Plan Review Details - Permit 07040222
| Plan Review Stops For Permit 07040222 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2007-04-18 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-18 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-18 |
Time |
15:43 |
Sent To |
P |
|
| Notes |
| 2007-04-18 17:07:30 | SENT TO JL DESK. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-04-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-04-16 |
Time |
16:34 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2007-04-16 |
Time |
15:56 |
Sent To |
|
|
| Notes |
| 2007-04-16 16:24:08 | | | | NONCOMPLIANT | | | | | | THE ENGINEER OF RECORD SHALL INDICATE THE CERTIFICATE | | | OF AUTHORIZATIONNUMBER ALONG WITH OTHER INFORMATION | | | REQUIRED BY 61G15-23.002FLORIDA ADMINISTRATIVE CODE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-04-18 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-04-18 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-04-18 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2007-04-18 10:57:16 | ***DENIED*** | | | | | | 1) PLEASE NOTE OTHER REVIEW COMMENTS REGARDING | | | REQUIREMENTS OF FAC 61G15-23.002 AND MAKE CORRECTIONS. | | | | | | 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY | | | WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2007-04-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-04-06 |
Time |
17:33 |
Sent To |
|
|
| Notes |
| 2007-04-06 17:33:21 | TO BOB # 14 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-04-09 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-04-09 |
Time |
09:55 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-04-09 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2007-04-09 10:02:42 | *** DENIED *** | | | 1) INFORMATION MISSING FROM TITLE BLOCK, ENGINEER'S | | | PRINTED NAME AND LICENSE NUMBER, ALSO THE ENGINEERING | | | BUSINESS'S CERTIFICATE OF AUTHORIZATION NUMBER. | | | SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET | | | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE | | | NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND | | | LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS | | | AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE | | | ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-04-19 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-04-09 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-04-09 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2007-04-19 10:09:18 | INFORMATION MISSING FROM TITLE BLOCK. ENGINEER'S | | | PRINTED NAME AND LICENSE NUMBER.PLANS TO BE SEALED | | | AND SIGNED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
|