| 2007-05-04 11:56:14 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | _XX_1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH |
| | THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13. |
| | |
| | _XX_4.IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R |
| | 301.2.1.2. |
| | |
| | _XX_5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG IF YOU ARE |
| | USING SHUTTERS.ALSO COMPLETE THE ATTACHED |
| | INSTALLATION SCHEDULE FOR SHUTTERS. |
| | |
| | _XX_6.PROVIDE A FLOOR PLAN SHOWING: WINDOW |
| | LOCATIONS, SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE |
| | EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE |
| | FOR BEDROOMS, FBC R310, FBC EB 505.1. |
| | |
| | NEW COMMENT: |
| | |
| | PROVIDE A REASONABLE VALUE FOR THIS JOB, INCLUDING |
| | IMPACT PROTECTION.THIS IS TO INCLUDE THE ***VALUE*** |
| | OF ALL MATERIALS AND LABOR.THE ADDITIONAL FEES WILL |
| | LIKELY BE MINIMAL BUT IT IS LIKELY THAT A NOTICE OF |
| | COMMENCEMENT WILL BE REQUIRED. |
| | |
| | THE SAME PAPERWORK WAS SUBMITTED.IF YOU NEED |
| | ASSISTANCE IN DETERMINING HOW TO SHOW CODE COMPLIANCE, |
| | PLEASE CONTACT ME.DO NOT RESUBMIT THE SAME PAPERWORK |
| | AGAIN AS IT DOES NOT SHOW CODE COMPLIANCE AND THEREFORE |
| | THE PERMIT CANNOT BE ISSUED.PLEASE ADDRESS EVERY |
| | COMMENT. |
| | |
| | THE RESPONSE STATED "N/A ALREADY EXISTING" FOR THE |
| | IMPACT REQUIREMENT.WHEN YOU REPLACE WINDOWS, THEY ARE |
| | TO COMPLY WITH IMPACT PROTECTION REQUIREMENTS AS NOTED |
| | IN ITEM 4.EITHER PROVIDE PRODUCT APPROVALS FOR IMPACT |
| | WINDOWS OR PROVIDE PRODUCT APPROVALS FOR THE IMPACT |
| | PROTECTION (PANELS, ACCORDIONS, ETC.) ALONG WITH THE |
| | INSTALLATION SCHEDULE SHOWING HOW THEY WILL BE |
| | INSTALLED. |
| | |
| | THE WINDOW ELEVATIONS WAS SUBMITTED BUT DID NOT ADDRESS |
| | THE COMMENT "NOTE EXISTING CONDITIONS (TYPE OF WINDOW) |
| | AND OPENING SIZE FOR BEDROOMS, FBC R 310, FBC EB |
| | 505.1."THERE ARE SPECIFIC CODE REQUIREMENTS FOR |
| | BEDROOMS BUT AS YOU HAVE NOT PROVIDED ME WITH THE |
| | INFORMATION I HAVE REQUESTED, I CANNOT DETERMINE |
| | WHETHER OR NOT THIS JOB IS CODE COMPLIANT AS PROPOSED. |
| | PLEASE PROVIDE THE INFORMATION REQUESTED SO THAT I CAN |
| | ASSIST YOU IN GETTING A PERMIT ISSUED. |
| | |