20 15:24:56** DENIEDREVIEW **
  
  
 ** PLEASE SEE SOME COMMENTS BELOW ARE STILL THE SAME AS
 PREVIOUSLY NOTED. SOME COMMENTS ARE NEW AS THE SERVICE
 RISER FOR PROPOSED ELECTRICAL HAS CHANGED.
  
  
  
  
 1) NOTE: PLEASE SEE NO MEANS OF DISCONNECT FOR FEEDERS
 FROM THE GENERATOR AT THE BUILDING MEETING
 225.31-225.39
 THE ATS SHOWN WHICH IS NOTED AS EXISTING DOES NOT SHOW
 UP IN ANY RECORDS GOING BACK IN A SEARCH FOR MANY
 YEARS. THERE IS NOT INFORMATION ON WHETHER OR NOT
 PERMIT WAS EVER APPLIED OR ISSUED FOR THE INSTALLATION
 OF THIS ATS.
 THE ATS AS SHOWN NEEDS MANUFACTURES /SPECS OR CUT
 SHEETS SHOWING COMPLIANCE.
  
 2) NOTE: PLEASE SEE THE CONDUCTORS FROM THE ATS ARE
 SHOWN AS TAPPED CONDUCTOR AS NO OVER CURRENT PROTECTION
 CAN BE VERIFIED. THE ONLY OCP SHOWN IS 400AMPS, IF THIS
 IS THE SAME OCP THAT FEEDS THE MDP THEN PLEASE
 CLARIFY.
 THE J-BOX AS SHOWN DOES NOT CLEARLY SHOW HOW THIS
 WIRING IS BEING DONE AND IT IS NOT EASILY DETERMINED IF
 THERE ARE TAPPED CONDUCTORS WHICH ARE TERMINATING IN
 OCP OR IF THE ATS FEEDS ONLY THE MDP?
 240.4, 310.16, 240.21 ETC.
  
 3) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 INCREASED SCOPE OF WORK AND APPLIED VALUE FOR THE
 COMPLETE SCOPE OF WORKS NEEDS ADJUSTING. THE VALUE IS
 TO INCLUDE ALL WORK, ALL MATERIALS; ALL DESIGN COSTS,
 ALL EQUIPMENT, EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED.
 PLEASE SEE FBC 108.3 AND VERIFY.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-12-03 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 15:20 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 15:20 Sent To  
Notes
2007-12-03 15:20:29 
 ** DENIED 4TH TIME **
  
 ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW
 NOTES BASED ON REVISED PLAN SUBMITTED.
  
  
  
 1) NOTE:ALL CODES BELOW ARE TO BE STATED ON PLANS.
 AS STATED ON PREVIOUS REVIEWS: PLEASE INCLUDE THE
 RELEVANT CODES AS ADOPTED BY FS 553.73.
 PLEASE SEE THE FOLLOWING AT A MINIMUM SHALL BE STATED
 ON PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-110
 ** PLEASE SEE CODES FROM OTHER TRADES.
 ** PLEASE KNOW THAT THE *LATEST EDITION* IS NOT
 SUFFICIENT.
  
 2) NOTE: PLEASE SEE THE 2005 NEC AS THE RISER AS SHOWN
 IS NON-CODE COMPLIANT AND CONFUSING.
 PLEASE SEE FOR EXAMPLE THE METER WHICH IS NOT ONLY ON
 THE LOAD SIDE OF THE 1200AMP MAIN, BUT ALSO SHOWS
 CONDUITS FROM THE METER TO BOTH THE ATS AND TO MDP. HOW
 IS THIS POSSIBLE?
 PLEASE SEE RISER IS NOT COMPLETE WITH ALL OVER CURRENT
 PROTECTION AND CONDUCTOR SIZES AS NEEDED FOR CODE
 COMPLIANCE REVIEW.
 PLEASE GO OVER RISER AND SUBMIT CORRECTED PLANS.
 240.4, 310.16, ETC
 FBC 106.3.5.1.2
  
 3) NOTE: PLEASE SEE RISER IS STILL MISSING *EQUIPMENT
 GROUNDING CONDUCTORS* AS PREVIOUSLY REQUESTED AND
 REQUIRED BY CODE AFTER THE FIRST MEANS OF DISCONNECT.
 250.122, 250.110, 250.24, ETC.
  
 4) NOTE: PLEASE SEE PREVIOUS NOTES AS THE INTENDED
 LOADS ARE REQUIRED TO BE SHOWN. NO PANELS , SCHEDULES
 ETC.
 LOAD AS SHOWN IS NOT COMPLETE.
 702.5
  
 5) NOTE: PLEASE SPECIFY IF THERE ARE AN LIFE SAFETY OR
 EMERGENCY LOADS PER 700 PR 701 BEING FED.
  
 6) NOTE: PLEASE SEE PLANS SHOWING A LAYOUT OF ALL
 EQUIPMENT INCLUDING SERVICE EQUIPMENT AND DISCONNECTS
 WERE NOT SUBMITTED. UNABLE TO REVIEW FOR 225.31-225.39
 AT THIS TIME.
  
