| Plan Review Stops For Permit 07040327 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-07-05 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-07-05 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-07-05 |
Time |
11:46 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-06-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-06-15 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-06-15 |
Time |
13:30 |
Sent To |
PC |
|
| Notes |
| 2007-06-15 15:46:21 | BUILDING PLAN REVIEW | | | PERMIT:07040327 | | | ADD:376 ORANGE WAY | | | CONT: | | | TEL: (561)###-#### | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | | ANTICIPATED COOPERATION. | | | | | | 2)THE FENCE DETAIL ON SHEET A-2 SHALL MEET THE | | | REQUIREMENTS OF SECTION R4101.17.1 THROUGH R4101.17.3. | | | THE HEIGHTS OF THE FENCE INDICATED ON THE DRAWINGS DO | | | MEET THE REQUIREMENTS OF THIS SECTION. SHOW HOW THE | | | LATCH FOR THE GATE WILL MEET THE 54" REQUIREMENT. SHOW | | | ON THE DRAWINGS HOW FAR AWAY FROM THE POOL THE FENCE | | | WILL BE INSTALLED. SEE SEC.R4101.17.1.13. | | | | | | 3) 13-612.1.ABC.2.3.2 COVERS REQUIRED. | | | SPAS AND HEATED SWIMMING POOLS SHALL BE | | | EQUIPPED WITH A COVER DESIGNED TO | | | MINIMIZE HEAT LOSS. | | | | | | 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST | | | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC | | | (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES | | | PER108.3 FBC* | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-05-02 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-05-02 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-05-02 |
Time |
07:42 |
Sent To |
PC |
|
| Notes |
| 2007-05-02 12:06:46 | BUILDING PLAN REVIEW | | | PERMIT: 07040327 | | | ADD: 376 ORANGE WAY | | | CONT: SUREZ CARLOS | | | TEL: (561)432-8683 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 1ST | | | ACTION: DENIED | | | | | | 1)THESPECIFICATIONS DIMENTIONS ARE DIFFERENT FROM | | | THOSE INDICATED ON THE POOL DRAWINGS.THE POOL | | | DIMENTIONS SHALL BE THE SAME. SEE SHEET A-2. | | | | | | 2)A SEPERATE PERMIT IS REQUIRED FOR THE FENCE. | | | | | | 3) INDICATE THE TOTAL SQUARE FOOTAGE FOR THE POOL DECK | | | EVEN THOUGH IS WILL BE DONE BY OTHERS. | | | | | | 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST | | | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC | | | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES | | | PER 108.3 FBC* | | | | | | 5)FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT. | | | NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE | | | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: | | | 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT | | | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | NOTE: THE POOL SHALL BE DESIGN TO FBC.2004 SEC.424.2 | | | PRIVATE SWIMING POOL AND 2004 RESIDENTIAL CODECHAPTER | | | 41. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-06-04 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-06-04 |
Time |
06:57 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2007-06-04 |
Time |
06:50 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2007-04-19 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-04-19 |
Time |
17:15 |
Rev Time |
0.25 |
| Received By |
btrobaug |
Date |
2007-04-19 |
Time |
16:59 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-06-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-27 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-27 |
Time |
16:14 |
Sent To |
Z |
|
| Notes |
| 2007-06-27 16:15:06 | TO "Z" BOX/RESUB--NEW SHEETS FOR "Z, P, B" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-06-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-06-01 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-01 |
Time |
08:16 |
Sent To |
E |
|
| Notes |
| 2007-06-01 08:17:14 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-05-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-24 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-24 |
Time |
11:41 |
Sent To |
Z |
|
| Notes |
| 2007-05-24 11:42:09 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-04-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-13 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-13 |
Time |
15:55 |
Sent To |
E |
|
| Notes |
| 2007-04-13 15:56:07 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2007-05-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-10 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2007-04-10 16:17:00 | TO "Z" BOX |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-07-03 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-07-03 |
Time |
13:09 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2007-07-03 |
Time |
13:09 |
Sent To |
B |
|
| Notes |
