Plan Review Details - Permit 07040301
Plan Review Stops For Permit 07040301
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-20 Cont ID  
Sent By jjohnsto Date 2007-09-20 Time 14:05 Rev Time 2.22
Received By jjohnsto Date 2007-09-20 Time 14:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-20 Cont ID  
Sent By jwitmer Date 2007-07-31 Time 15:00 Rev Time 2.20
Received By jjohnsto Date 2007-09-18 Time 13:20 Sent To PC
Notes
2007-07-31 16:05:35PERMIT: 07040301
 ADD: 2497 OKEECHOBEE BLVD
 CONT: "PLAN REVIEW"
 TEL: (650)952-4400
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) 2ND REQUEST, THE OLD ARCHITECTURAL SHEETS STILL ARE
 MISSING THEIR CERTIFICATE OF AUTHORIZATION.PHILLIPS
 PARTNERSHIP, IS MISSING THEIR CERTIFICATE OF
 AUTHORIZATION,481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ARCHITECT PRACTICING UNDER A FICTITIOUS
 NAME, ACORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER.ADD THE NUMBER TO EACH
 SHEET.
  
 4- 12 )COMPLIED.
  
 13) 2ND REQUEST,SHEET A-0 THIS IS AN INTERIOR
 RENOVATIION OF AN EXISTING SPACE, PLEASE SEE 2004/ 2006
 UPDATES TO THE FLORIDA EXISTING BUILDING CODE., TO
 WHICH LEVEL WILL THIS ALTERATION BE?
 SEE 2004 EXISTING BUILDING CODECHAPTER 3, FOR LEVELS
 OF ALTERATION.
  
 14) ENERGY CALCS, ONLY 1 SET OF ENERGY CALCS WERE
 SUBMITTED. THE DESIGN PROFESSIONAL FOR ELECTRIC AND
 LIGHTING HADN'T SEALED HIS WORK. MECHANICAL NO
 SIGNATURE NOR SEAL. PLANS, SPECIFICATIONS, REPORTS
 OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE
 AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-13 Cont ID  
Sent By jwitmer Date 2007-06-13 Time 07:28 Rev Time 2.77
Received By jwitmer Date 2007-06-13 Time 07:28 Sent To PC
Notes
2007-06-13 08:07:18BUILDING PLAN REVIEW
 PERMIT: 07040301
 ADD: 2497 OKEECHOBEE BLVD
 CONT: "PLAN REVIEW"
 TEL: (650)952-4400
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)PHILLIPS PARTNERSHIP, IS MISSING THEIR CERTIFICATE
 OF AUTHORIZATION,481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, ACORPORATION, OR
 A PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER.ADD
 THE NUMBER TO EACH SHEET.
  
 4)THE MECHANICAL AND PLUMBING SHEETS HAVE THE DESIGN
 PROFESSIONAL USING AN INVALID SEAL.RULE
 61G15-23.001(1) F.A.C.THE FLORIDA BOARD OF
 PROFESSIONAL
 ENGINEERS HAS CLEANED UP THE APPEARANCE OF THE SEAL BY
 ELIMINATING OBSOLETE CONTENT AND CHANGING THE WORD
 "CERTIFICATE" TO "LICENSE". A GRACE PERIOD RAN THROUGH
 DEC. 31,2005.PURSUANT TO SECTION 471.025 F. S. , THE
 BOARD HEREBY ESTABLISHES AS INDICATED BELOW THE FORMS
 OF EMBOSSING IMPRESSION SEALS WHICH ARE ACCEPTABLE TO
 THE BOARD.
 SAID SEAL SHALL BE A MINIMUM OF 1 7/8" IN DIAMETER. ALL
 ENGINEERS MUST BE UTILIZING SEALS AS ILLUSTRATED IN
 THIS RUKE NO LATER THAN JANUARY 1, 2006.
  
 5) BEWARE OF EXTERIOR WORK TO BE COMPLETED DURING
 HURRICANE SEASON. 109.3.10.1 HURICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION MATERIALS EQUIPMENT
 AND DEBRIS WITHIN 24 HRS AFTER A HURRICANE WATCH HAS
 BEENISSUED SHALL BE SUBJECT TO A FINE NOT TO EXCEED
 $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 6) IT APPEARS THE FRONT DOORS ARE TO BE REPLACED AND
 EFIS WORK WILL ALSO BE REPLACED.FL BLD CODE
 1609.1.4: COMPONENTS & CLADDING, PROVIDE 2 COPIES(3 IF
 THRESHOLD OR RESIDENT INSPECTOR) OF PRODUCT TESTING
 REPORTS ,MISSING REPORTS ARE AS FOLLOWS:
 A) EXTERIOR GLAZED DOORS
 B) EFIS SYSTEMS
  
 7)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8)) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9) FOR WORK ON THE EXTERIOR OF THE BUILDING WIND
 INFORMATION WILL BE NEEDED FOR THE DESIGN:
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 10) SHEET A-0, CODE INFORMATION BUILDING TYPE "2C"
 PLEASE SEE 2004 FBC TABLE 503 AND SECTION 602 FOR
 BUILDING CLASSIFICATION.
  