 7) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK
 HAS NOT CHANGED PER FBC 108.3.
 ALL EQUIPMENT, LABOR, MATERIALS, DESIGN COST ETC EVEN
 IF *ANY* IS OWNER SUPPLIED SHALL BE INCLUDED.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-09-18 Cont ID  
Sent By dpalmer Date 2007-09-18 Time 15:54 Rev Time 0.00
Received By dpalmer Date 2007-09-18 Time 14:48 Sent To I
Notes
2007-09-18 15:55:15 
 ** DENIED 3RD TIME **
  
  
 ** PLEASE SEE THERE ARE ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW
 COMMENTS DUE TO INFORMATION OR CHANGES MADE TO PLANS.
 ** PLEASE SEE THE ELECTRICAL RISER AND PLANS HAVE BEEN
 COMPLETELY REVISED WITH SOMETHING DIFFERENT THAN SHOWN
 ON PREVIOUS PLANS.
  
 1) NOTE: AS STATED ON PREVIOUS REVIEWS: PLEASE INCLUDE
 THE RELEVANT CODES AS ADOPTED BY FS 553.73.
 PLEASE SEE THE FOLLOWING AT A MINIMUM SHALL BE STATED
 ON PLANS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-110
 ** PLEASE SEE CODES FROM OTHER TRADES.
 ** PLEASE KNOW THAT THE *LATEST EDITION* IS NOT
 SUFFICIENT.
  
 2) NOTE: PLEASE SEE THE TITLE BLOCKS HAVE NOW BEEN
 CHANGED TO LIST A NEW FIRM. PLEASE SEE THERE ARE TWO
 NEW SETS. ONE SET DOES NOT CONTAIN ANY SIGNATURE, DATE
 OR SEAL ON SHEET A-1 AND THE OTHER SET FOR SHEET A-1
 CONTAINS A RAISED/EMBOSSED SEAL OVER A *PHOTO-COPIED*
 SIGNATURE AND DATE.
 PLEASE SEE FS 481.221 AS THIS REQUIRES AND ORIGINAL
 DATE AND SIGNATURE BY THE DESIGN PROFESSIONAL.
 ** PLANS WILL BE RETAINED BY THIS OFFICE FOR POSSIBLE
 REVIEW BY THE FLORIDA BOARD OF ARCHITECTS AND STATE
 LEGAL COUNSEL TO THE BOARD.
  
 3) NOTE: PLEASE SEE THE PLANS ON SHEET A-1 NOW CALL FOR
 THE GENERATOR BEING AS EXISTING! HOW IS THIS POSSIBLE
 WHEN THE PERMIT APPLICATION IS TO INSTALL THIS NEW
 UNIT? A FIELD INSPECTION MAY BE PERFORMED TO VERIFY IF
 THE INSTALLATION HAS TAKEN PLACE.
  
 4) NOTE: PLEASE CORRELATE PLANS. PLEASE SEE SHEET PE-1
 WHICH INDICATE A 4INCH CONDUIT AND 250MCM FOR
 CONDUCTORS YET THE ELECTRICAL RISER SHOWS 4-3/0*S.
 PLEASE SEE 310.16, 240.4 ETC.
 PLEASE SEE THE CONDUCTORS ON RISER ARE NOT OF
 SUFFICIENT SIZE BASED ON THE OVER CURRENT PROTECTION
 WHICH IS INDICATED ON THE GENERATOR SPECS SHEETS. THIS
 IS BEING SHOWN AS 300AMP.
  
 5) NOTE: PLEASE SEE RISER SHOWS THE BREAKER WHICH IS
 SUPPOSEDLYTHE EXISTING PANEL *A* AS 200AMPS. AS THE
 RISER DOES NOT INDICATE THE SIZE OF THIS EXISTING
 PANEL, THIS CAN NOT BE REVIEWED. THIS SEEMS INDICATE
 THIS PANEL BASED ON THE CONDUCTOR SIZES AND THE OVER
 CURRENT PROTECTION LISTED AS A 200AMP RATED PANEL. MAY
 NOT FEED A 200AMP PANEL WITH A 300AMP BREAKER. PREVIOUS
 RISER SHOWED THIS AS 400AMP PANEL.
 PLEASE INDICATE THE SIZES OF ALL EQUIPMENT ON RISER.
 PLEASE COMPLETE RISER WITH THE CORRECT OVER CURRENT
 PROTECTION DEVICES AND SIZES OF ALL EQUIPMENT TO
 COORDINATE WITH THE MINIMUM REQUIREMENTS OF THE 2005
 NEC/NFPA-70.
  
 6) NOTE: PLEASE SEE MISSING DISCONNECT PER
 225.31-225.39
  
 7) NOTE: PLEASE SUBMIT THE MISSING MANUFACTURES
 SPECS/CUT SHEETS FOR THE NEW TRANSFER SWITCH. 110.3,
 90.7.
  
 8) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK INCLUDING ALL LABOR, EQUIPMENT, MATERIALS; DESIGN
 COST ETC SHALL MEET FBC 108.3.
 THIS IS REQUIRED EVEN IF ANY OF THESE ITEMS ARE OWNER
 SUPPLIED.
  
