Plan Review Details - Permit 07040420
Plan Review Stops For Permit 07040420
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-09-07 Cont ID  
Sent By mjacobs Date 2007-09-07 Time 06:26 Rev Time 0.00
Received By mjacobs Date 2007-09-06 Time 12:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-20 Cont ID  
Sent By mjacobs Date 2007-07-20 Time 10:24 Rev Time 0.00
Received By mjacobs Date 2007-07-20 Time 07:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-16 Cont ID  
Sent By mjacobs Date 2007-06-16 Time 10:00 Rev Time 0.00
Received By mjacobs Date 2007-06-16 Time 07:39 Sent To  
Notes
2007-06-16 10:00:43BUILDING PLAN REVIEW
 PERMIT: 0704042
 ADD: 222 LAKEVIEW AVE #1700
 CONT: PASS INTERNATIONAL
 TEL: (954)421-9000
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2)THE TITLE BLOCK SHALL INDICATE THE CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ARCHITECTURAL FIRM. FLORIDA
 STATUTES 481.221(2)ALL FINAL CONSTRUCTION DOCUMENTS
 AND INSTRUMENTS OF SERVICE WHICH INCLUDE DRAWINGS,
 PLANS, SPECIFICATIONS, OR REPORTS PREPARED OR ISSUED BY
 THE REGISTERED ARCHITECT AND BEING FILED FOR PUBLIC
 RECORD SHALL BEAR THE SIGNATURE AND SEAL OF THE
 REGISTERED ARCHITECT WHO PREPARED OR APPROVED THE
 DOCUMENT AND THE DATE ON WHICH THEY WERE SEALED. THE
 SIGNATURE, DATE, AND SEAL SHALL BE EVIDENCE OF THE
 AUTHENTICITY OF THAT TO WHICH THEY ARE AFFIXED. NOTE:
 ALL INFORMATION ON THE SEAL SHALL BE LEGIBLE ON EACH
 SHEET. CHECK ALL PAGES FOR CLARITY OF THE SEAL.
  
 3)ON SHEET A3.1 DETAIL L10 SHOWS DOORS IN FRONT OF
 THE SINK. THE DOORS SHALL BE REMOVED TO PROVIDE THE
 FORWARD APPROACH FOR ACCESSIBILITY.SEE FBC 11-4.24.
  
 4)SHOW IN DETAIL HOW THE RECPTIONIST AREA/COUNTER
 WILL MEET THE REQUIREMENTS OF SECTION 11-7. A PORTION
 OF THE MAIN COUNTER SHALL BE 36 INCHES LONG AND 36
 INCHE HIGH.
  
 5)THE ROOM NEXT TO #3 INTERVIEW ROOM, WILL A DOOR BE
 INSTALL OR WILL IT BE AN OPENING. SHOW THE DIMENTION OF
 THE OPENING ON THE PLANS OR THE SWING OF THE DOOR.
  
 6)ALL DRINKING FOUNTAINS AND WATER COOLERS SHALL MEET
 THE REQUIREMENTS OF 11-4.15 AND FIGURE 27.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-23 Cont ID  
Sent By mjacobs Date 2007-04-23 Time 10:53 Rev Time 0.00
Received By mjacobs Date 2007-04-23 Time 07:34 Sent To  
Notes
2007-04-23 12:12:15BUILDING PLAN REVIEW
 PERMIT: 07040420
 ADD: 222 LAKEVIEW AVE
 CONT: PASS INTERNATIONAL INC.
 TEL: (954)421-9000
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)THE EXISTING ROOM NEXT TO INTERVIEW #3 NEEDS A
 DOOR, UNLESS THIS AREA WILL BE CLOSED OFF. SHOW THE
 EXTENSION OF THE NEW WALL EXTENDING FROM INTERVIEW ROOM
 #2 TO THE EXTERIOR WALL. SEE THE DEMO SHEET D1.1 AND
 A1.1.
 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 TE WORK PROPOSED.
  