 11) SHEET A-0, CODE INFORMATION OCCUPANCY LEFT BLANK?
 SEE 302.1
  
 12) SHEET A-0 INDICATES CODE INFORMATION AS DESIGNED TO
 THE 2004 FBC, PLEASE UPDATE INCLUDING THE2006
 AMENDMENTS.
  
 13) SHEET A-0 THIS IS AN INTERIOR RENOVATIION OF AN
 EXISTING SPACE, PLEASE SEE 2004/ 2006 UPDATES TO THE
 FLORIDA EXISTING BUILDING CODE., TO WHICH LEVEL WILL
 THIS ALTERATION BE?
  
 14) SHEET A-0 INDICATES ENERGY CALCS WERE ATTACHED,
 WHERE?
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-09-27 Cont ID  
Sent By dpalmer Date 2007-09-27 Time 19:54 Rev Time 0.00
Received By dpalmer Date 2007-09-27 Time 18:32 Sent To FIRE
Notes
2007-09-27 19:55:472007-09-27 19:55:47
  
 PLANS OK, STAMPED. ROUTED TO FIRE AS FIRE REVIEW STILL
 NEEDS TO STAMP PLANS AS NOTED ON PREVIOUS REVIEW. PLANS
 WILL BE ROUTED BACK TO ELECTRICLA FOR PROCESSING ONCE
 FIRE HAS STAMPED PLANS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-09-04 Cont ID  
Sent By dpalmer Date 2007-09-04 Time 20:26 Rev Time 0.00
Received By dpalmer Date 2007-09-04 Time 20:26 Sent To  
Notes
2007-09-04 20:26:542007-09-04 20:26:54
  
 ** DENIED 3RD REVIEW **
  
 ** THIS IS THE SECOND REVIEW UNDER PERMIT.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED ADDRESSING.
  
  
 1) NOTE: PLEASE SEE ALL ARCHITECTURAL SHEETS IN BOTH
 SETS ARE NOT SEALED AS REQUIRED PER FS 481.221. THIS IS
 REQUIRED FOR ALL SHEETS IN BOTH SETS.
  
 2) NOTE:PLEASE SEE THE ENERGY CALCULATIONS THAT WERE
 SUBMITTED ARE NOT SEALED ON THE SHEET WHICH
 SPECIFICALLY CALLS FOR THE CERTIFICATIONS TO BE MADE. (
 IT WAS NOTICED THAT ONE OF THE SHEETS IN THE REAR OF
 THE SHEETS WAS SIGNED, AND SEALED)
 PLEASE SEE 13-103.1.1.1 AS THIS IS REQUIRED ON EACH OF
 THE TWO SETS BEING REQUESTED TO BE SUBMITTED FOR
 REVIEW. PLEASE SEE FAC 61G15-23.002 AND FS 471.025
  
 3) NOTE:AS STATED ON THE PREVIOUS REVIEWS, PLEASE
 INCLUDE LOCATIONS OF ALL OVER RIDE DEVICES BEING
 INSTALLED AND AS REQUIRED PER 13-415.1.ABC.1.1 AND
 .1.2.
 PLEASE SEE THE SAME SECTIONS OF CODE AS THE OVER RIDES
 SHALL BE LOCATED SO THAT THE OCCUPANT CAN VISUALLY SEE
 THE LIGHTING WHICH IS BEING CONTROLLED. THERE IS ONE
 EXCEPTION WHICH THE USE OF PILOT LIGHTS MAY BE USED,
 HOWEVER NEITHER THE LOCATION OF THE DEVICES FOR OVER
 RIDE FOR CONTROL OF LIGHTING IS SHOWN ON PLANS AS
 REQUIRED PER CODE OR PILOT LIGHTS ARE DETAILED ON
 PLANS.
 PLEASE ALSO SEE THAT THE TYPE OF OVER RIDE DEVICE(S)
 SHALL STATE THEIR MAXIMUM TIMES BASED ON THE TYPE OF
 DEVICE CHOSEN.
 THE PREVIOUS REVIEW NOTE WITH RESPECT TO MORE
 INFORMATION NEEDED FOR LIGHTING CONTROLS, OVER RIDES
 AND SEPARATE SPACES WAS RESPONDED BY THE MENTION OF A
 BATTERY BACK UP FIXTURE IN THE BATHROOMS??
 PLEASE PROVIDE INFORMATION ON THE OVER RIDES,
 LOCATIONS, TIMES ON OVER RIDES, SEPARATE SPACE DEVICES
 ETC. THE ONLY TIME WHICH COULD BE LOCATED FOR NOTE #101
 WAS MOTION WITH 15MINS.
 PLEASE SEE THE MOTION SENSOR DEVICE WHICH IS BEING
 ASSUMED AS MS ON PLANS WILL NOT BE ACCEPTED BY THIS
 OFFICE IN MULTI-USE RESTROOMS WITH PARTITION TYPE
 WALLS. THESE WOULD NEED TO BE COMBO TYPE DEVICES SUCH
 AS ULTRASONIC ETC.
 PLEASE SEE NOTE #4 FROM BOTH PREVIOUS REVIEWS. THIS
 OFFICE CAN NOT EXPLAIN IN TYPE WRITTEN NOTES ANY
 FURTHER. PLEASE CALL TO GO OVER AND FOR QUESTIONS
 REGARDING THIS.
  