 9) NOTE: PLEASE CLARIFY HOW A 200AMP TRANSFER SWITCH IS
 BEING FED FROM A 300AMP BREAKER AND OVER CURRENT
 PROTECTION?
 NEC 2005
  
 10) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTORS IN ALL CONDUITS AFTER THE FIRST MEANS OF
 DISCONNECT OF SERVICE MAIN.
 250.110, 250.122, 250.24 ETC
  
 11) NOTE: PLEASE SUBMIT INTENDED LOADS AND LOAD SUMMARY
 PER NEC 220, 408.4
  
 12 NOTE: PLEASE SEE AS REQUESTED IN THE PREVIOUS REVIEW
 PLEASE SUBMIT TWO SETS OF COMPLETE PLANS INCLUDING ALL
 SPECIFICATIONS, ETC. PLEASE SEE SOME OF THE SHEETS ARE
 STILL ATTACHED TO OLD PLANS ETC.
 FBC 106.1.2, 106.1.3., 106.3.5.1.2
  
 ** PLEASE KNOW AS THERE ARE ITEMS NOT YET SUBMITTED FOR
 REVIEW, A COMPLETE REVIEW FOR CODE COMPLIANCE CAN ONLY
 BE BASED ON THE PLANS AND DOCUMENTS SUBMITTED.
  
  
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-18 14:49:28** REMOVED FROM INCOMING DUE TO DATED ORDER OF PLANS
 WHICH ELECTRICAL REVIEW IS UP TO.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-06 Cont ID  
Sent By dpalmer Date 2007-07-06 Time 10:18 Rev Time 0.00
Received By dpalmer Date 2007-07-06 Time 09:10 Sent To I
Notes
2007-07-06 10:19:032007-07-06 10:19:03
 ** UNSAT 2ND REVIEW **
  
 **PLEASE SEE MOST COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
 ** PLEASE SEE THERE ARE NEW NOTES DUE TO NEW A SHEETS
 SUBMITTED AND REPEAT COMMENTS NOTE.
  
  
 1) NOTE: SAME NOTE FROM PREVIOUS REVIEW.
 PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH ARE
 SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE
 THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC
 FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE
 ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS FOR ALL
 TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-110
 ** PLEASE SEE OTHER CODES WHICH MAY BE NOTED FROM OTHER
 TRADES.
  
 2) NOTE: SAME NOTE FROM PREVIOUS REVIEW: HOWEVER PLEASE
 ALSO SEE NEW NOTES BELOW WITH RESPECT TO THE NEW
 A-SHEETS.
 PLEASE SEE BUILDING REVIEW COMMENTS AS THE ENGINEERING
 SHEETS SUBMITTED ARE NOT SIGNED, DATED OR SEALED AS
 REQUIRED PER FAC 61G15-23.002, FS 471.025
  
 3) NOTE: SAME NOTE AS PREVIOUS REVIEW.
 PLEASE SEE THE ELECTRICAL SHEETS EVEN WHEN FALLING
 UNDER THE EXCEPTION OF FS 471.003 STILL REQUIRES THE
 PRINTED NAME AND SIGNATURE OF THE DESIGN PROFESSIONAL
 WHICH IN THIS CASE IS THE ELECTRICAL CONTRACTOR.
  
 4) NOTE: SAME NOTE AS PREVIOUS PLANS.
 PLEASE KNOW THAT NO HAND DRAWN PEN OR PENCIL MAY BE
 DRAWN ON PLANS WHICH ARE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES. (SEE SITE PLANS.
 PLEASE ALSO SEE THE SHEETS FOR SITE CONTAIN A RAISED
 SEAL OVER A PHOTO-COPIED SIGNATURE WHICH IS NOT
 PERMITTED PER FS 472.025
  
 5) NOTE: SAME NOTE AS PREVIOUS PLANS.
 PLEASE SEE THE RISER IS NOT COMPLETE AT THIS TIME.
 PLEASE COMPLETE WITH ALL EQUIPMENT, MTS, ATS ETC. NO
 TRANSFER DEVICES ARE SHOWN EVEN IF THEY ARE EXISTING.
 PLEASE BE SURE TO DELINEATE WHAT IS EXISTING AND NEW.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS ON THE
 TRANSFER DEVICE(EVEN IF EXISTING). THIS RECORD SET OF
 PLANS NEEDS TO SHOW CODE COMPLIANCE.
 PLEASE KNOW THAT VERIFICATION FOR THE REQUIRED
 DISCONNECTING MEANS CAN NOT BE VERIFIED AT THIS TIME.
 110.3, 90.7, FBC 106.1.2
  
 6) NOTE: SAME NOTE AS PREVIOUS REVIEW.
 PLEASE SEE FEEDERS ARE NOT RATED FOR 150AMPS PER THE 75
 DEGREE COLUMN PER 310.16, 110.14. PLEASE ADJUST
 FEEDERS.
  
 7) NOTE: SAME NOTE AS PREVIOUS REVIEW.
 PLEASE SEE 250.122 AS THE EQUIPMENT GROUNDING
 CONDUCTOR IS NOT LARGER ENOUGH. (#4 MIN)
  
 8) NOTE: SAME NOTE AS PREVIOUS REVIEW.
 PLEASE SEE 310.4 AS PARALLEL CONDUCTORS MAY NOT BE RUN
 SMALLER THAN 1/0.
  
 9) NOTE: SAME NOTE AS PREVIOUS REVIEW.
 PLEASE SUBMIT LOAD CALCULATIONS FOR INTENDED LOADS.
 702.5, 220
 FBC 106.1.2
  
 10) NOTE: SAME NOTE AS PREVIOUS REVIEW.
 PLEASE SEE PLUMBING REVIEW COMMENTS FOR MISSING
 REQUIRED GAS RISER.
  
