Plan Review Details - Permit 07040396
Plan Review Stops For Permit 07040396
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-04-27 Cont ID  
Sent By shill Date 2007-04-27 Time 15:55 Rev Time 0.00
Received By shill Date 2007-04-27 Time 15:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-04-20 Cont ID  
Sent By shill Date 2007-04-20 Time 15:41 Rev Time 0.00
Received By shill Date 2007-04-20 Time 15:41 Sent To  
Notes
2007-04-20 15:54:45****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
 REGARDING THE LETTER PREPARED BY JOHN HOLT, PE, NOTE
 THE FOLLOWING:
  
 1.THE ENGINEERING DOES NOT REFER TO THE NOA.PRODUCT
 APPROVALS ARE TO BE REVIEWED BY DESIGNER OF RECORD,
 FBC*106.3.3.
  
 2.THE ENGINEER STATES THAT THE CORNER IS 4" EACH
 DIRECTION.PLEASE REVISE, SEE FBC R 301.
  
 3.THE ENGINEER STATES THAT THE LAP NAILING IS 3", 4"
 IS THE MINIMUM SPACING, RAS117.
  
 4.THE ENGINEER STATES THAT THE CORNERIS TO HAVE 5
 1/2INCH SPACING.RAS117 REQUIRES THAT NAILING BE
 ROUNDED DOWN TO THE NEXT WHOLE NUMBER.
  
 5.THE ENGINEER STATES THAT HE IS USING 140 EXPOSURE C
 PRESSURES.ASCE7-02 OR FBC TABLE 1609.6.2.1(2)?
 ENGINEER DOES NOT SPECIFY DESIGN PRESSURES, SO I CANNOT
 DETERMINE WHETHER OR NOT ENHANCED FASTENING FOR ZONE 2,
 PERIMETER, IS REQUIRED.ENGINEER SPECIFIES ONLY THE
 FIELD AND CORNER, ZONES 1 AND 3.
  
 6.THE FIELD FASTENING SPECIFIED BY THE ENGINEER IS
 NOT COMPLIANT FOR THE ASSEMBLY THE CONTRACTOR HAS
 SELECTED.AS THE ENGINEER DOES NOT REFERENCE ANY NOA
 OR ASSEMBLY, DOES HE INTEND THAT THIS FASTENING IS FOR
 ANY ROOF SYSTEM?MOST HAVE FASTENING CLOSER THAN
 10INCHES.
  
 7.SEE GENERAL LIMITATION #7.PROVIDE CALCULATIONS IN
 ACCORDANCE WITH RAS117.
  
 A SET HAS BEEN RETAINED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-12 Cont ID  
Sent By shill Date 2007-04-12 Time 18:07 Rev Time 0.00
Received By shill Date 2007-04-12 Time 18:07 Sent To  
Notes
2007-04-12 18:09:37****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 ____1.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13.
  
 ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY:
  
 MEAN ROOF HEIGHT
  ROOF PITCH
  ROOF DECK TYPE
  AREA OF EACH ROOF TYPE
  
 ____3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS.
  
 _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
  
 ____ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.
  
 ____ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING