Plan Review Details - Permit 07040254
Plan Review Stops For Permit 07040254
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-17 Cont ID  
Sent By adarroug Date 2007-04-17 Time 11:27 Rev Time 0.00
Received By adarroug Date 2007-04-17 Time 11:27 Sent To M
Notes
2007-04-17 11:28:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-13 Cont ID  
Sent By tgordon Date 2007-04-13 Time 16:39 Rev Time 0.00
Received By tgordon Date 2007-04-09 Time 14:25 Sent To  
Notes
2007-04-09 14:25:54TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-04-24 Cont ID  
Sent By tgordon Date 2007-04-24 Time 11:28 Rev Time 0.40
Received By tgordon Date 2007-04-24 Time 11:28 Sent To  
Notes
2007-04-24 11:30:40*** PROVISO ***
 1) THE DWELLING WILL BE REQUIRED TO HAVE
 SMOKE ALARMS INSTALLED IF NOT ALREADY
 PRESENT, PER 2004 FBC/R 313.1.1, AND SEE
 2004 FEBC 303.1 LEVEL ONE ALTERATION
 INCLUDE REPLACEMENT OF EQUIPMENT.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-13 Cont ID  
Sent By tgordon Date 2007-04-13 Time 16:08 Rev Time 0.45
Received By tgordon Date 2007-04-13 Time 16:08 Sent To  
Notes
2007-04-13 16:12:02*** DENIED ***
 1) FLOOR PLAN DESIGN IS NOT OF GOOD QUALITY, UNABLE TO
 DEFINE WHAT THE ROOMS ARE, IF THEIR ARE DOORS, WERE THE
 AIR HANDLER IS LOCATED (IN CLOSET, OUT IN ROOM, OR IN
 ATTIC), NEED TO STATE ON PLANS IF FIRST OR SECOND
 FLOOR
  
 2) MECHANICAL PLANS ARE DIFFICULT TO READ. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY. PER 2004 FBC
 106.1.1.
  
 3) SHOW LOCATION OF THE TWO CONDENSER UNITS ON THE
 PLANS.
  
 4) SHOW LOCATION OF DRAIN LINES ON PLANS.
  
 5) SHOW SEER OF A/C SYSTEMS ON PLANS.
  
 6) SHOW HOW RETURN AIR IS GETTING FROM ROOMS TO AIR
 HANDLER.
  
 7) PLEASE SUBMIT PLANS THAT LOOK SOME-WHAT
 PROFESSIONAL. SEE 2004 FBC 106.1.1 AND CITY WPB AMEND.
 106.1.3 QUALITY OF BUILDING PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.