  
 ** NEW NOTES**
  
 11) NOTE: PLEASE SEE THE NEW A-SHEETS WHICH ARE MISSING
 INFORMATION REQUIRED PER FAC 61G1-16.004, FS 481.219.
 PLEASE SEE MISSING PRINTED NAME, PRINTED LICENSE NUMBER
 OF ARCHITECT AND MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER. IT WAS LOCATED ON THE STATE WEBSITE THAT THE
 APPLICATION HAS BEEN MADE FOR THE STATE LICENSE HOWEVER
 APPLICATION FOR LICENSE IN LIEU OF THE ACTUAL REQUIRED
 LICENSE ON SHEETS CAN NOT BE ACCEPTED.
 PLEASE SEE WE HAVE ATTACHED THIS SHEET PRINTED THE
  
 12) NOTE: PLEASE SEE THE APPLIED FOR VALUE FOR THE
 COMPLETE SCOPE OF WORK SHOWN AND AS APPLIED FOR IS LOW.
 PLEASE SEE THE VALUE SHALL INCLUDE ALL LABOR, MATERIALS
 , EQUIPMENT, DESIGN COST, ETC EVEN IF ANY OF THESE
 ITEMS ARE OWNER SUPPLIED.
 PLEASE SEE FBC 108.3.
 PLEASE KNOW AN ADJUSTMENT MAY BE MADE BY THIS OFFICE
 USING ADOPTED REFERENCES TO THE FBC IF THE VALUE IS NOT
 ADJUSTED BY THE CONTRACTOR.
  
 13) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY AN NOTICE GIVEN AT THIS TIME.
  
 ** PLEASE KNOW AT THIS TIME AS MUCH OF THE NEEDED
 INFORMATION HAS NOT BEEN SUBMITTED, THERE MAY BE
 COMMENTS ON THE FOLLOWING REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-06 09:11:252007-07-06 09:11:25
 PLANS REMOVED FROM INCOMING. WILL RETURN TO INCOMING
 WATING FOR COMM BOARD ONCE ELECTRICAL REVIEW IS
 COMPLETED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-01 Cont ID  
Sent By dpalmer Date 2007-05-01 Time 16:51 Rev Time 0.00
Received By dpalmer Date 2007-05-01 Time 12:45 Sent To I
Notes
2007-05-01 16:52:07** UNSAT **
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-110
 ** PLEASE SEE OTHER CODES WHICH MAY BE NOTED FROM OTHER
 TRADES.
  
 2) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS AS THE
 ENGINEERING SHEETS SUBMITTED ARE NOT SIGNED, DATED OR
 SEALED AS REQUIRED PER FAC 61G15-23.002, FS 471.025
  
 3) NOTE: PLEASE SEE THE ELECTRICAL SHEETS EVEN WHEN
 FALLING UNDER THE EXCEPTION OF FS 471.003 STILL
 REQUIRES THE PRINTED NAME AND SIGNATURE OF THE DESIGN
 PROFESSIONAL WHICH IN THIS CASE IS THE ELECTRICAL
 CONTRACTOR.
  
 4) NOTE: PLEASE KNOW THAT NO HAND DRAWN PEN OR PENCIL
 MAY BE DRAWN ON PLANS WHICH ARE SIGNED AND SEALED BY A
 DESIGN PROFESSIONAL.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES. (SEE SITE PLANS.
 PLEASE ALSO SEE THE SHEETS FOR SITE CONTAIN A RAISED
 SEAL OVER A PHOTO-COPIED SIGNATURE WHICH IS NOT
 PERMITTED PER FS 472.025
  
 5) NOTE: PLEASE SEE THE RISER IS NOT COMPLETE AT THIS
 TIME. PLEASE COMPLETE WITH ALL EQUIPMENT, MTS, ATS
 ETC.
 NO TRANSFER DEVICES ARE SHOWN EVEN OF THEY ARE
 EXISTING.
 PLEASE BE SURE TO DELINEATE WHAT IS EXISTING AND NEW.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS ON THE
 TRANSFER DEVICE(EVEN IF EXISTING). THIS RECORD SET OF
 PLANS NEEDS TO SHOW CODE COMPLIANCE.
 PLEASE KNOW THAT VERIFICATION FOR THE REQUIRED
 DISCONNECTING MEANS CAN NOT BE VERIFIED AT THIS TIME.
 110.3, 90.7, FBC 106.1.2
  
 6) NOTE: PLEASE SEE FEEDERS ARE NOT RATED FOR 150AMPS
 PER THE 75 DEGREE COLUMN PER 310.16, 110.14. PLEASE
 ADJUST FEEDERS.
  
 7) NOTE: PLEASE SEE 250.122 AS THE EQUIPMENT GROUNDING
 CONDUCTOR IS NOT LARGER ENOUGH. (#4 MIN)
  
 8) NOTE: PLEASE SEE 310.4 AS PARALLEL CONDUCTORS MAY
 NOT BE RUN SMALLER THAN 1/0.
  