 4) NOTE:PLEASE SEE AS STATED ON PREVIOUS REVIEW(S).
 PLEASE COORDINATE ALL FIXTURES ON PLANS, FIXTURE LEGEND
 AND THE ENERGY CALCULATIONS BEING SUBMITTED. PLEASE SEE
 THESE STILL DO NOT CORRELATE.
 PLEASE SEE THE LIGHTING FIXTURE LEGEND: FOR EXAMPLE:
 PLEASE SEE THE WATTAGE OF EACH TYPE OF FIXTURE DOES NOT
 APPEAR ON THE ENERGY CALCULATIONS AS SHOWN. (60WATT
 FIXTURES ETC)
 PLEASE SEE THE TOTAL NUMBER OF FIXTURES FOR EXAMPLE OF
 THE 124WATT FIXTURES SHOWN AS A TOTAL OF185 ON
 FIXTURE LEGEND INDICATES A TOTAL OF 215 ON
 CALCULATIONS. THIS IS THE SAME FOR 62 WATT FIXTURES.
 PLEASE NOT ONLY COORDINATE THE FIXTURE LEGEND WITH THE
 CALCULATIONS BUT ALSO COORDINATE WITH THE FIXTURES ON
 PLANS.
 PLEASE SEE 13-415.2, 13-415.1.B (AS METHOD B IS BEING
 SUBMITTED)
  
 5) NOTE: PLEASE KNOW FEES ARE OWED BEFORE ISSUANCE OF
 PERMIT BASED ON THE INCREASED VALUE AS STATED ON LETTER
 FROM PHILLIPS PARTNERSHIP.
 PLEASE KNOW THAT WHEN PLANS ARE SUBMITTED FOR THE
 FOLLOWING REVIEW, THE RE-SUB FEE OF 10% WILL BE DUE AT
 TIME OF RE-SUBMISSION OF PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** AS STATED ON PREVIOUS REVIEW:
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-02 Cont ID  
Sent By dpalmer Date 2007-07-02 Time 15:22 Rev Time 0.00
Received By dpalmer Date 2007-07-02 Time 14:21 Sent To I
Notes
2007-07-02 15:22:142007-07-02 15:22:14
  
 *** UNSAT ***
  
  
 *** PLEASE NOTE: AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW AS THESE ITEMS CAN NOT BE
 REVIEWED AT THIS TIME.
  
  
 ** PLEASE SEE THERE ARE STILL COMMENTS FROM PREVIOUS
 REVIEW WHICH ARE IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE RESPONSE LETTER FROM THE DESIGNER
 IS QUOTING THE ELECTRICAL REVIEW COMMENTS HOWEVER THE
 COMMENTS AS BEING QUOTED ARE NOT THAT IN ITS ENTIRETY
 OF THIS REVIEWERS COMMENT. PLEASE SEE COMMENT #7 FOR
 EXAMPLE. PLEASE BE SURE IF QUOTING COMMENTS FROM TRADES
 THEY ARE AS ACCURATE AS POSSIBLE. THIS HELPS THE REVIEW
 PROCESS. PLEASE SEE NOTE # 7 FROM PREVIOUS REVIEW AS
 THE RESPONSE ONLY SEEMS TO MENTION ONE PART OF THE
 PREVIOUS NOTES.
 FBC 106.3
  
 2) NOTE:PLEASE SEE THERE ARE SEVERAL SHEETS IN THE
 ARCHITECTURAL PLANS WHICH ARE SHEETS NOT CORRECT OR
 CHANGED FROM PREVIOUS REVIEW. PLEASE SEE THESE SHEETS
 WHICH WERE NOT CHANGED DO NOT CONTAIN THE REQUIRED
 INFORMATION.
 PLEASE ALSO SEE THE MEP PLANS WHICH DO NOT CONTAIN THE
 INFORMATION AS NEEDED EVEN THOUGHT THE TITLE BLOCKS ARE
 LISTED?
 ** THIS IS REQUIRED.
 PLEASE SEE THE SHEETS FROM THE ARCHITECT WERE NOT DATED
 AS REQUIRED UNDER FS 481.221 NEW AND OLD SHEETS.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE MISSING INFORMATION REQUIRED ON TITLE BLOCKS
 FOR ARCHITECTURAL FIRM AS REQUIRED UNDER FAC
 61G1-16.004 AND FS 481.219.
 PLEASE SEE THE MISSING PRINTED NAME, PRINTED LICENSE
 NUMBER OF THE DESIGNER OF RECORD ALONG WITH THE MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER.
 **THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY ANY OTHER TRADES.
  
 3) NOTE:PLEASE SEE ONLY ONE SET OF ENERGY
 CALCULATIONS WERE SUBMITTED. PLEASE SEE THIS SET WAS
 NOT SEALED AS REQUIRED ONLY SIGNED AND DATED BY THE
 DESIGNER OF RECORD. PLEASE ALSO SEE THE OWNER AGENT IS
 STILL NOT SIGNED.
 PLEASE SEE 13-103.1.1.1 AS THIS IS REQUIRED ON EACH OF
 THE TWO SETS BEING REQUESTED TO BE SUBMITTED FOR
 REVIEW.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT SEPARATE ENERGY CALCULATIONS AS THE
 SEPARATE SHEETS. THE INFORMATION MAY STILL BE ON PLANS;
 HOWEVER THE SEPARATE SHEETS ARE NEEDED.
 PLEASE BE SURE TO SIGN, DATE AND SEAL.
 FBC 13-103.1.1.1
  
 4) NOTE: THE PREVIOUS REVIEW NOTE WITH RESPECT TO MORE
 INFORMATION NEEDED FOR LIGHTING CONTROLS, OVER RIDES
 AND SEPARATE SPACES WAS RESPONDED BY THE MENTION OF A
 BATTERY BACK UP FIXTURE IN THE BATHROOMS??
 PLEASE PROVIDE INFORMATION ON THE OVER RIDES,
 LOCATIONS, TIMES ON OVER RIDES, SEPARATE SPACE DEVICES
 ETC. THE ONLY TIME WHICH COULD BE LOCATED FOR NOTE #101
 WAS MOTION WITH 15MINS.
 PLEASE SEE THE MOTION SENSOR DEVICE WHICH IS BEING
 ASSUMED AS MS ON PLANS WILL NOT BE ACCEPTED BY THIS
 OFFICE IN MULTI-USE RESTROOMS WITH PARTITION TYPE
 WALLS. THESE WOULD NEED TO BE COMBO TYPE DEVICES SUCH
 AS ULTRASONIC ETC.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE CLARIFY NEW CONTROL METHODS FOR NEW LIGHTING
 BEING INSTALLED.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE SOME NOTES TO OCCUPANCY SENSOR TYPE DEVICES
 ARE NOTED, HOWEVER TIMES OF MAXIMUM PERMITTED TIMES ARE
 NOT SHOWN.
 PLEASE ALSO SEE THAT THE MS TYPE DEVICE NOTED FOR
 BATHROOMS WILL NOT PROVIDE NEEDED COVERAGE FOR THE LIFE
 SAFETY ASPECT OF LIGHTING CONTROL. PLEASE ADJUST THE
 TYPE OF DEVICE.
 LS 101 7.8,7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE
 LIGHTING SWITCHES SHALL BE PERMITTED WITHIN THE MEANS
 OF EGRESS, PROVIDED THAT THE SWITCH CONTROLLERS ARE
 EQUIPPED FOR FAIL-SAFE OPERATION, THE ILLUMINATION
 TIMERS ARE SET FOR A MINIMUM 15-MINUTE DURATION, AND
 THE MOTION SENSOR IS ACTIVATED BY ANY OCCUPANT MOVEMENT
 IN THE AREA SERVED BY THE LIGHTING UNITS.
 PLEASE ALSO SEE CHAPTER 10 OF THE FBC. 1006.
  