 4)481.221 IF PRACTICING THROUGH A DULY AUTHORIZED
 BUSINESS, INDICATE THE CERTIFICATE OF AUTHORIZATION
 NUMBER ON THE TITLE BLOCK.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-09-10 Cont ID  
Sent By btrobaug Date 2007-09-10 Time 07:20 Rev Time 0.00
Received By btrobaug Date 2007-09-10 Time 06:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-07-19 Cont ID  
Sent By btrobaug Date 2007-07-19 Time 16:35 Rev Time 0.00
Received By btrobaug Date 2007-07-18 Time 16:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-13 Cont ID  
Sent By btrobaug Date 2007-06-13 Time 16:44 Rev Time 0.33
Received By btrobaug Date 2007-06-13 Time 16:11 Sent To  
Notes
2007-06-13 16:44:39 
  
  
  
  
 NONCOMPLIANT
  
 THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK MUST
 SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 FAC. THE
 SEAL IS INDISCERNIBLE. ALSO MUST PROVIDE A TITLE
 BLOCK.
  
 A SEPARATE LOW VOLTAGE PERMIT IS REQUIRED FOR THE
 ACCESS CONTROL SYSTEM, SPECIFICATIONS FOR ALL DEVICES
 AND EQUIPMENT MUST BE SUBMITTED WITH THE LOW VOLTAGE
 APPLICATION. TWO COPIES OF THIS SHEET, SIGNRD AND
 SEALED MUST BE SUBMITTED WITH THAT APPLICATION FOR
 RECORD RETENTION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-17 Cont ID  
Sent By btrobaug Date 2007-04-17 Time 14:10 Rev Time 1.00
Received By btrobaug Date 2007-04-17 Time 11:24 Sent To  
Notes
2007-04-17 14:00:12 
  
 NONCOMPLIANT
  
 THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK MUST
 SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 FAC. THE
 SEAL IS INDISCERNIBLE.
  
 THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE.
  
 A SEPARATE LOW VOLTAGE PERMIT IS REQUIRED FOR THE
 ACCESS CONTROL SYSTEM, SPECIFICATIONS FOR ALL DEVICES
 AND EQUIPMENT MUST BE SUBMITTED WITH THE LOW VOLTAGE
 APPLICATION. TWO COPIES OF THIS SHEET, SIGNRD AND
 SEALED MUST BE SUBMITTED WITH THAT APPLICATION FOR
 RECORD RETENTION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-09-25 Cont ID  
Sent By mawillia Date 2007-09-25 Time 19:18 Rev Time 0.00
Received By mawillia Date 2007-09-25 Time 18:57 Sent To  
Notes
2007-09-25 19:18:27*****APPROVED*****
  
  
 REVISED PLAN SHEETS A1.1 AND E-2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-07-20 Cont ID  
Sent By mwennerg Date 2007-07-20 Time 15:18 Rev Time 0.00
Received By mwennerg Date 2007-07-20 Time 15:18 Sent To  
Notes
2007-07-20 15:19:53PLANS APPROVED ON 6/20/07 AND STAMPED ON 7/20/07.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-06-20 Cont ID  
Sent By mawillia Date 2007-06-20 Time 12:44 Rev Time 0.00
Received By mawillia Date 2007-06-20 Time 12:31 Sent To  
Notes
2007-06-20 12:43:37*****PROVISO*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW APPEAR
 TO HAVE BEEN ADDRESSED, HOWEVER, THE APPROPIATE PLAN
 SHEET(S) WILL BE STAMPED WHEN ALL OTHER PLAN REVIEWS
 HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-18 Cont ID  
Sent By mwennerg Date 2007-04-18 Time 14:14 Rev Time 0.00
Received By mwennerg Date 2007-04-18 Time 14:13 Sent To  
Notes
2007-04-18 14:18:19***DENIED***
  
