Plan Review Details - Permit 07040449
Plan Review Stops For Permit 07040449
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-01 Cont ID  
Sent By choops Date 2007-05-01 Time 13:56 Rev Time 0.00
Received By jgomez Date 2007-05-01 Time 07:38 Sent To Z
Notes
2007-05-01 08:06:09BUILDING REVIEW CHECKLIST:
 1- SHEET 1 OF 3:
 A) TYPICAL INTERIOR BEARING WALL: CLARIFY WHY IS
 THERE A DROP BETWEEN BEDROOM AND LOUNGE AREA? WHICH ONE
 IS THE LOWEST AREA? SPECIFY FINISH FLOOR AREA IN
 RELATION TO FINISH GRADE? SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 B) TYPICAL INTERIOR BEARING WALL DOESN'T MATCH
 INFORMATION SUBMITTED ON PROPOSED FLOOR PLAN. THERE IS
 AN EXISTING 4"X6" BEAM WHICH IS NOT SHOWN ON THE
 SECTION/DETAIL..ALL INFORMATION TO MATCH. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 C) SIZE OF WINDOWS SPECIFIED IN THE BEDROOM DON'T
 COMPLY WITHSEC. R310 OF 2004 FLORIDA RESIDENTIAL CODE
 IF USING SINGLE HUNG OR SLIDING WINDOWS.CLEARLY
 IDENTIFY TYPE OF WINDOW AND REVISE SIZE AS REQUIRED TO
 COMPLY WITH EGRESS REQUIREMENTS.
  
 D) EMERGENCY EGRESS NOTES: UPDATE ALL INFORMATION.
 SEE SEC. R310 OF 2004 FLORIDA RESIDENTIAL CODE FOR
 CORRECT CODE SECTIONS TO BE REFERENCED AND REVISE AS
 REQUIRED.
  
 2- SHEET 2 OF 3:
 A) FOUNDATION PLAN DOESN'T MATCH SECTION DETAIL FOR
 INTERIOR BEARING WALL SHOWN ON SHEET 1 OF 3. REVISE AS
 REQUIRED TO MATCH.
  
 B) CONCRETE SLAB NOTESHOWN IN THE FOUNDATION PLAN
 ISNOT CLEAR.FINISH FLOOR ELEVATION IS NOT CLEAR.
 IS THIS A NEW CONCRETE SLAB?MISSINGSPECS FOR
 TERMITE TREATMENT AND SOIL BEARING CAPACITY?.
  
 C) PROVIDE ONLY THE DETAILS AND NOTES THAT APPLY TO
 THIS PROJECT TO EXPEDITE REVIEW PROCESS AND AVOID
 CONFLICTS OR DELAYS.
  
 3-COMPLETE SCOPE OF WORK IS NOT CLEAR. NEED TO
 IDENTIFY SPECIFIC WORK TO BE PERFORMED AND VALUATION
 DECLARED IN THE PERMIT APPLICATION NEED TO BE UPDATED
 TO REFLECT ALL WORK AND INCLUDE THE ENGINEER FEES AS
 REQUIRED BY SEC. 108.3 OF CITY AMENDMENTS TO FBC 2004.
  
 4- ENERGY CALCULATIONS:
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
 B) REVISE INFORMATION ON TOP OF FORM. EG: OWNER
 INFORMATION IS INCORRECT AND PROVIDE CORRECT BUILDING
 ADDRESS.
  
 5- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 6- AFTER ALL PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD (561)233-5115) TO VERIFY IF
 IMPACT FEES ARE DUE OR NOT. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF IMPACT FEES ARE DUE.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) SIMPSON CONNECTORS SPECIFIED ON PLANS AND
 DETAILS.
  
 B) WINDOWS AND EXTERIOR DOORS IF REPLACING THEM.
 ***NOTE: SEE COMMENT REGARDING EGRESS WINDOWS.
  
 C) STORM SHUTTERS IF REPLACING WINDOWS.
 ***NOTE: STORM SHUTTERS REQUIRE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE.
  
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-18 Cont ID  
Sent By btrobaug Date 2007-04-18 Time 16:53 Rev Time 1.00
Received By btrobaug Date 2007-04-18 Time 12:14 Sent To M
Notes
2007-04-18 14:04:06 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE EQUIPMENT GROUNDING CONDUCTOR MUST COMPLY WITH
 250.66. INDICATE THE SIZE ON THE PLAN. AN EQUIPMENT
 GROUNDING CONDUCTOR MUST BE INSTALLED FROM THE FIRST
 MEANS OF DISCONNECT TO THE PANEL PER 250.118, SIZED PER
 250.122.
  
 2} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3} THERE IS AN EQUIPMENT GROUND REQUIRED TO BE RAN WITH
 THE FEEDER FROM THE DISCONNECT TO THE PANEL, SEE
 250.122.
  
 4} SHOW THE LOCATION OF THE AHU AND A/C DISCONNECTS PER
 440.14,RECEPTACLE PER 210.63,
  
 5} THE AHU IS LISTED AS FUTURE ON THE PANEL SCHEDULE,
 THERE IS ONE SHOWN ON THE PLAN, ALSO LISTED IN THE
 MECHANICAL NOTES AND THERE IS A A/C COMPRESSOR ON THE
 SCHEDULE. CORRELATE EQUIPMENT THAT IS TO BE PART OF
 THIS PERMIT.
  
 6} THERE ARE TWO REFRIGERATORS LISTED ON THE SCHEDULE,
 ONLY ONE ON THE PLAN. ALSO DON'T RECOGNIZE EQUIPMENT
 CALLED "AIR CONDENSER" OR "PROTECTION" LISTED ON THE
 SCHEDULE. SEE 408.4. NEC PLEASE SEE NEW VERBAGE FOR
 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE SUFFICIENT
 DETAIL TO ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM
 ALL OTHERS."
  
 7} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). NO CIRCUIT IS SHOWN ON THE
 SCHEDULE
  
 8} THE PANEL SCHEDULE LISTS 2 KITCHEN LIGHT CIRCUITS
 AND THERE IS ONLY ONE KITCHEN LIGHT.
  
 9} THE PANEL SCHEDULE LISTS TWO SMALL APPLIANCE
 CIRCUITS 1 AND2.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-07 Cont ID  
Sent By jleech Date 2007-05-07 Time 07:55 Rev Time 0.00
Received By jleech Date 2007-04-16 Time 13:35 Sent To  
Notes
2007-04-16 13:35:16TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-20 Cont ID  
Sent By tgordon Date 2007-04-20 Time 08:05 Rev Time 0.30
Received By tgordon Date 2007-04-20 Time 08:05 Sent To P
Notes
2007-04-20 08:17:38*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) PLANS PAGE 3 OF 3 SHOW A SPLIT A/C SYSTEM BEING
 INSTALLED AND ALSO NOTED IN THE LOUNGE AREA "WINDOW
 UNIT A/C TO BE INSTALLED BY OWNER", IF THIS IS CORRECT
 PLEASE HAVE COOLING LOAD CALCULATIONS AND ENERGY
 CALCULATIONS SHOW TWO A/C SYSTEMS AND GIVE INFORMATION
 OF WINDOW UNIT ON A/C EQUIPMENT LISTING.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-07 Cont ID  
Sent By choops Date 2007-05-07 Time 07:40 Rev Time 0.00
Received By jleech Date 2007-05-07 Time 07:40 Sent To  
Notes
2007-05-07 07:55:07DENIED;
 1. ELECTRICAL PLAN SHOWS OUTLETS FOR FOR A AUTOMATIC
 CLOTHES WASHER AND A DRYER, LOCATION NOT SHOWN ON
 DRAWINGS. A WASHING MECHINE HOOK UP IS REQUIRED, SEE
 FBC-2004 PLUMBING TABLE 403.1.
 2. ADD NOTE TO PLANS, "WATER HEATER TO BE ON A 4"
 CONCRETE PAD". SHOW ENCLOSURE FOR WATER HEATER. IF IT
 IS A MANUFACTURED PRODUCT PLEASE SUBMIT MANUFACTURE'S
 SPECIFICATIONS.
 3. SHOW ON PLANS FLOOR PLAN BEFORE CHANGES.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2007-05-01 Cont ID  
Sent By choops Date 2007-05-01 Time 11:41 Rev Time 0.00
Received By choops Date 2007-05-01 Time 11:41 Sent To P
Notes
2007-05-01 11:43:35***FAILED***
  
  
 1) PLEASE PROVIDE 2 COPIES OF AND UPDATED SURVEY (NO
 MORE THAN A YEAR OLD) SHOWING THE LOCATIONS OF EXISTING
 ACCESSORY STRUCTURE AND ALL DIMENSIONS
  
 2) PLEASE PROVIDE THE LOCATION AND DIMENSIONS (FROM
 PROPERTY LINES) TO PROPOSED MECHANICAL EQUIPMENT.
  
 3) PLEASE PROVIDE AND EXISTING FLOOR PLAN AND A
 DEMOLITION PLAN TO SHOW THE RELATIONSHIP BETWEEN WHAT
 EXISTS AND WHAT IS PROPOSED.
  
 4) CITY RECORDS INDICATE THIS IS A 2 STORY BUILDING
 WITH AN EXISTING APARTMENT, ARE THE PROPOSED
 RENOVATIONS TO THE EXISTING APARTMENT, OR ESTABLISHMENT
 OF A NEW APARTMENT?IF IT IS A NEW ESTABLISHMENT ON
 THE FIRST FLOOR, IT IS PROHIBITED.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720