| 2007-04-30 11:45:27 | ** UNSAT ** |
| | |
| | ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1 |
| | ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF |
| | WEST PALM BEACH. |
| | |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | |
| | 2) NOTE: PLEASE VERIFY SYSTEM BEING INSTALLED AND |
| | PROPOSED. PLEASE SEE THE GENERATOR LOAD CALCULATIONS |
| | AND SPECIFICATIONS INDICATE THIS UNIT AS 120/240 SINGLE |
| | PHASE, AND THE PLANS INDICATE THE EQUIPMENT/PANEL BEING |
| | 120/208V. |
| | PLEASE ALSO SEE THAT PART OF THE RISER SHOWS THIS |
| | SERVICE AS THREE PHASE.? |
| | FBC 106 .1.2 |
| | |
| | 3) NOTE: PLEASE SEE THE RISER STILL SEEMS TO SHOW A |
| | CONNECTION FROM THE GUTTER TO THE SAME PANEL WHICH IS |
| | BEING FED FROM THE GENERATOR? |
| | PLEASE CLARIFY RISER AS SHOWN AS THE EXISTING |
| | CONNECTION FROM GUTTER WOULD BE REQUIRED TO BE REMOVED |
| | INCLUDING CONDUIT. |
| | PLEASE CLARIFY RISER AS SHOWN WITH THE FEED FROM FPL. |
| | DOES THIS COME THROUGH THE METER? IS THIS A 600AMP |
| | METER/ OR CT. |
| | FBC 106.1.2, |
| | NEC 215.5 |
| | |
| | 4) NOTE: PLEASE CLARIFY THE LOAD CALCULATIONS AS SHOWN. |
| | PLEASE SEE THESE MENTION APARTMENT LOADS, HOWEVER THE |
| | LOADS ARE NOT COMPLETE FOR APARTMENTS. |
| | PLEASE SEE THE LOADS MUST BE BASED ON THE NEC. 220 |
| | (2005 NEC). |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SEE THE LOAD CALCULATION SHEET |
| | INDICATES THE GENERATOR BREAKERAT 200AMPS, THE RISER |
| | SHOWS THIS AS 150AMPS, AND THE SPECS INDICATES 175AMP? |
| | PLEASE COORDINATE ALL, AT THIS TIME THE SIZES OF |
| | CONDUCTORS ETC CAN NOT BE VERIFIED. |
| | 240.4, 310.16 ETC. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE THE SPECS SUBMITTED FOR THE ATS |
| | DOES NOT INDICATE A DISCONNECTING MEANS FOR THE |
| | LINE/NORMAL SIDE AND A BREAKER/DISCONNECT FOR THE |
| | GENERATOR/EM SIDE? |
| | PLEASE REVISE SPECS OR RISER TO INCLUDE A DISCONNECTING |
| | MEANS AT THE SERVICE LOCATION. |
| | 225.31-225.39. |
| | ** PLEASE KNOW, AS ZONING COMMENTS WILL MOST LIKELY |
| | REQUIRE THIS UNIT TO BE IN AN ENCLOSURE THE BREAKER ON |
| | THE GENERATOR MAY NOT BE USED. |
| | |
| | 7) NOTE: PLEASE PROVIDE ALL ELECTRICAL EQUIPMENT ON THE |
| | PLAN LAYOUT SHEET. |
| | FBC 106.1.2 |
| | LOCATIONS NEED TO BE VERIFIED FOR 230, 225 ETC. |
| | |
| | 8) NOTE: PLEASE SEE THE SPECIFICATIONS INDICATES THIS |
| | AS BEING CONNECTED TO A PROPANE TANK, YET THE GAS |
| | PERMIT APPLICATION MENTIONS THIS WILL BE A NATURAL GAS |
| | UNIT? |
| | PLEASE SEE COMMENTS FROM PLUMBING. |
| | |
| | 9) NOTE: PLEASE SEE THE NOC SUBMITTED AS EXPIRED PER FS |
| | 713.13(2). |
| | PLEASE SEE THE NOC WILL BE REQUIRED TO BE RE-RECORD |
| | BEFORE PICKING UP THE PERMIT. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-04-27 17:00:40 | PLANS REMOVED FROM INCOMING/TABLE IN ELEC FOR REVIEW. |