Plan Review Details - Permit 07040221
Plan Review Stops For Permit 07040221
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-30 Cont ID  
Sent By jgomez Date 2007-04-30 Time 13:07 Rev Time 0.00
Received By jgomez Date 2007-04-30 Time 13:07 Sent To P
Notes
2007-04-30 13:24:31BUILDING REVIEW CHECKLIST:
 1- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 VALUATION SHALL INCLUDE, LABOR, MATERIALS AND
 ENGINEER'SFEES.REVISE VALUE TO INCLUDE ALL THIS
 FACTORS OR IT WILL BE UPDATED ACCORDING TO SEC. 108.3
 CITY AMENDMENTS TO FBC 2004.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 3- AFTER DRAWINGS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. FLAGLER DR. (561)233-5115)TO PAY
 IMPACT FEES. BRING BACK STAMPED DRAWINGS AND COPY OF
 PAID RECEIPT IF ADDITIONAL FEES ARE DUE.
  
 4- ENGINEER TO PROVIDE ALL HIS INFORMATION IN ALL
 DRAWINGS ASREQUIRED BY SEC. 61G15-23.002OF FLORIDA
 ADMINISTRATIVE CODE.
  
 5- ENGINEER TO CLARIFY HIS STATUS WITHDBPR. ACCORDING
 TO THE WEBSITE HIS LICENSE IS IN DELINQUENT STATUS.
 NEED TO CORRECT INFORMATION PRIOR TO SUBMITTAL OF
 DRAWINGS TO THIS OFFICE.
  
 6- SHEET 1:
 A) TYPICAL WALL SECTION CALLS FOR EXISTING CONC.
 BEAM BUT ARROWIS POINTING TO THE FOOTING. REVISE AS
 REQUIRED.
  
 B) SPECIFY CEILING INSULATION. SEE ENERGY
 CALCULATIONS.
  
 C) SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R602.1.2
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 D) SPECIFY BUILDING CODE AND DESIGN CRITERIA AS
 REQUIRED BY SEC. R301 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 E) SPECIFY DESIGN PRESSURES FOR EXTERIOR DOORS AND
 WINDOWS AS REQUIRED BYTABLE 1609.6.2.1(2) OF 2004
 FBC.
  
 F) SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806
 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 G) PROVIDE COMPLETEDETAILS/SPECS FOR STRUCTURAL
 BUCKS FOR EXTERIOR DOORS AND WINDOWS. SEE SEC. R613.6.2
 OF 2004 FLORIDA RESIDENTIAL CODE FOR PROPER WAY OF
 INSTALLING BUCKS. ALSO, SEE PRODUCT APPROVALS FOR
 REQUIRED BUCK SIZE.
  
 H)MISSINGSPECS FOR COLUMNS AT THE ENDS OF
 OPENINGS AND FOR LINTELS ABOVE OPENINGS.ALSO MISSING
 SPECS FOR CONCRETE BLOCK REINFORCEMENT.PROVIDE
 COMPLETE INFORMATION. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 7-PROVIDE ENERGY CALCULATIONS(2 COPIES) AS REQUIRED
 BY SEC. 13-600 FBC 2004. FORMS TO BE COMPLETE INCLUDING
 INFORMATION ON TOP OF FORM AND BOTTOM OF FORM TO BE
 SIGNED AND DATED BY THE OWNER OR AGENT.
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) EXTERIOR DOOR.
  
 B) WINDOW MULLIONS.
  
 C) PRECAST LINTELS IF SPECIFIED ONPLANS.
  
 9- ENGINEER TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-12 Cont ID  
Sent By btrobaug Date 2007-04-12 Time 15:46 Rev Time 0.50
Received By btrobaug Date 2007-04-12 Time 15:29 Sent To P
Notes
2007-04-12 15:46:37 
  
  
 1} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES PER 108.3 FBC AS
 AMENDED. INCREASE THE VALUE AT THE
 COUNTER AND RESUBMIT.
  
 2} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD.
  
 3} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1)
 AND 210.52 (A) (2).
  
 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY. THE CONTRACTOR OF RECORD MAY BE THE
 DESIGN PROFESSIONAL IF EXEMPTIONS UNDER THOSE STATUTES
 ARE APPLICABLE. THE ENGINEER MUST PROVIDE A TITLE
 BLOCK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 09:50 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 09:50 Sent To E
Notes
2007-04-12 09:51:06TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-02 Cont ID  
Sent By jroach Date 2007-05-02 Time 08:15 Rev Time 0.00
Received By tgordon Date 2007-04-06 Time 17:35 Sent To  
Notes
2007-04-06 17:35:59TO ZONING

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-05-02 Cont ID  
Sent By tgordon Date 2007-05-02 Time 08:13 Rev Time 0.15
Received By tgordon Date 2007-05-02 Time 08:13 Sent To  
Notes
2007-05-02 08:14:41NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-05-01 Cont ID  
Sent By jleech Date 2007-05-01 Time 14:14 Rev Time 0.00
Received By jleech Date 2007-05-01 Time 14:14 Sent To M
Notes
2007-05-01 14:14:55NO PLUMBING SHOWN ON THIS PLAN.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-04-11 Cont ID  
Sent By jroach Date 2007-04-11 Time 20:01 Rev Time 0.00
Received By jroach Date 2007-04-11 Time 20:01 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-10 Cont ID  
Sent By jroach Date 2007-04-10 Time 19:09 Rev Time 0.00
Received By jroach Date 2007-04-10 Time 19:09 Sent To I
Notes
2007-04-10 19:13:01***FAILED***
  
 1) PROPOSED ENCLOSURE SHALL CONFORM TO THE MINIMUM
 FRONT SETBACK OF 25 FEET.ACCORDING TO THE SURVEY, THE
 STRUCTURE IS 24.9 FEET FROM THE FRONT PROPERTY LINE.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.