 5) NOTE: PLEASE SEE THE VALUE AS APPLIED SEEMS LOW.
 PLEASE KNOW THE VALUE SHALL INCLUDE ALL LIGHTING
 FIXTURES EQUIPMENT ETC EVEN IF ANY OF THESE ITEMS ARE
 OWNER SUPPLIED.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE KNOW WHEN APPLYING FOR PERMIT, THE VALUE FOR
 THE COMPLETE SCOPE OF WORK SHALL INCLUDE ALL LABOR AND
 MATERIALS EVEN IF EQUIPMENT, FIXTURES ETC ARE OWNER
 SUPPLIED.
 PLEASE KNOW THAT A VALUE MAY BE USED USING THE ADOPTED
 GUIDES UNDER THE FBC 108.3
  
 6) NOTE:PLEASE SEE THE NUMBER OF FIXTURES ARE NOW
 SHOWN ON FIXTURE LEGEND AS REQUESTED HOWEVER PLEASE SEE
 THERE ARE SOME MINOR DIFFERENCES IN THE ENERGY
 CALCULATIONS AND THE FIXTURE LEGEND FIXTURES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE NUMBER OF FIXTURES IN THE FIXTURE
 LEGEND FOR EACH AND COORDINATE WITH THE ENERGY
 CALCULATIONS WHICH ARE TO BE REVISED.
 FBC CHAPTER 13, 13-415.2, 13-415.1.AB.1.1 ETC PLEASE
 SEE TABLES FOR METHOD B AND INDICATE ACCORDINGLY. **
 PLEASE VERIFY THE WATTAGE ETC SHOWN FOR THE *JELLY JAR*
 FIXTURE.
  
 ** PLEASE KNOW THERE MAY BE NEW COMMENTS ONCE
 ADDITIONAL INFORMATION IS SUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-02 14:22:022007-07-02 14:22:02
 PLANS REMOVED FROM INCOMING AND WILL BE RETURNED TO
 INCOMING WAITING FOR COMM BOARD ONCE ELECTRICLA REVIEW
 IS DONE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-21 Cont ID  
Sent By dpalmer Date 2007-04-21 Time 15:33 Rev Time 0.00
Received By dpalmer Date 2007-04-21 Time 14:41 Sent To I
Notes
2007-04-21 15:33:27** UNSAT **
  
 ** PLEASE SEE ANY REFERENCES TO CHAPTER 1 OF THE FBC
 ARE THE ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY
 OF WEST PALM BEACH.
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. THIS
 WOULD INCLUDE REQUIRED CODES ON TRADE SHEETS. PLEASE
 KNOW THERE ARE CHANGES IN THE FBC WHICH MAY AFFECT
 DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON
 TITLE BLOCKS FOR ARCHITECTURAL FIRM AS REQUIRED UNDER
 FAC 61G1-16.004 AND FS 481.219.
 PLEASE SEE THE MISSING PRINTED NAME, PRINTED LICENSE
 NUMBER OF THE DESIGNER OF RECORD ALONG WITH THE MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER.
 **THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY ANY OTHER TRADES.
  
 3) NOTE: PLEASE ALSO SEE THE MISSING INFORMATION
 REQUIRED FOR THE ENGINEERING FIRM AS REQUIRED UNDER FAC
 61G15-23.002 AND FS 471.023.
 PLEASE SEE THE MISSING PRINTED NAME AND MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER.
 THIS IS REQUIRED ON ALL SHEETS WHICH CONTAIN THE TITLE
 BLOCK FOR ENGINEERING FIRM AND DESIGNERS OF RECORD.
  
 4) NOTE: PLEASE SEE THE M AND P SHEETS WHICH ARE SEALED
 WITH A SEAL WHICH IS NO LONGER VALID IN THE STATE OF
 FLORIDA. PLEASE SEE FAC 61G15-23.001 WHICH IN FEB 04
 CHANGED TO REQUIRE THE WORDING OF *LICENSE* IN SAID
 SEAL INSTEAD OF THE WORDING OF *CERTIFICATE*.
 AN EXTENSION WAS ISSUED BY THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS TO THE DATE OF DECEMBER 31ST,
 2005 HOWEVER ALL PLANS AFTER THAT DATE MUST CONTAIN THE
 NEW SEAL. *PLEASE OBTAIN*.
  
 5) NOTE: PLEASE SEE THE SEAL AS NOTED IN NOTE #4 ABOVE
 SHALL BE OF MINIMUM SIZE AS REQUIRED UNDER FAC
 61G15-23.001. (2INCHES)
 THE SEAL AT THIS TIME IS NOT OF THE REQUIRED MINIMUM
 SIZE. THIS IS NOT A NEW RULING.
 REQUIRED WHETHER OR NOT THIS IS NOTED BY OTHER TRADES.
  
 6) NOTE: PLEASE SEE THE VERSION OF THE FLORIDA ENERGY
 CODE IS NOT CORRECT. PLEASE SEE THE NEW ADOPTED FBC
 2004 W/ 2006 REVISIONS IN CHAPTER 13.
  
 PLEASE SUBMIT SEPARATE ENERGY CALCULATIONS AS THE
 SEPARATE SHEETS. THE INFORMATION MAY STILL BE ON PLANS,
 HOWEVER THE SEPARATE SHEETS ARE NEEDED.
 PLEASE BE SURE TO SIGN, DATE AND SEAL.
 FBC 13-103.1.1.1
  
 7) NOTE: PLEASE CLARIFY NEW CONTROL METHODS FOR NEW
 LIGHTING BEING INSTALLED.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE SOME NOTES TO OCCUPANCY SENSOR TYPE DEVICES
 ARE NOTED, HOWEVER TIMES OF MAXIMUM PERMITTED TIMES ARE
 NOT SHOWN.
 PLEASE ALSO SEE THAT THE MS TYPE DEVICE NOTED FOR
 BATHROOMS WILL NOT PROVIDE NEEDED COVERAGE FOR THE LIFE
 SAFETY ASPECT OF LIGHTING CONTROL. PLEASE ADJUST THE
 TYPE OF DEVICE.
 LS 101 7.8,7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE
 LIGHTING SWITCHES SHALL BE PERMITTED WITHIN THE MEANS
 OF EGRESS, PROVIDED THAT THE SWITCH CONTROLLERS ARE
 EQUIPPED FOR FAIL-SAFE OPERATION, THE ILLUMINATION
 TIMERS ARE SET FOR A MINIMUM 15-MINUTE DURATION, AND
 THE MOTION SENSOR IS ACTIVATED BY ANY OCCUPANT MOVEMENT
 IN THE AREA SERVED BY THE LIGHTING UNITS.
 PLEASE ALSO SEE CHAPTER 10 OF THE FBC. 1006.
  
 8) NOTE: PLEASE KNOW WHEN APPLYING FOR PERMIT, THE
 VALUE FOR THE COMPLETE SCOPE OF WORK SHALL INCLUDE ALL
 LABOR AND MATERIALS EVEN IF EQUIPMENT, FIXTURES ETC ARE
 OWNER SUPPLIED.
 PLEASE KNOW THAT A VALUE MAY BE USED USING THE ADOPTED
 GUIDES UNDER THE FBC 108.3
  
 9) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3(4) FOR ANY
 FA DEVICES FOR ADA COMPLIANCE WHICH MAY BE REQUIRED TO
 BE CHANGED OR INSTALLED.
 PLEASE SEE REVIEWS FROM OTHER TRADES,( FIRE MARSHAL) IF
 ANY WORK TO THESE EXISTING SYSTEMS ARE TAKING PLACE,
 THIS BASE INFORMATION SHALL BE INCLUDE ON THESE BASE
 PLANS EVEN WHEN THESE SYSTEMS ARE UNDER SEPARATE
 PERMIT.
 FBC 106.3.5.1.2
  
 10) NOTE: PLEASE INDICATE THE NUMBER OF FIXTURES IN THE
 FIXTURE LEGEND FOR EACH AND COORDINATE WITH THE ENERGY
 CALCULATIONS WHICH ARE TO BE REVISED.
 FBC CHAPTER 13, 13-415.2, 13-415.1.AB.1.1 ETC PLEASE
 SEE TABLES FOR METHOD B AND INDICATE ACCORDINGLY.
 ** PLEASE VERIFY THE WATTAGE ETC SHOWN FOR THE *JELLY
 JAR* FIXTURE.
  
 11) NOTE: PLEASE KNOW THAT ALL LV WORK FOR SOUND
 SYSTEMS, ETC WILL BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT, HOVER MAY BE SHOWN ON THESE PLANS.
 ONCE PLANS ARE STAMPED THE LV CONTRACTOR/ELECTRICAL
 CONTRACTOR WOULD ONLY NEED TO FILL OUT PERMIT
 APPLICATION, APPROPRIATE VALUE AND REFERENCE MAIN
 PLANS. PERMIT WILL BE ISSUED THE SAME TIME AS A
 *TURN-AROUND*.
 ANY QUESTIONS ON THIS PLEASE CALL.
  