 9) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR INTENDED
 LOADS.
 702.5, 220
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE PLUMBING REVIEW COMMENTS FOR
 MISSING REQUIRED GAS RISER.
  
 ** PLEASE KNOW AT THIS TIME AS MUCH OF THE NEEDED
 INFORMATION HAS NOT BEEN SUBMITTED, THERE MAY BE
 COMMENTS ON THE FOLLOWING REVIEW.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-05-01 12:46:30REMOVED FROM INCOMING, IN ELEC FOR REVIEW. WILL RETURN
 TO INCOMING TABLE WAITING FOR COMM BOARD ONCE REVIEW IS
 COMPLETED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-12-19 Cont ID  
Sent By mwennerg Date 2007-12-19 Time 14:50 Rev Time 0.00
Received By mwennerg Date 2007-12-19 Time 14:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-09-27 Cont ID  
Sent By mwennerg Date 2007-09-27 Time 10:14 Rev Time 0.00
Received By mwennerg Date 2007-09-27 Time 10:14 Sent To  
Notes
2007-09-27 10:17:37***DENIED***
  
 PLEASE NOTE THAT COMMENTS FROM PREVIOUS REVIEW NEED TO
 BE ADDRESSED.
  
 1) OK
  
 2) NFPA 110, STANDARD FOR EMERGENCY AND STAND BY POWER
 SYSTEMS SHALL BE COMPLIED WITH. PLEASE ADD TO PLANS.
  
 3) THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO PROPERTY OR VICINITY
 INCLUDING STREETS, ROADS, FIRELANES ETC. PLEASE
 RESPOND
  
 4) DEPENDANT UPON LOCATION OF THE EQUIPMENT, SAFEGUARDS
 AGAINST MECHANICAL DAMAGE MAY BE REQUIRED. PLEASE
 ADVISE
  
 5) OK
  
 NEW COMMENTS:
  
 1) PLEASE SEE OTHER REVIEW COMMENTS REGARDING
 REQUIREMENTS FOR SEAL OF DESIGN PROFESSIONALS.
  
 2) PLANS REFERENCE EXISTING AND NEW GENERATOR. PLEASE
 CORRELATE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-07-31 Cont ID  
Sent By mwennerg Date 2007-07-31 Time 10:13 Rev Time 0.00
Received By mwennerg Date 2007-07-31 Time 10:13 Sent To  
Notes
2007-07-31 10:20:38***DENIED***
  
 PLEASE NOTE THAT SOME COMMENTS FROM PREVIOUS REVIEW
 NEED TO BE ADDRESSED.
  
 1) OK
  
 2) NFPA 110, STANDARD FOR EMERGENCY AND STAND BY POWER
 SYSTEMS SHALL BE COMPLIED WITH. PLEASE ADD TO PLANS.
  
 3) THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO PROPERTY OR VICINITY
 INCLUDING STREETS, ROADS, FIRELANES ETC. PLEASE
 RESPOND
  
 4) DEPENDANT UPON LOCATION OF THE EQUIPMENT, SAFEGUARDS
 AGAINST MECHANICAL DAMAGE MAY BE REQUIRED. PLEASE
 ADVISE
  
 5) OK
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-08 Cont ID  
Sent By mawillia Date 2007-06-08 Time 15:00 Rev Time 0.00
Received By mawillia Date 2007-06-08 Time 12:14 Sent To  
Notes
2007-06-08 14:35:04*****DENIED*****
  
  
 1.THE COMPLETE ADDRESS OF THE PROJECT SITE SHALL BE
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.STATIONARY GENERATORS FOR EMERGENCY USE OR STANDBY
 POWER SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 110.
  
 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF (INCLUDING STREETS, ROADS, FIRE
 LANES)
  
 4.DEPENDANT UPON LOCATION OF THE EQUIPMENT,
 SAFEGUARDS AGAINST MECHANICAL DAMAGE MAY BE REQUIRED
 AND SHALL BE ILLUSTRATED.
  
 5. CLEARLYIDENTIFY LOCATION OF GENERATOR WITH
 RELATION TO BUILDING OPENINGS AND ILLUSTRATE
 DISTANCES.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2007-07-26 Cont ID  
Sent By rregueir Date 2007-07-26 Time 11:40 Rev Time 0.00
Received By rregueir Date 2007-07-26 Time 11:40 Sent To  
Notes
2007-07-26 11:41:28FUEL REVIEW STOP NOT REQUIRED AS THIS GENERATOR IS RUN
 ON 100% NATURAL GAS AND HAS NO ON-SITE FUEL PROVISIONS.

Review Stop G GAS REVIEW
Rev No 6 Status P Date 2008-06-17 Cont ID  
Sent By mperson Date 2008-06-17 Time 15:22 Rev Time 0.00
Received By mperson Date 2008-06-17 Time 15:22 Sent To PC
Notes
2008-06-17 15:23:21NOTE: NEW PE-2 SHEET SUBMITTED.
  
 ****************PROVISO****************
 NOTE: PER THE MANUFACTURER'S SPECIFICATION SHEETS THE
 GENERATOR AT 100% IS 1154 CFH. PER THE INDICATED SIZING
 TABLES AND DELIVERY PRESSURE GAS SYSTEM IS NATURAL
 GAS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2008-03-21 Cont ID  
Sent By mperson Date 2008-03-21 Time 15:57 Rev Time 0.00
Received By mperson Date 2008-03-21 Time 15:57 Sent To  
Notes
2008-03-21 15:58:49NOTE: NEW SHEETS SUBMITTED.
  
 ****************PROVISO****************
 NOTE: PER THE MANUFACTURER'S SPECIFICATION SHEETS THE
 GENERATOR AT 100% IS 1154 CFH. PER THE INDICATED SIZING
 TABLES AND DELIVERY PRESSURE GAS SYSTEM IS NATURAL
 GAS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-12-07 Cont ID  
Sent By mperson Date 2007-12-07 Time 06:31 Rev Time 0.00
Received By mperson Date 2007-12-07 Time 06:02 Sent To  
Notes
2007-12-07 06:31:13****************PROVISO****************
 NOTE: PER THE MANUFACTURER'S SPECIFICATION SHEETS THE
 GENERATOR AT 100% IS 1154 CFH. PER THE INDICATED SIZING
 TABLES AND DELIVERY PRESSURE GAS SYSTEM IS NATURAL
 GAS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-09-24 Cont ID  
Sent By mperson Date 2007-09-24 Time 09:49 Rev Time 0.00
Received By mperson Date 2007-09-24 Time 09:49 Sent To  
Notes
2007-09-24 10:52:32DENIED 3RD TIME
 REFERENCE:
 ** FBC-2004 WITH 2006 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. NOTE: AS STATED ON PREVIOUS REVIEWS:
 PLEASE INCLUDE THE RELEVENT CODES AS ADOPTED BY FS
 533.73.
 PLEASE SEE THE FOLLOWING AT A MINIMUM SHALL BE STATED
 ON PLANS.
 **FBC-2004 WITH 2006 REVISIONS, FUEL GAS.
  
 2. PLEASE REFERENCE THE ELECTRICAL COMMENT #2 ON FIRM
 CHANGE AND TITLE BLOCK INFORMATION.
  
 3. 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION
 DOCUMENTS, SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A
 PERMIT.
  
 4. SHEET A-1 AND PE-1 INDICATE GENERATOR AS EXISTING,
 SSHEET PE-1 EXISTING GAS RISER INDICATES NEW GENERATOR.
 THIS IS CONFUSING, PLEASE CORRELATE THE PLANS ON THE
 RESUBMITTAL. PER FBC-2004 CHAPTER 1, SECTION 106.1.1
 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 5. SHEET PE-1 GAS RISER THE PRESSURE REGULATOR VALVE
 TO THE GENERATOR PER FBC-2004 FUEL GAS, SECTION 409.4
 MP REGULATOR VALVES: A LISTED SHUTOFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR.
 PLEASE CORRECT THIS ON THE RESUBMITTAL.
  
 6. SHEET PE-1 GAS RISER: WHAT IS THE PURPOSE OF THE
 MECHANICAL SHUT OFF VALVE LOCATED BETWEEN THE GAS METER
 AND GENERATOR? THIS IS NOT REQUIRED, PLEASE DELETE THIS
 ON THE RESUBMITTAL.
  
 7. SHEET PE-1 GAS RISER: SHOW TYPE OF PIPING MATERIAL
 BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 NOTE: THE PIPING MATERIAL IS NOT INDICATED, PLEASE DO
 THIS ON THE RESUBMITTAL.
  
 8. SHEET PE-1 PLUMBING NOTES: NOTE #1 PLEASE DELETE
 THE FOLLOWING "STANDARD PLUMBING CODE, CHAPTER 46" AND
 ADD IN ITS PLACE THE FOLLOWING "FBC-2004 WITH 2006
 REVISIONS, FUEL GAS".
  
 9. SHEET PE-1 PLUMBING NOTES: NOTE #3 PLEASE DELETE
 AND ADD IN ITS PLACE THE FOLLOWING PER FBC-2004 W/2006
 REV. SECTION 404.8.2 PROTECTIVE COATINGS AND WRAPPINGS.
 PIPE PROTECTIVE COATINGS AND WRAPPINGS SHALL BE
 APPROVED FOR THE APPLICATION AND SHALL BE FACTORY
 APPLIED. EXCEPTION: WHERE INSTALLED IN ACCORDANCE WITH
 THE MANUFACTURER'S INSTALLATION INSTRUCTIONS, FIELD
 APPLICATION OF COATINGS AND WRAPPINGS SHALL BE
 PERMITTED FOR PIPE NIPPLES, FITTINGS AND LOCATIONS
 WHERE THE FACTORY COATING OR WRAPPING HAS BEEN DAMAGED
 OR NECESSARILY REMOVED AT JOINTS.
  