| 2007-07-03 13:15:08 | NOTE: THERE IS NO PLUMBING PERMIT BEING APPLIED FOR ON | | | THE POOL PERMIT APPLICATION. A PLUMBING PERMIT IS | | | REQUIRED FOR THE POOL, AND THERE IS NO POOL HEATER: | | | | | | ****************PROVISO**************** | | | 1) COMPLY WITH FBC-2004 SEC 424.2, OR | | | FBCR-2004 SEC R4101 PRIVATE SWIMMING | | | POOLS. | | | 2) FBC-2004 SEC. 424.2.7.2, OR | | | FBCR-2004 SEC. R4101.7.2 PUMPS AND | | | EQUIPMENT SHALL BE MOUNTED ON A | | | SUBSTANTIAL BASE IN A MANNER THAT WILL | | | ELIMINATE STRAIN ON PIPING.SLAB SHALL | | | BE A NOMINAL 4" THICK. | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2007-06-15 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-06-15 |
Time |
11:56 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2007-06-15 |
Time |
11:56 |
Sent To |
B |
|
| Notes |
| 2007-06-15 11:57:38 | NOTE: THERE IS NO PLUMBING PERMIT BEING APPLIED FOR ON | | | THE POOL PERMIT APPLICATION. A PLUMBING PERMIT IS | | | REQUIRED FOR THE POOL, AND THERE IS NO POOL HEATER: |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-04-24 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-04-24 |
Time |
11:49 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2007-04-24 |
Time |
11:49 |
Sent To |
B |
|
| Notes |
| 2007-04-24 13:09:24 | DENIED | | | REFERENCE: | | | ** FBC-2004 PLUMBING. | | | ** FBC-2004 SECTIONS 424.2 AND R4101 SWIMMINGS. | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. SHEET AS-3 LEGEND IS MISLABELED. THE LEGEND MUST | | | CORRELATE WITH THE EQUIPMENT LAYOUT. PLEASE CORRECT ON | | | THE RESUBMITTAL. | | | | | | 2. SHEET AS-3 PLUMBING NOTE #9: PLEASE DELETE THE WORD | | | "BOCK" AND PLEASE ADD IN ITS PLACE THE WORD "BACK" ON | | | THE RESUBMITTAL. | | | | | | 3. FBC-2004 SEC. 424.2.12.1, OR | | | FBCR-2004 SEC. R4101.12.1 PRESSURE | | | TESTS. PER MANUFACTURE RECOMMENDATIONS, | | | NO AIR TEST SHALL BE APPROVED FOR PVC | | | PIPE AND FITTINGS. (PLEASE ADD TO PLUMBING NOTES ON | | | SHEET AS-3) | | | | | | 4. FBC-2004 SEC. 424.2.13.2, OR | | | FBCR-2004 SEC.R4101.13.2 JOINTS AND | | | CONNECTIONS, FBC PLMG SEC 605.21, PURPLE | | | PRIMER REQUIRED ON PVC PIPING.(PLEASE ADD TO PLUMBING | | | NOTES ON SHEET AS-3) | | | | | | ********IMPORTANT INFORMATION******** | | | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | | PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED, PLEASE INCLUDE A | | | TRANSMITTAL LETTER INDICATING HOW EACH | | | ITEM WAS ADDRESSED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. | | | NOTE: ONLY ONE CORRECTED DRAWING | | | IN RED INK FOR REFERENCE FOR | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2007-06-28 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-06-28 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-06-28 |
Time |
16:58 |
Sent To |
P |
|
| Notes |
| 2007-06-28 16:59:34 | RESTAMPED APPROVED PLANS |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2007-05-30 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-05-30 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2007-05-30 |
Time |
14:30 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-04-12 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-04-12 |
Time |
18:49 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2007-04-12 |
Time |
18:48 |
Sent To |
I |
|
| Notes |
| 2007-04-12 18:53:22 | ***FAILED*** | | | | | | 1) RECENT SURVEY SHALL BE PROVIDED SHOWING THE LOCATION | | | OF THE POOL AND THE SETBACKS FROM ALL PROPERTY LINES. | | | | | | 2) SETBACKS SHALL BE MEASURED FROM THE PROPERTY LINE TO | | | THE WATER'S EDGE. | | | | | | 3) POOL EQUIPMENT SHALL BE SHOWN ON THE SITE PLAN AND | | | SURVEY.SETBACKS FROM ALL PROPERTY LINES SHALL BE | | | PROVIDED. | | | | | | 4) EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE OR | | | SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS | | | BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE | | | RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED. | | | BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN | | | HEIGHT ABOVE GRADE. | | | | | | 5) ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH | | | A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING | | | GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES | | | PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE.(CHILD | | | SAFETY BARRIERS DO NOT SATISFY THIS REQUIREMENT).AT | | | LEAST 90 PERCENT OF THE SURFACE AREA OF ALL SCREEN | | | ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH WHICH | | | AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT SHALL | | | BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A | | | 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE, | | | AT THE PROPERTY LINE, TO ENSURE PRIVACY. | | | | | | AS THERE IS NO SURVEY AND THE SITE PLAN DOES NOT | | | INDICATE AN EXISTING FENCE THAT WOULD SATISFY THESE | | | CRITERIA, A FENCE PERMIT SHALL BE SUBMITTED | | | CONCURRENTLY WITH THE POOL PERMIT. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | | AT (561) 822-1435. |
|
|