 1) PLEASE CLARIFY CODE REFERENCE, NFPA 101 27-33. SHT
 A4.1
  
 2) DOORS SHALL COMPLY WITH NFPA 101, SEC. 7.2.1. SHT
 A4.1.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 4) PLEASE PROVIDE MANUFACTURER SPEC SHEETS, MORE
 INFORMATION AND DETAILS REGARDING ACCESS CONTROL
 SYSTEM. SPECIAL LOCKING ARRANGEMENTS TO COMPLY WITH
 NFPA 101, SEC. 7.2.1.6.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-17 Cont ID  
Sent By adarroug Date 2007-09-17 Time 15:12 Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 15:12 Sent To M
Notes
2007-09-17 15:13:13TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 09:16 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 09:16 Sent To  
Notes
2007-09-04 10:59:08TO "BOB"#7
2007-08-27 09:16:55WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-03 Cont ID  
Sent By adarroug Date 2007-07-03 Time 15:42 Rev Time 0.00
Received By adarroug Date 2007-07-03 Time 15:42 Sent To  
Notes
2007-07-09 15:42:56TO "BOB"#18
2007-07-03 15:42:38WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-04 Cont ID  
Sent By adarroug Date 2007-06-04 Time 10:24 Rev Time 0.00
Received By adarroug Date 2007-06-04 Time 10:24 Sent To  
Notes
2007-06-05 14:45:50TO "BOB"#18
2007-06-04 10:24:14WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-24 Cont ID  
Sent By jleech Date 2007-04-24 Time 07:37 Rev Time 0.00
Received By jleech Date 2007-04-13 Time 16:25 Sent To  
Notes
2007-04-16 16:36:32TO "BOB"#12
2007-04-13 16:29:36WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-09-18 Cont ID  
Sent By tgordon Date 2007-09-18 Time 09:48 Rev Time 0.30
Received By tgordon Date 2007-09-18 Time 09:48 Sent To  
Notes
2007-09-18 09:49:19REVISION TO MECH. PLANS PAGE M1.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-09-07 Cont ID  
Sent By tgordon Date 2007-09-07 Time 10:53 Rev Time 0.20
Received By tgordon Date 2007-09-07 Time 10:53 Sent To  
Notes
2007-09-07 10:56:24REVISION TO MECH. PLANS PAGES M1 AND M2.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-07-10 Cont ID  
Sent By tgordon Date 2007-07-10 Time 10:52 Rev Time 0.30
Received By tgordon Date 2007-07-10 Time 10:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-06-12 Cont ID  
Sent By tgordon Date 2007-06-12 Time 15:27 Rev Time 1.20
Received By tgordon Date 2007-06-12 Time 15:27 Sent To  
Notes
2007-06-12 15:36:13*** DENIED ***
 *** THE FOLLOWING COMMENTS APPLY TO ALL THE PAGES OF
 THE SET OF PLANS.
 1) AS NOTED IN THE LAST REVIEW 4-17-07. INFORMATION
 MISSING IN TITLE BLOCK FOR ARCHITECT (ARCHITECT FIRM
 LICENSE NUMBER), SEE FAC 61G1-16.004 TITLE BLOCK. A
 TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 2) ARCHITECT FIRM LICENSE NUMBER FOR YOSHINO
 TRIESCHMANN DESIGN GROUP EXPIRED 2-28-07 AND CLOSED,
 SEE ATTACHED LICENSE INFORMATION, PLEASE CORRECT. ***
 INTERIOR DESIGN BUSINESS LICENSE NUMBERS ADDED TO FRONT
 SHEET WITH ARCHITECT SEAL IS NOT APPROPRIATE, PLEASE
 CORRECT ARCHITECT FIRM LICENSE NUMBER OR YOU MAY REMOVE
 THE DESIGN GROUP FROM ALL TITLE BLOCKS AND ADD ALL
 PERTINENT INFORMATION FOR ARCHITECT TO TITLE BLOCK.
  
 3) SEE ELECTRICAL REVIEW NOTE REGARDING SEAL,THIS
 NOTE APPLIES TO ALL PAGES IN SET OF PLANS, PLEASE
 CORRECT.
  