 10. SHEET PE-1 PLUMBING NOTES: NOTE #5 PLEASE DELETE
 THE FOLLOWING "402(1)" THIS IS FROM THE 2001 CODE WHICH
 IS THE WRONG CODE CYCLE. THE CORRECT TABLE FROM THE
 FBC-2004 W/2006 REV. IS 402.4(2). PLEASE CORRECT THIS
 ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK
 ON THE INDICATED PLAN SHEETS BY THIS PLAN EXAMINER FOR
 REFERENCE FOR THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-07-31 Cont ID  
Sent By jleech Date 2007-07-31 Time 10:43 Rev Time 0.00
Received By jleech Date 2007-07-31 Time 10:43 Sent To  
Notes
2007-07-31 11:06:09DENIED;
 SAME COMMENTS AS LAST REVIEW;
 1. GAS PERMIT REQUIRED. GAS CONTRACTOR TO SUBMIT PLANS
 WITH PERMIT APPLICATION.
 ******* IMPORTANT INFORMATION*******
 AS OF 8/25/06 GENERATOR PERMIT APPLICATIONS
 SHALL NOT BE ACCEPTED UNLESS THE ELECTRIC AND GAS
 INFORMATION IS TO BE SUBMITED AT THE SAME TIME. ( NO
 GAS APPLICATION OR PLAN HAS BEEN SUBMITED).
 2.SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 3.SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 4.TYPE OF GAS, (LP OR NATURAL)
 5.BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 6.SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8.SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 9.INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-06-04 Cont ID  
Sent By mperson Date 2007-06-04 Time 08:19 Rev Time 0.00
Received By mperson Date 2007-06-04 Time 08:19 Sent To  
Notes
2007-06-04 09:14:04DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/COM INSPECTION.
  
 ******IMPORTANT INFORMATION******
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL INFOR-
 MATION AND GAS (OR DIESEL) INFORMATION
 IS ALL SUBMITTED AT THE SAME TIME. THE
 GENERATOR, ELECTRICAL AND GAS/DIESEL IN-
 FORMATION WILL BE ROUTED TOGETHER. THIS
 WILL ENSURE THAT ALL OF THE INFORMATION (PARTICULARLY
 THE MANUFACTURER'S SPECI-
 FICATIONS AND INSTALLATION INSTRUCTIONS)
 ARE AVAILABLE TO ALL PLAN REVIEWERS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. PLEASE INDICATE TYPE OF GAS, (LP OR NATURAL) ON GAS
 DRAWINGS.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: IF GAS DELIVERY PRESSURE IS 2 PSI OR GREATER
 PLEASE SUBMIT MANUFACTURER SPECIFICATON SHEETS OF MP
 REGULATOR INDICATING THE MANUFACTURER'S NAME, MAXIMUM
 BTU LOAD CAPACITY AND SHOW A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY (NRTL).
  
 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS ON FUTURE SUBMITTED GAS DRAWINGS.
  
 9. NOTE: A GAS PERMIT CAN NOT BE ISSUED UNTIL A
 GEN/COM PERMIT APPLICATION HAS BEEN APPROVED BY ZONING
 FOR THE GENERATOR LOCATION.
  
 10. NOTE: PLANS ARE NOT ACCEPTABLE PER FBC-2004
 CHAPTER 1, SECTIONS 106.1.1 AND 106.1.3, PLEASE DO NOT
 MODIFY PLANS WITH PEN OR PENCIL ONCE PLANS HAVE BEEN
 SIGNED AND SEALED BY THE DESIGN PROFESSIONAL. (SEE
 SUBMITTED SITE PLANS)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-06-04 Cont ID  
Sent By adarroug Date 2008-06-04 Time 14:10 Rev Time 0.00
Received By adarroug Date 2008-06-04 Time 14:10 Sent To E
Notes
2008-06-04 14:11:04TO "COMM" BD#14

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-03-18 Cont ID  
Sent By adarroug Date 2008-03-18 Time 11:11 Rev Time 0.00
Received By adarroug Date 2008-03-18 Time 11:11 Sent To  
Notes
2008-03-19 13:22:57TO "COMM" BD#29
2008-03-18 11:12:22WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-20 Cont ID  
Sent By adarroug Date 2007-11-20 Time 15:37 Rev Time 0.00
Received By adarroug Date 2007-11-20 Time 15:37 Sent To  
Notes
2007-11-30 13:48:07TO "COMM" BD#46
2007-11-20 15:37:35WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 16:08 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 16:08 Sent To  
Notes
2007-09-20 11:34:24TO "COMM" BD#42
2007-08-27 16:08:54WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-28 Cont ID  
Sent By adarroug Date 2007-06-28 Time 16:55 Rev Time 0.00
Received By adarroug Date 2007-06-28 Time 16:55 Sent To  
Notes
2007-07-16 08:51:19TO "COMM" BD#52
2007-06-28 16:56:06WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-06-11 Time   Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 14:44 Sent To  
Notes
2007-05-02 13:27:13TO "COMM' BD#9
2007-04-23 14:44:50WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-12-06 Cont ID  
Sent By rregueir Date 2007-12-06 Time 07:58 Rev Time 0.00
Received By rregueir Date 2007-12-06 Time 07:58 Sent To  
Notes
2007-12-06 07:59:22PASSED PENDING GAS REVIEW APPROVAL. MECH STAMP NOT
 REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-10-18 Cont ID  
Sent By rregueir Date 2007-10-18 Time 10:59 Rev Time 0.00
Received By rregueir Date 2007-10-18 Time 10:52 Sent To  
Notes
2007-10-18 10:53:35REVIEW #: 3
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. NOT ADDRESSED. NO INFORMATION PROVIDED.
  