 12) NOTE: PLEASE KNOW THAT PLANS HAVE ONLY BEEN
 SUBMITTED FOR *PLAN REVIEW ONLY* AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT.
 ONCE PLANS ARE CODE COMPLIANT AND ALL INFORMATION IS
 SUBMITTED, PLANS CAN NOT BE STAMPED UNTIL PERMIT IS
 APPLIED FOR SO THAT VERIFICATION OF LICENSURE, PERMIT
 VALUE ETC CAN BE VERIFIED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-10-01 Cont ID  
Sent By mawillia Date 2007-10-01 Time 10:28 Rev Time 0.00
Received By mawillia Date 2007-10-01 Time 10:07 Sent To  
Notes
2007-10-01 10:07:36*****APPROVED*****
  
  
 PLAN SHEETS A2-0,A4-0, ANDE2.1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 18:15 Rev Time 0.00
Received By mawillia Date 2007-07-26 Time 18:01 Sent To  
Notes
2007-07-26 18:14:09*****PROVISO*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEET(S)
 WILL BE STAMPED WHEN ALL REVIEWS HAVE BEEN SATISFIED.
  
  
  
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-01 Cont ID  
Sent By mawillia Date 2007-06-01 Time 15:30 Rev Time 0.00
Received By mawillia Date 2007-06-01 Time 14:33 Sent To  
Notes
2007-06-01 15:30:22*****DENIED*****
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE REMOVAL AND (OR) THE REPLACEMENT OF BUILDING
 MATERIALS & SUPPLIES SHALL NOT HINDER OR INTERFERE WITH
 EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF (INCLUDING FIRE LANES).
  
 4.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE EXTERIOR
 ELEVATION WHICH FRONTS OKEECHOBEE BOULEVARD.AS PER
 WEST PALM BEACH CODE, THOSE NUMBERS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND NO LESS THAN 1" IN WIDTH.
  
 5.SHOW THE LOCATION OF THE 2A10:BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFIES THE 75' TRAVEL
 DISTANCE.
  
 6.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN THE EXITS, EXIT ACCESS CORRIDORS, AND
 OTHER SPACES AS CLASS A, CLASS B. OR CLASS C.
  
 7.WILL THE SCOPE OF WORK HAVE CAUSE FOR THE FIRE
 SPRINKLERS TO BE ALTERED OR MODIFIED?IF SO, SEPARATE
 PLANS SND PERMIT WILL BE REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-27 Cont ID  
Sent By adarroug Date 2007-09-27 Time 11:11 Rev Time 0.00
Received By adarroug Date 2007-09-27 Time 11:11 Sent To E
Notes
2007-09-27 11:11:55TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-08 Cont ID  
Sent By jjohnsto Date 2007-09-20 Time 13:57 Rev Time 0.00
Received By dpalmer Date 2007-08-08 Time 18:41 Sent To  
Notes
2007-09-04 14:43:48TO "COMM" BD#62
2007-08-08 18:42:21WAITING FOR COMM BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-21 Cont ID  
Sent By adarroug Date 2007-06-21 Time 10:55 Rev Time 0.00
Received By adarroug Date 2007-06-21 Time 10:55 Sent To  
Notes
2007-07-09 14:07:26TO "COMM" BD#16
2007-06-21 10:55:39WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-13 Cont ID  
Sent By jwitmer Date 2007-06-13 Time 07:28 Rev Time 0.00
Received By jwitmer Date 2007-04-10 Time 15:13 Sent To  
Notes
2007-04-12 13:49:10TO "COMM" BD#7
2007-04-10 15:13:57WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2007-09-09 Cont ID  
Sent By rregueir Date 2007-09-09 Time 14:18 Rev Time 0.00
Received By rregueir Date 2007-09-09 Time 14:13 Sent To  
Notes
2007-09-09 14:17:37NO MECHANICAL (A/C) SYSTEMS ARE BEING ALTERED, MODIFIED
 OR ADDED IN THIS SCOPE OF WORK. NO ATREATIONS,
 MODIFICATIONS OR ADDITIONS ARE NECESSARY FOR CODE
 COMPLIANCE.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-05-01 Cont ID  
Sent By rregueir Date 2007-05-01 Time 07:55 Rev Time 0.00
Received By rregueir Date 2007-05-01 Time 07:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-09-21 Cont ID  
Sent By kstevens Date 2007-09-21 Time 14:02 Rev Time 0.00
Received By kstevens Date 2007-09-21 Time 14:02 Sent To  
Notes
2007-09-21 14:04:19INSTALLINGAUTOMATIC FLUSH VALVES--PLUMBING PERMIT
 REQUIRED

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-07-19 Cont ID  
Sent By kstevens Date 2007-07-19 Time 17:26 Rev Time 0.00
Received By kstevens Date 2007-07-19 Time 17:26 Sent To  
Notes
2007-07-19 17:53:05DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW
  