 4) NEW COMMENT,SEE ATTACHED NOTICE FS 553.80(2)(B)
 REGARDING FOUR TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-17 Cont ID  
Sent By tgordon Date 2007-04-17 Time 15:21 Rev Time 0.45
Received By tgordon Date 2007-04-17 Time 15:21 Sent To  
Notes
2007-04-17 15:29:20*** DENIED ***
 1) INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT
 (FIRM LICENSE NUMBER), SEE FAC 61G1-16.004 TITLE
 BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 2) FIRM LICENSE NUMBER FOR YOSHINO TRIESCHMANN DESIGN
 GROUP EXPIRED 2-28-07, PLEASE CORRECT.
  
 3) SEE ELECTRICAL REVIEW NOTE REGARDING SEAL, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-09-10 Cont ID  
Sent By jleech Date 2007-09-10 Time 15:07 Rev Time 0.00
Received By jleech Date 2007-09-10 Time 15:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-07-23 Cont ID  
Sent By jleech Date 2007-07-23 Time 07:22 Rev Time 0.00
Received By jleech Date 2007-07-23 Time 07:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-06-19 Cont ID  
Sent By jleech Date 2007-06-19 Time 08:38 Rev Time 0.00
Received By jleech Date 2007-06-19 Time 08:38 Sent To  
Notes
2007-06-19 09:02:25DENIED;
 1. BREAK SINK KNEE CLEARANCE NOT ADDRESSED. (SECOND
 REQUEST) PAGE 3.1 DETAIL A-7 (BREAK SINK) CABINET DOORS
 NOT PERMITED ON CABINET UNDER SINK. NO DOOR PERMITED TO
 SWING INTO THE CLEAR FLOOR SPACE. THE LOCATION OF THE
 SUMP PUMP MUST NOT LOCATED IN THE CLEAR FLOOR SPACE
 UNDER THE BREAK SINK. SHOW LOCATION OF PUMP ON PLANS
 WITH NOTE.
 2. PAGE D-1 NOTE 3, EXISTING CABINTRY, SINK AND PIPES
 TO BE REMOVED. NO DEAD ENDS MORE THAN 2' PERMITED IN
 THE SANITARY PLUMBING SYSTEM.
 3. COMMENTS BY ELECTRICAL AND MECHANICAL PLAN REVIEWS (
 ADMINISTRATION CODE PROBLEMS)MUST ALSO BE ADDRESSED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-24 Cont ID  
Sent By jleech Date 2007-04-24 Time 07:10 Rev Time 0.00
Received By jleech Date 2007-04-24 Time 07:10 Sent To  
Notes
2007-04-24 07:36:26DENIED;
 1.PAGE 3.1 DETAIL A-7 (BREAK SINK) DOOR AND KICK PLAT
 NOT TO CODE. SEE FBC-2004 BUILDING CHAPTER 11 HANDICAP
 CODE SECTION 11-4.24.3, KNEE CLEARANCE REQUIRED UNDER
 THE SINK, 27" HIGH 30" WIDE, AND 19" DEEP. PLEASE SHOW
 A FRONT VIEW ON PLANS AND MAKE REFORANCE TO SECTIONS
 11-4.24.4, DEPTH OF SINK, 11-4.24.6 EXPOSED PIPES AND
 11-4.24.7 FAUSE TO BE LEVER OPERATED.
 2. PAGE D.1.1, KEY NOTE 3; ALL DELETED SANITARY AND
 VENT PIPING MUST BE REMOVED SO NO DEAD ENDS ARE IN THE
 SANITARY SYSTEM. FBC - 2004 PLUMBING SECTION 704.5 .
 3.THE SUBMITED DRAWINGS DO NOT SHOW A DRINKING FOUNTAIN
 IN THE COMMON AREA. IF ONE DOES NOT EXIST THEN THE
 WATER COOLER MUST BE A DRINKING FOUNTAIN WITH A DRAIN.
 SEE TABLE 403.1 AND SECTION 410. THE DRINKING FOUNTAIN
 OR COOLER MUST MEET H/C REQUIREMENTS. SUBMIT CUT SHEET
 FOR WATER COOLER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-07-19 Cont ID  
Sent By choops Date 2007-07-19 Time 17:20 Rev Time 0.00
Received By choops Date 2007-07-19 Time 17:20 Sent To  
Notes
2007-07-19 17:21:58*VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.


Account Summary | Usage Policy | Privacy Policy