 2. NOT ADDRESSED. NO INFORMATION PROVIDED.
  
 3. NOT ADDRESSED. NO INFORMATION PROVIDED.
  
 THERE APPEARS TO HAVE BEEN NO RESPONSE TO ANY COMMENTS
 FROM REVIEW DATED 7/26/07. PLEASE RESPOND TO EACH
 COMMENT AND SHOW COMPLIANCE WITH SAME.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-07-26 Cont ID  
Sent By rregueir Date 2007-07-26 Time 11:56 Rev Time 0.00
Received By rregueir Date 2007-07-26 Time 11:56 Sent To  
Notes
2007-07-26 11:55:56----------------DENIED-------------------
  
 FBC 4002 CODE FAMILY W/ 2005 AND 2006 REVISIONS
 NFPA 37-02
  
 1. SHOW ON SITE PLAN THE DISTANCE OF GENERATOR FROM
 PROPERTY LINES AND ADJACENT BUILDINGS.
  
 2. GENERATOR SHALL BE INSTALLED PER MANUFACTURER'S
 INSTALLATION INSTRUCTIONS, WHICH WERE NOT PROVIDED.
 PROVIDE INFORMATION SUCH AS REQUIRED CLEARANCE FROM
 WALLS/BUILDINGS FOR SERVICE, MAINTENANCE, AIRFLOW FOR
 COOLING AND COMBUSTION.
  
 3. SHOW WEATHERPROOF ENCLOSURE AND ATTACHMENT TO SLAB
 TO BE DESIGNED FOR MIN. 140 MPH WIND ZONE PER FBC,M
 301.13 AND FBC CH. 16
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-14 Cont ID  
Sent By rregueir Date 2007-05-14 Time 07:42 Rev Time 0.00
Received By rregueir Date 2007-05-11 Time 15:47 Sent To  
Notes
2007-05-14 07:41:39------------DENIED--------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
 FBC CH 1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THESE PLANS ARE NOT ACCEPTABLE PER FBC 106.1.1 AND
 106.1.3. PLEASE DO NOT MODIFY PLANS WITH PEN OR PENCIL
 ONCE PLANS HAVE BEEN SIGNED AND SEALED BY THE
 SURVEYOR.
  
 RONALD J REGUEIRO
 561.805-6719
 [email protected]

Review Stop Z ZONING
Rev No 5 Status P Date 2008-04-01 Cont ID  
Sent By jroach Date 2008-04-01 Time 09:36 Rev Time 0.00
Received By jroach Date 2008-04-01 Time 09:36 Sent To  
Notes
2008-04-01 09:37:16***PASSED WITH PROVISOS***
  
 REFER TO ATTACHED TREE ALTERATION PERMIT FOR CONDITIONS
 OR PROVISOS.ADDITIONALLY, SHRUBS/HEDGES SHALL BE
 PLANTED AT TWO (2) FOOT INTERVALS AROUND THE EXTERIOR
 OF THE ENCLOSURE.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 4 Status F Date 2007-12-17 Cont ID  
Sent By jroach Date 2007-12-17 Time 11:37 Rev Time 0.00
Received By jroach Date 2007-12-17 Time 11:37 Sent To  
Notes
2007-12-17 11:38:12***FAILED***
  
 THIS IS THE 4TH ISSUANCE OF THE FOLLOWING COMMENT....
  
 1) MINOR AMENDMENT TO THE COMMERCIAL PLANNED
 DEVELOPMENT (CPD) SHALL BE SUBMITTED TO AND APPROVED BY
 THE PLANNING AND ZONING DEPARTMENT PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-09-20 Cont ID  
Sent By jroach Date 2007-09-20 Time 18:04 Rev Time 0.00
Received By jroach Date 2007-09-20 Time 18:04 Sent To  
Notes
2007-09-20 18:06:21***FAILED***
  
 THIS IS THE 3RD ISSUANCE OF THE FOLLOWING COMMENT....
  
 1) MINOR AMENDMENT TO THE COMMERCIAL PLANNED
 DEVELOPMENT (CPD) SHALL BE SUBMITTED TO AND APPROVED BY
 THE PLANNING AND ZONING DEPARTMENT PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT.
  
 FYI...THERE IS TO BE A MINIMUM OF FIVE (5) FEET OF
 LANDSCAPING ALONG THE ENTIRE LENGTH OF THE PARKING
 STALL WITH ONE (1) SHADE TREE.THE NEW DESIGN
 ELIMINATES A MAJORITY OF THIS REQUIRED LANDSCAPE
 ISLAND.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-07-22 Cont ID  
Sent By jroach Date 2007-07-22 Time 20:56 Rev Time 0.00
Received By jroach Date 2007-07-22 Time 20:56 Sent To  
Notes
2007-07-22 20:56:17***FAILED***
  
 1) MINOR AMENDMENT TO THE COMMERCIAL PLANNED
 DEVELOPMENT (CPD) SHALL BE SUBMITTED TO AND APPROVED BY
 THE PLANNING AND ZONING DEPARTMENT PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-09 Cont ID  
Sent By jroach Date 2007-05-09 Time 19:24 Rev Time 0.00
Received By jroach Date 2007-05-09 Time 19:24 Sent To  
Notes
2007-05-09 19:27:33***FAILED***
  
 1) MINOR AMENDMENT TO THE COMMERCIAL PLANNED
 DEVELOPMENT (CPD) SHALL BE SUBMITTED TO AND APPROVED BY
 THE PLANNING AND ZONING DEPARTMENT PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.