Plan Review Details - Permit 07040327
Plan Review Stops For Permit 07040327
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-05 Cont ID  
Sent By mjacobs Date 2007-07-05 Time 12:05 Rev Time 0.00
Received By mjacobs Date 2007-07-05 Time 11:46 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-15 Cont ID  
Sent By mjacobs Date 2007-06-15 Time 15:46 Rev Time 0.00
Received By mjacobs Date 2007-06-15 Time 13:30 Sent To PC
Notes
2007-06-15 15:46:21BUILDING PLAN REVIEW
 PERMIT:07040327
 ADD:376 ORANGE WAY
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2)THE FENCE DETAIL ON SHEET A-2 SHALL MEET THE
 REQUIREMENTS OF SECTION R4101.17.1 THROUGH R4101.17.3.
 THE HEIGHTS OF THE FENCE INDICATED ON THE DRAWINGS DO
 MEET THE REQUIREMENTS OF THIS SECTION. SHOW HOW THE
 LATCH FOR THE GATE WILL MEET THE 54" REQUIREMENT. SHOW
 ON THE DRAWINGS HOW FAR AWAY FROM THE POOL THE FENCE
 WILL BE INSTALLED. SEE SEC.R4101.17.1.13.
  
 3) 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.
  
 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER108.3 FBC*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-02 Cont ID  
Sent By mjacobs Date 2007-05-02 Time 12:06 Rev Time 0.00
Received By mjacobs Date 2007-05-02 Time 07:42 Sent To PC
Notes
2007-05-02 12:06:46BUILDING PLAN REVIEW
 PERMIT: 07040327
 ADD: 376 ORANGE WAY
 CONT: SUREZ CARLOS
 TEL: (561)432-8683
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)THESPECIFICATIONS DIMENTIONS ARE DIFFERENT FROM
 THOSE INDICATED ON THE POOL DRAWINGS.THE POOL
 DIMENTIONS SHALL BE THE SAME. SEE SHEET A-2.
  
 2)A SEPERATE PERMIT IS REQUIRED FOR THE FENCE.
  
 3) INDICATE THE TOTAL SQUARE FOOTAGE FOR THE POOL DECK
 EVEN THOUGH IS WILL BE DONE BY OTHERS.
  
 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 5)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 NOTE: THE POOL SHALL BE DESIGN TO FBC.2004 SEC.424.2
 PRIVATE SWIMING POOL AND 2004 RESIDENTIAL CODECHAPTER
 41.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-04 Cont ID  
Sent By btrobaug Date 2007-06-04 Time 06:57 Rev Time 0.33
Received By btrobaug Date 2007-06-04 Time 06:50 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-04-19 Cont ID  
Sent By btrobaug Date 2007-04-19 Time 17:15 Rev Time 0.25
Received By btrobaug Date 2007-04-19 Time 16:59 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-06-27 Cont ID  
Sent By adarroug Date 2007-06-27 Time 16:14 Rev Time 0.00
Received By adarroug Date 2007-06-27 Time 16:14 Sent To Z
Notes
2007-06-27 16:15:06TO "Z" BOX/RESUB--NEW SHEETS FOR "Z, P, B"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 08:16 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 08:16 Sent To E
Notes
2007-06-01 08:17:14TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-24 Cont ID  
Sent By adarroug Date 2007-05-24 Time 11:41 Rev Time 0.00
Received By adarroug Date 2007-05-24 Time 11:41 Sent To Z
Notes
2007-05-24 11:42:09TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-13 Cont ID  
Sent By adarroug Date 2007-04-13 Time 15:55 Rev Time 0.00
Received By adarroug Date 2007-04-13 Time 15:55 Sent To E
Notes
2007-04-13 15:56:07TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-05-02 Time   Rev Time 0.00
Received By adarroug Date 2007-04-10 Time 16:16 Sent To  
Notes
2007-04-10 16:17:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-07-03 Cont ID  
Sent By mperson Date 2007-07-03 Time 13:09 Rev Time 0.33
Received By mperson Date 2007-07-03 Time 13:09 Sent To B
Notes
2007-07-03 13:15:08NOTE: THERE IS NO PLUMBING PERMIT BEING APPLIED FOR ON
 THE POOL PERMIT APPLICATION. A PLUMBING PERMIT IS
 REQUIRED FOR THE POOL, AND THERE IS NO POOL HEATER:
  
 ****************PROVISO****************
 1) COMPLY WITH FBC-2004 SEC 424.2, OR
 FBCR-2004 SEC R4101 PRIVATE SWIMMING
 POOLS.
 2) FBC-2004 SEC. 424.2.7.2, OR
 FBCR-2004 SEC. R4101.7.2 PUMPS AND
 EQUIPMENT SHALL BE MOUNTED ON A
 SUBSTANTIAL BASE IN A MANNER THAT WILL
 ELIMINATE STRAIN ON PIPING.SLAB SHALL
 BE A NOMINAL 4" THICK.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-06-15 Cont ID  
Sent By mperson Date 2007-06-15 Time 11:56 Rev Time 0.33
Received By mperson Date 2007-06-15 Time 11:56 Sent To B
Notes
2007-06-15 11:57:38NOTE: THERE IS NO PLUMBING PERMIT BEING APPLIED FOR ON
 THE POOL PERMIT APPLICATION. A PLUMBING PERMIT IS
 REQUIRED FOR THE POOL, AND THERE IS NO POOL HEATER:

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-24 Cont ID  
Sent By mperson Date 2007-04-24 Time 11:49 Rev Time 0.33
Received By mperson Date 2007-04-24 Time 11:49 Sent To B
Notes
2007-04-24 13:09:24DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 SECTIONS 424.2 AND R4101 SWIMMINGS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET AS-3 LEGEND IS MISLABELED. THE LEGEND MUST
 CORRELATE WITH THE EQUIPMENT LAYOUT. PLEASE CORRECT ON
 THE RESUBMITTAL.
  
 2. SHEET AS-3 PLUMBING NOTE #9: PLEASE DELETE THE WORD
 "BOCK" AND PLEASE ADD IN ITS PLACE THE WORD "BACK" ON
 THE RESUBMITTAL.
  
 3. FBC-2004 SEC. 424.2.12.1, OR
 FBCR-2004 SEC. R4101.12.1 PRESSURE
 TESTS. PER MANUFACTURE RECOMMENDATIONS,
 NO AIR TEST SHALL BE APPROVED FOR PVC
 PIPE AND FITTINGS. (PLEASE ADD TO PLUMBING NOTES ON
 SHEET AS-3)
  
 4. FBC-2004 SEC. 424.2.13.2, OR
 FBCR-2004 SEC.R4101.13.2 JOINTS AND
 CONNECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING.(PLEASE ADD TO PLUMBING
 NOTES ON SHEET AS-3)
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 3 Status P Date 2007-06-28 Cont ID  
Sent By choops Date 2007-06-28 Time 16:58 Rev Time 0.00
Received By choops Date 2007-06-28 Time 16:58 Sent To P
Notes
2007-06-28 16:59:34RESTAMPED APPROVED PLANS

Review Stop Z ZONING
Rev No 2 Status P Date 2007-05-30 Cont ID  
Sent By jroach Date 2007-05-30 Time 14:30 Rev Time 0.00
Received By jroach Date 2007-05-30 Time 14:30 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-12 Cont ID  
Sent By jroach Date 2007-04-12 Time 18:49 Rev Time 0.00
Received By jroach Date 2007-04-12 Time 18:48 Sent To I
Notes
2007-04-12 18:53:22***FAILED***
  
 1) RECENT SURVEY SHALL BE PROVIDED SHOWING THE LOCATION
 OF THE POOL AND THE SETBACKS FROM ALL PROPERTY LINES.
  
 2) SETBACKS SHALL BE MEASURED FROM THE PROPERTY LINE TO
 THE WATER'S EDGE.
  
 3) POOL EQUIPMENT SHALL BE SHOWN ON THE SITE PLAN AND
 SURVEY.SETBACKS FROM ALL PROPERTY LINES SHALL BE
 PROVIDED.
  
 4) EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE OR
 SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS
 BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE
 RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
  
 5) ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH
 A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING
 GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES
 PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE.(CHILD
 SAFETY BARRIERS DO NOT SATISFY THIS REQUIREMENT).AT
 LEAST 90 PERCENT OF THE SURFACE AREA OF ALL SCREEN
 ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH WHICH
 AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT SHALL
 BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 AS THERE IS NO SURVEY AND THE SITE PLAN DOES NOT
 INDICATE AN EXISTING FENCE THAT WOULD SATISFY THESE
 CRITERIA, A FENCE PERMIT SHALL BE SUBMITTED
 CONCURRENTLY WITH THE POOL PERMIT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.