| 2007-04-30 13:24:31 | BUILDING REVIEW CHECKLIST: |
| | 1- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW. |
| | VALUATION SHALL INCLUDE, LABOR, MATERIALS AND |
| | ENGINEER'SFEES.REVISE VALUE TO INCLUDE ALL THIS |
| | FACTORS OR IT WILL BE UPDATED ACCORDING TO SEC. 108.3 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | |
| | 3- AFTER DRAWINGS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. FLAGLER DR. (561)233-5115)TO PAY |
| | IMPACT FEES. BRING BACK STAMPED DRAWINGS AND COPY OF |
| | PAID RECEIPT IF ADDITIONAL FEES ARE DUE. |
| | |
| | 4- ENGINEER TO PROVIDE ALL HIS INFORMATION IN ALL |
| | DRAWINGS ASREQUIRED BY SEC. 61G15-23.002OF FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | 5- ENGINEER TO CLARIFY HIS STATUS WITHDBPR. ACCORDING |
| | TO THE WEBSITE HIS LICENSE IS IN DELINQUENT STATUS. |
| | NEED TO CORRECT INFORMATION PRIOR TO SUBMITTAL OF |
| | DRAWINGS TO THIS OFFICE. |
| | |
| | 6- SHEET 1: |
| | A) TYPICAL WALL SECTION CALLS FOR EXISTING CONC. |
| | BEAM BUT ARROWIS POINTING TO THE FOOTING. REVISE AS |
| | REQUIRED. |
| | |
| | B) SPECIFY CEILING INSULATION. SEE ENERGY |
| | CALCULATIONS. |
| | |
| | C) SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R602.1.2 |
| | OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | D) SPECIFY BUILDING CODE AND DESIGN CRITERIA AS |
| | REQUIRED BY SEC. R301 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | E) SPECIFY DESIGN PRESSURES FOR EXTERIOR DOORS AND |
| | WINDOWS AS REQUIRED BYTABLE 1609.6.2.1(2) OF 2004 |
| | FBC. |
| | |
| | F) SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806 |
| | OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | G) PROVIDE COMPLETEDETAILS/SPECS FOR STRUCTURAL |
| | BUCKS FOR EXTERIOR DOORS AND WINDOWS. SEE SEC. R613.6.2 |
| | OF 2004 FLORIDA RESIDENTIAL CODE FOR PROPER WAY OF |
| | INSTALLING BUCKS. ALSO, SEE PRODUCT APPROVALS FOR |
| | REQUIRED BUCK SIZE. |
| | |
| | H)MISSINGSPECS FOR COLUMNS AT THE ENDS OF |
| | OPENINGS AND FOR LINTELS ABOVE OPENINGS.ALSO MISSING |
| | SPECS FOR CONCRETE BLOCK REINFORCEMENT.PROVIDE |
| | COMPLETE INFORMATION. SEC. 106.1.2 CITY AMENDMENTS TO |
| | FBC 2004. |
| | |
| | 7-PROVIDE ENERGY CALCULATIONS(2 COPIES) AS REQUIRED |
| | BY SEC. 13-600 FBC 2004. FORMS TO BE COMPLETE INCLUDING |
| | INFORMATION ON TOP OF FORM AND BOTTOM OF FORM TO BE |
| | SIGNED AND DATED BY THE OWNER OR AGENT. |
| | |
| | 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) EXTERIOR DOOR. |
| | |
| | B) WINDOW MULLIONS. |
| | |
| | C) PRECAST LINTELS IF SPECIFIED ONPLANS. |
| | |
| | 9- ENGINEER TO REVIEW AND APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |
| | |
| | |