Plan Review Details - Permit 07040456
| Plan Review Stops For Permit 07040456 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-05-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-05-01 |
Time |
18:24 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-05-01 |
Time |
18:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-04-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-04-27 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-04-27 |
Time |
09:21 |
Sent To |
|
|
| Notes |
| 2007-04-27 10:06:23 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)THE PLANS SPECIFY JOHNS MANVILLE FOR THE FLAT | | | DECK.CHANGING THE PRODUCT REQUIRES A REVISION TO THE | | | BUILDING PERMIT AS THE DESIGNER OF RECORD HAS SPECIFIED | | | THE PRODUCT IN THE PLAN. | | | | | | 2.)IF YOU ARE USING THE GAF AS PROPOSED WITH THIS | | | PERMIT, INDICATE WHICH BASE SHEET FASTENER YOU ARE | | | USING AS THE DIFFERENT OPTIONS HAVE DIFFERENT DESIGN | | | PRESSURE LIMITATIONS. | | | | | | 2ND REVIEW - THIS CAN BE DONE ONLY AFTER THE ARCHITECT | | | HAS REVISED SHEET A102. | | | | | | 3.)THE ROOFING CONTRACTOR HAS SELECTED AN ASSEMBLY | | | WHICH IS DIFFERENT FROM THE ASSEMBLY CHOSEN AT THE TIME | | | OF PERMIT ISSUANCE FOR THE MASTER PERMIT, METAL ROOF. | | | THE ASSEMBLY THE ROOF CONTRACTOR HAS SELECTED HAS A | | | DESIGN PRESSURE LIMITATION OF -27.5, NOT COMPLIANT FOR | | | ZONE 1 (REQUIRES -32.3). | | | | | | 2ND REVIEW - THE CORRECT ASSEMBLY HAS BEEN INCLUDED. | | | HOWEVER, SEE NEW COMMENT REGARDING ENGINEER'S | | | PRESSURES. | | | | | | 4.)ZONES 2 AND 3 REQUIRE -68.1 AS PER PLAN.SEE | | | LIMITATION #1, PAGE 8.CALCULATIONS PREPARED BY AN | | | ARCHITECT, ENGINEER OR REGISTERED ROOF CONSULTANT | | | REQUIRED. | | | | | | 2ND REVIEW - NOT ADDRESSED. | | | | | | 5.)ADDRESSED. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-04-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-04-16 |
Time |
10:05 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-04-16 |
Time |
10:05 |
Sent To |
|
|
| Notes |
| 2007-04-16 10:30:54 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)THE PLANS SPECIFY JOHNS MANVILLE FOR THE FLAT | | | DECK.CHANGING THE PRODUCT REQUIRES A REVISION TO THE | | | BUILDING PERMIT AS THE DESIGNER OF RECORD HAS SPECIFIED | | | THE PRODUCT IN THE PLAN. | | | | | | 2.)IF YOU ARE USING THE GAF AS PROPOSED WITH THIS | | | PERMIT, INDICATE WHICH BASE SHEET FASTENER YOU ARE | | | USING AS THE DIFFERENT OPTIONS HAVE DIFFERENT DESIGN | | | PRESSURE LIMITATIONS. | | | | | | 3.)THE ROOFING CONTRACTOR HAS SELECTED AN ASSEMBLY | | | WHICH IS DIFFERENT FROM THE ASSEMBLY CHOSEN AT THE TIME | | | OF PERMIT ISSUANCE FOR THE MASTER PERMIT, METAL ROOF. | | | THE ASSEMBLY THE ROOF CONTRACTOR HAS SELECTED HAS A | | | DESIGN PRESSURE LIMITATION OF -27.5, NOT COMPLIANT FOR | | | ZONE 1 (REQUIRES -32.3). | | | | | | 4.)ZONES 2 AND 3 REQUIRE -68.1 AS PER PLAN.SEE | | | LIMITATION #1, PAGE 8.CALCULATIONS PREPARED BY AN | | | ARCHITECT, ENGINEER OR REGISTERED ROOF CONSULTANT | | | REQUIRED. | | | | | | 5.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED | | | IN ADDITION TO THE NOA SUBMITTED, FAC9B72. | | | WWW.FLORIDABUILDING.ORG | | | | | | | | | | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2007-04-17 |
|
|
Cont ID |
|
| Sent By |
ssherman |
Date |
2007-04-17 |
Time |
17:41 |
Rev Time |
0.00 |
| Received By |
ssherman |
Date |
2007-04-17 |
Time |
17:41 |
Sent To |
|
|
| Notes |
| 2007-04-17 17:41:35 | HISTORICAL APPROVAL PER JILLIAN PAPA |
|
|
|