Plan Review Details - Permit 07040295
Plan Review Stops For Permit 07040295
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-06-20 Cont ID  
Sent By mjacobs Date 2007-06-20 Time 17:55 Rev Time 0.00
Received By mjacobs Date 2007-06-20 Time 17:28 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-05-29 Cont ID  
Sent By mjacobs Date 2007-05-29 Time 08:53 Rev Time 0.00
Received By mjacobs Date 2007-05-29 Time 08:08 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-20 Cont ID  
Sent By mjacobs Date 2007-04-20 Time 18:35 Rev Time 0.00
Received By mjacobs Date 2007-04-20 Time 14:45 Sent To  
Notes
2007-04-20 18:35:40BUILDING PLAN REVIEW
 PERMIT: 07040295
 ADD: 1515N.FLAGLER DR.
 CONT: PONITE SITE DEV. CONST.
 TEL: (561)792-4313
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)THE PUSH SIDE OF THE NEW TOILET DOOR SHALL HAVE A
 CLEAR SPACE OF 12". THE COUNTER TOP OF LAV-1 IS LESS
 THAN TWELVE INCHES FROM THE EDGE OF THE DOOR.SEE FBC
 CH.11 FIGURE 25 FOR MORE INFORMATION.
  
 3)IN REFERENCE TO SECTION 1210 OF THE FBC., STATE ON
 THE DRAWINGS WHAT MATERIALS WILL BE USE ON THE FLOOR
 AND WALLS.
  
 4)ALL THE INFORMATION ON THE ARCHITECT SEAL IS NOT
 LEGIGLE. THE NAME AND NUMBER OF THE REGISTERED
 ARCHICTECT SHALL BE LEGIBLE ON THE SEAL ALONG WITH ALL
 OTHER INFORMATION. FBC. 106.1.1 CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-11-28 Cont ID  
Sent By btrobaug Date 2007-11-28 Time 11:24 Rev Time 0.00
Received By btrobaug Date 2007-11-28 Time 07:44 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-06-19 Cont ID  
Sent By btrobaug Date 2007-06-19 Time 13:29 Rev Time 0.00
Received By btrobaug Date 2007-06-19 Time 13:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-05-24 Cont ID  
Sent By btrobaug Date 2007-05-24 Time 14:30 Rev Time 0.50
Received By btrobaug Date 2007-05-24 Time 12:53 Sent To  
Notes
2007-05-24 14:30:03 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE FIXTURE COUNT ON THE PLAN DO NOT MATCH THE WHAT
 IS INDICATED ON THE ENERGY GAUGE SHEET #2 IN THE ENERGY
 CALCULATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-25 Cont ID  
Sent By btrobaug Date 2007-04-25 Time 15:03 Rev Time 1.00
Received By btrobaug Date 2007-04-25 Time 13:52 Sent To I
Notes
2007-04-25 14:59:56 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 SHEET #2 OF THE ENERGY GAUGE ONLY LISTS 1 FLUORESCENT,
 AND NOTE THAT ALTHOUGH A MANUAL CONTROL IS LISTED, IT
 MUST AUTOMATICALLY TURN LIGHTS OFF WITHIN 30 MINUTES OF
 ALL OCCUPANTS LEAVING THE SPACE PER 13-415.1ABC.1.2(A).
 DESIGNATE WHICH MANUFACTURER AND MODELS ARE BEING
 SPECIFIED FOR THIS PROJECT BY THE ENGINEER.
  
 CORRELATE THE FIXTURE SCHEDULE WITH THE ENERGY CALCS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-06-20 Cont ID  
Sent By mawillia Date 2007-06-20 Time 12:27 Rev Time 0.00
Received By mawillia Date 2007-06-20 Time 12:19 Sent To  
Notes
2007-06-20 12:27:35*****APPROVED*****
  
  
 PLAN SHEET 2 (OF 2) WAS STAMPED, INITIALED, AND DATED
 ON 05/18/2007 BY CAPT. MIKE WENNERGREN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-13 Cont ID  
Sent By mwennerg Date 2007-04-13 Time 12:36 Rev Time 0.00
Received By mwennerg Date 2007-04-13 Time 12:36 Sent To  
Notes
2007-04-13 12:48:29***DENIED***
  
 1) PLEASE SEE MECHANICAL COMMENT REGARDING A FIRE
 DAMPER. NEW INSTALLATIONS SHALL BE TESTED FOR CLOSURE
 IN ACCORDANCE WITH UL 555 PRIOR TO FINAL INSPECTION.
  
 2) IN ACCORDANCE WITH LOCAL REQUIREMENTS, DUCT SMOKE
 DETECTORS TO INITIATE A GENERAL FIRE ALARM IF
 APPLICABLE.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-19 Cont ID  
Sent By adarroug Date 2007-11-19 Time 14:39 Rev Time 0.00
Received By adarroug Date 2007-11-19 Time 14:39 Sent To E
Notes
2007-11-19 14:39:30TO "BTROBAUGH" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-08 Cont ID  
Sent By adarroug Date 2007-06-08 Time 10:44 Rev Time 0.00
Received By adarroug Date 2007-06-08 Time 10:44 Sent To  
Notes
2007-06-11 15:34:20TO "BOB"#3
2007-06-08 10:45:17WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-07 Cont ID  
Sent By adarroug Date 2007-05-07 Time 15:32 Rev Time 0.00
Received By adarroug Date 2007-05-07 Time 15:32 Sent To  
Notes
2007-05-11 15:02:58TO "BOB"#10
2007-05-07 15:32:19WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-25 Cont ID  
Sent By btrobaug Date 2007-04-25 Time 15:03 Rev Time 0.00
Received By btrobaug Date 2007-04-10 Time 14:26 Sent To PC
Notes
2007-04-10 14:29:08TO "BOB"#5

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-05-18 Cont ID  
Sent By tgordon Date 2007-05-18 Time 10:44 Rev Time 0.30
Received By tgordon Date 2007-05-18 Time 10:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-11 Cont ID  
Sent By tgordon Date 2007-04-11 Time 10:24 Rev Time 1.00
Received By tgordon Date 2007-04-11 Time 10:24 Sent To  
Notes
2007-04-11 10:42:27*** DENIED ***
 1) SEE PAGE 2 A/C PLAN, V.D. FOR NEW 6" O.S.A. DUCT
 NEED TO BE INTHE SPACE THE A/C UNIT IT IS SERVING IS
 IN.
  
 2) THE 6" O.S.A. DUCT WILL REQUIRE A FIRE DAMPER WERE
 IT PENETRATES THE RATED TENANT SEPARATION PARTITION OR
 SHOW HOW IT MEETS THE EXCEPTIONS OF 2004 FBC/M
 607.5.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-05-15 Cont ID  
Sent By jleech Date 2007-05-15 Time 08:14 Rev Time 0.00
Received By jleech Date 2007-05-15 Time 08:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-12 Cont ID  
Sent By jleech Date 2007-04-12 Time 07:35 Rev Time 0.00
Received By jleech Date 2007-04-12 Time 07:35 Sent To  
Notes
2007-04-12 07:57:14DENIED;
 1. PAGE 1 (FLOOR PLAN NOTE) 14. TOILET ROOM FINISH,
 PLEASE SPECIFY MATERIAL TO BE USED ON THE FLOOR AND
 WALLS. SECTION 1210.2 REQUIRES A SMOOTH HARD SURFACE
 WITHIN 2' OF THE TOILET AND TO A HEIGHT OF 4' FROOM THE
 FLOOR. PAINT IS NOT A HARD SURFACE IT CAN CHIP OR
 SCRATCHED.
 2. SINK-1 IS NOT SHOWN ON THE SANITARY RISER DIAGRAM.
 3. WATER RISER, IF THE "T" AT THE TOP OF THE DROPS
 INDICATE WATER HAMMER ARRESTORS PLEASE LOWER THEM TO
 THE BOTTOM OF THE DROPS. SEE SECTION 604.9. WATER
 HAMMER ARRESTORS ARE NOT REQUIRED BUT IF INSTALLED THEY
 MUST BE INSTALLED CLOSE TO THE SOURCE OF HAMMER PER
 MANUFATURE SPECIFICATIONS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695