 1. ALL SHEETS WITH THE ARCHITECTURAL TITLE BLOCK
 REQUIRE THE BUSINESS LICENSE NUMBER, THE PHONE NUMBER,
 THE SIGNATURE & THE PRINTED NAME OF THE ARCHITECT AT A
 MINIMUM PER FAC 61G1-16.004(1)(2)(5)(6) & FS 481.219,
 481.2055. THE SIGNATURE APPEARS TO BE INITIALS, BUT IF
 THIS IS THE LEGAL SIGNATURE OF THE ARCHITECT, PLEASE
 SUBMIT A SIGNED, SEALED, NOTORIZED LETTER INDICATING
 THE LEGAL SIGNATURE FOR OUR FILES.
 ****RESPONSE NOTED, BUT THE INFORMATION REQUIRED IN THE
 TITLE BLOCK OF EACH SHEET HAS NOT BEEN ADDED TO ALL
 SHEETS. SEE SHTS A1-2, A1-4, A3-0, A5-0, A6-2, A6-3,
 A6-4, A7-0, A7-4, EC-1, EC-2, SP-1 THRU SP-4 AS WELL AS
 ALL MECHANICAL AND ELECTRICAL SHEETS WITH ARCHITECTURAL
 TITLE BLOCK.
  
 2. OK
 3. OK
 4.OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL
 VOID SHEETS FROM ALL PLANS AND PLACE ONE SET
 OF THEM LOOSELY ON TOP OF THE COLLATED PLANS
 TO BE REVIEWED. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-30 Cont ID  
Sent By kstevens Date 2007-05-30 Time 09:48 Rev Time 0.00
Received By kstevens Date 2007-05-29 Time 12:53 Sent To  
Notes
2007-05-30 10:03:02DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH THE ARCHITECTURAL TITLE BLOCK
 REQUIRE THE BUSINESS LICENSE NUMBER, THE PHONE NUMBER,
 THE SIGNATURE & THE PRINTED NAME OF THE ARCHITECT AT A
 MINIMUM PER FAC 61G1-16.004(1)(2)(5)(6) & FS 481.219,
 481.2055. THE SIGNATURE APPEARS TO BE INITIALS, BUT IF
 THIS IS THE LEGAL SIGNATURE OF THE ARCHITECT, PLEASE
 SUBMIT A SIGNED, SEALED, NOTORIZED LETTER INDICATING
 THE LEGAL SIGNATURE FOR OUR FILES.
  
 2. SHT A0-1 ROOM FINISH SCHEDULE. THE TOILET ROOMS WALL
 FINISH, PER SECTION 1210.2 REQUIRE ALL WALLS WITHIN 2
 FEET OF URINALS & WATER CLOSETS SHALL HAVE A "SMOOTH,
 HARD, NONABSORBENT SURFACE". PAINTED WALLS DO NOT
 COMPLY WITH THE "HARD" PORTION OF THE REQUIREMENT.
 PLEASE INDICATE COMPLIANCE.
  
 3. SHTS A1-1, A1-3 & A2-0. SHT A1-1 SHOWS A SINK IN THE
 STOCK ROOM THAT IS NOT INDICATED ON SHTS A1-3 & A2-0.
 IS THIS SINK EXISTING AND WILL BE DEMO'D? PLEASE
 CLARIFY. IF THE SINK WILL BE DEMO'D, DEAD ENDS ARE
 PROHIBITED PER SECTION 704.5. SECTION 106.1.1.
  
 4. ALL MECHANICAL & ELECTRIC SHEETS. THE SEAL FOR THE
 ENGINEER IS NOT APPROVED. (SEE ATTACHED SHEET).-- THE
 CERTIFICATE OF AUTHORIZATION NUMBER IS REQUIRED IN THE
 TITLE BLOCK OF THE ENGINEERING COMPANY. FAC
 61G15-23.002(2) & FS 471.025.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL
 VOID SHEETS FROM ALL PLANS AND PLACE ONE SET
 OF THEM LOOSELY ON TOP OF THE COLLATED PLANS
 TO BE REVIEWED. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2007-09-18 Cont ID  
Sent By lfranco Date 2007-09-18 Time 18:01 Rev Time 0.00
Received By lfranco Date 2007-04-23 Time 17:55 Sent To I
Notes
2007-04-23 17:58:39PLANNING AND ZONING:NO REVIEW NEEDED.
  
 1.HOWEVER, IF A NEW SIGN FOR "OLD NAVY"IS PROPOSED.
 A REVIEW BY THE PLANNING AND ZONING WILL BE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 OFFICE: (561) 822-1443


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved