Plan Review Details - Permit 07040274
Plan Review Stops For Permit 07040274
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-08-30 Cont ID  
Sent By jwitmer Date 2007-08-30 Time 07:12 Rev Time 0.77
Received By jwitmer Date 2007-08-30 Time 07:12 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-13 Cont ID  
Sent By jwitmer Date 2007-06-13 Time 12:03 Rev Time 2.22
Received By jwitmer Date 2007-06-13 Time 12:02 Sent To PC
Notes
2007-06-13 12:33:42BUILDING PLAN REVIEW
 PERMIT: 07040274
 ADD: 6329 N JOG RD
 CONT: DELTA PETROLEUM
 TEL: (561)722-1632
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2A) THE REPLACEMENT OF THE ABOVE GROUND DIESEL TANK
 DOESN'T PROVIDE ANY MANUFACTURERES INFORMATION, PLEASE
 PROVIDE ADDITIONAL INFORMATION. IF THIS SYSTEM PROVIDES
 A DOUBLE WALLED TANK, IF SO OF WHAT TYPE OF MATERIAL?
 FBC 4115.2.5
 2B) THE SECOND CONCERN IS IF THE TANK TO BE PROVIDED IS
 A DOUBLE WALLED TANK HOW WOULD ONE KNOW IF THERE IS A
 LEAK BETWEEN THE TANKS? IS THERE AN LEAKAGE ALARM OR
 SIGNAL OF SOME TYPE? FBC 415.7.2.6
 2C) IN THE FUEL SYSTEM SITE WORK FOR THE REMOVAL OF THE
 OLD 5,000 DIESEL TANK THE PLANS INDICATE THE OLD
 CONTAINMENT WALL AND PEDESTALS WERE TO BE REMOVED.
 SECTION FBC 415.7.2.2 IT INDICATES EITHER A FIRE
 BARRIER WALL OR HORIZONTAL ASSEMBLIES OR BOTH AROUND
 THE STORAGE TANK SHALL BE PERMITTED.
  
 3) SHEET 2OF 2 TANK ANCHOR DETAIL INDICATES(1)1"
 REDHEAD TO BE INSTALLED INTO A 3,000 PSI SLAB. THE PLAN
 DOES NOT INDICATE HOW MANY ANCHORS WILL NEED TO BE
 INSTALLED TO RESIST THE MOMENT OF OVERTURNING?NOR
 DOES THE PLAN INDICATE IF THIS IS A NEW SLAB OR A
 REUSED SLAB. THERE IS A SLAB DETAIL FOR A FUEL SLAB?
  
 4) THIS SAME ANCHORING SYSTEM DOES NOT PROVIDE ALL THE
 WIND INFO REQUIRED.2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING CATEGORY (FUEL
 DISPENSING FACILITY)
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
  
 5) 406.5.1 CONSTRUCTION.MOTOR FUEL-DISPENSING
 FACILITIES SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE
 FLORIDA FIRE PREVENTION CODE AND THIS SECTION.
  
 6) PLEASE PROVIDE THE MSDS SHEETS FOR DIESEL.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-07-23 Cont ID  
Sent By dpalmer Date 2007-07-23 Time 15:17 Rev Time 0.00
Received By dpalmer Date 2007-07-23 Time 15:17 Sent To I
Notes
2007-07-23 15:23:48ELEC OK, ELECTRICAL PERMIT REQUIRED REQUIRED.
2007-07-23 15:18:27PLANS REMOVED FROM INCOMING, WILL BE RETURNED TO
 INCOMING WAITING FOR COMM BOARD ONCE REVIEW IS
 COMPLETED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-21 Cont ID  
Sent By dpalmer Date 2007-04-21 Time 13:30 Rev Time 0.00
Received By dpalmer Date 2007-04-21 Time 13:01 Sent To  
Notes
2007-04-21 13:30:40** UNSAT **
  
 1) NOTE: PLEASE STATE ON PLANS ALL UPDATED DATED
 ADOPTED CODES AS OF DECEMBER 8TH, 2006 WHICH MUTS
 INCLUDE THE FOLLOWING AT A MINIMUM FOR ELECTRICAL.
 NFPA-70 2005, 2004 FBC W/ 2006 REVISIONS.
 ** SEE OTHER TRADE REVIEWS FOR ANY OTHER CODES.
  
 2) NOTE: PLEASE PROVIDE A LAYOUT FOR ALL CLASS AND
 DIVISION LOCATIONS PER NEC 514.
 PLEASE INDICATE THE DISTANCE FOR EPO DEVICE. PLEASE SEE
 THE MINIMUM/MAXIMUM 541.11C
  
 3) NOTE: PLEASE INDICATE ANY INCREASE OF LOAD ON THE
 PANEL WHICH IS SHOWN AS EXISTING.
 220
 FBC 106.1.2
  
 4) NOTE: PLEASE PROVIDE FURTHER DETAIL FOR GROUNDING AS
 NOTED. PLEASE INDICATE SIZING, ATTACHMENT LOCATIONS.
 (NEW AND/OR EXISTING MEETING CURRENT CODE.514.16, 250,
 501.130
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-08-13 Cont ID  
Sent By mawillia Date 2007-08-13 Time 16:57 Rev Time 0.00
Received By mawillia Date 2007-08-13 Time 16:41 Sent To  
Notes
2007-08-13 16:52:32*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN SATISFIED;PLAN SHEET 2 (OF 2) STAMPED,
 INITIALED, AND DATED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-01 Cont ID  
Sent By mawillia Date 2007-06-01 Time 13:20 Rev Time 0.00
Received By mawillia Date 2007-06-01 Time 12:50 Sent To  
Notes
2007-06-01 12:49:28*****DENIED*****
  
  
 1.THE COMPLETE ADDRESS OF THE PROJECT LOCATION SHALL
 BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
 PLEASE NOTE THAT THE NUMBER 6329 IS MISSING.
  
 2.PRECAUTIONS SHALL BE TAKEN TO PREVENT THE IGNITION
 OF FLAMMABLE VAPORS FROM THE VARIOUS SOURCES BEFORE,
 DURING, AND AFTER THE PROJECTED SCOPE OF WORK.
  
 3.SMOKING SHALL BE PERMITTED ONLY IN DESIGNATED AND
 PROPERLY IDENTIFIED AREAS.
  
 4.ALL METALLIC EQUIPMENT WHERE AN IGNITABLE MIXTURE
 COULD BE PRESENT SHALL BE BONDED OR GROUNDED.
  
 5.UNSUPERVISED, ISOLATED ABOVEGROUND STORAGE TANKS
 SHALL BE SECURED AND MARKED IN SUCH A MANNER AS TO
 IDENTIFY THE FIRE HAZARDS OF THE TANK AND THE TANK'S
 CONTENT.THE AREA IN WHICH THE TANK IS LOCATED SHALL
 BE PROTECTED FROM TAMPERING OR TREPASSING, WHERE
 NECESSARY.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-11 Cont ID  
Sent By adarroug Date 2007-07-11 Time 09:28 Rev Time 0.00
Received By adarroug Date 2007-07-11 Time 09:28 Sent To  
Notes
2007-07-24 10:02:31TO "COMM" BD#24
2007-07-11 09:28:51WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-13 Cont ID  
Sent By jwitmer Date 2007-06-13 Time 12:02 Rev Time 0.00
Received By jwitmer Date 2007-04-09 Time 16:58 Sent To  
Notes
2007-04-12 13:46:23TO "COMM" BD#4
2007-04-09 16:58:51WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-08-02 Cont ID  
Sent By rregueir Date 2007-08-02 Time 09:35 Rev Time 0.00
Received By rregueir Date 2007-08-02 Time 08:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-01 Cont ID  
Sent By rregueir Date 2007-05-01 Time 08:22 Rev Time 0.00
Received By rregueir Date 2007-05-01 Time 08:06 Sent To  
Notes
2007-05-01 08:22:03--------------DENIED----------------
  
 PLEASE REFERENCE FLORIDA BUILDING CODE 2004 W/2006
 REVISIONS, AND NOT THE UNIFORM BUILDING CODE.
  
 PLEASE REVISE DRAWING TO ACCURATELY REFLECT TESTING
 METHODS AS STATED IN THE ATTACHED INSTALLATION
 INSTRUCTIONS. PLAN IS NOT TO BE ALTERED BY ANYONE OTHER
 THAN THE DESIGNER OF RECORD.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2007-07-31 Cont ID  
Sent By eschneid Date 2007-07-31 Time 17:38 Rev Time 0.00
Received By eschneid Date 2007-07-31 Time 17:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-13 Cont ID  
Sent By eschneid Date 2007-04-13 Time 12:21 Rev Time 0.00
Received By eschneid Date 2007-04-13 Time 12:21 Sent To  
Notes
2007-04-13 13:03:03FAILED
  
 1) THE 2005 AERIAL OF THE SITE SHOWS THAT THERE IS
 LANDSCAPING THAT PROVIDES A BUFFER FOR THE EAST SIDE OF
 THE TANK ADJACENT TO THE DRIVE AISLE.PLEASE VERIFY,
 EITHER ON THE PLAN OR WITH PHOTOS, THAT THE LANDSCAPING
 REMAINS ON THE EAST SIDE OF THE TANK.IF THE LANDSCAPE
 NO LONGER EXISTS, A HEDGE WILL BE REQUIRED TO SCREEN
 THE NEW TANK.
  
 CONTACT ERIC SCHNEIDER @ 822-1435.