Plan Review Details - Permit 07040189
Plan Review Stops For Permit 07040189
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-06-11 Cont ID  
Sent By lursu Date 2007-06-11 Time 16:49 Rev Time 0.00
Received By lursu Date 2007-06-08 Time 10:27 Sent To  
Notes
2007-06-11 16:49:42PERMIT ATTACHED TO CORRECT PARCEL , PCN =
 74434318170021040
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
  
2007-06-08 10:28:00APPL. SHOWS 1707 VILLAGE BLVD APT.104--COPY SENT TO
 LILI

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-09-20 Cont ID  
Sent By shill Date 2007-09-20 Time 17:50 Rev Time 0.00
Received By shill Date 2007-09-20 Time 17:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-08-30 Cont ID  
Sent By shill Date 2007-08-30 Time 18:07 Rev Time 0.00
Received By shill Date 2007-08-30 Time 18:07 Sent To  
Notes
2007-08-30 18:13:17****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 FROM PREVIOUS LIST:
  
 4.)THE SHUTTER CONNECTION MOUNTING TYPE IS BLANK.
 THIS SHOULD BE A THROUGH L, SEE THE PRODUCT APPROVAL
 ANCHOR SCHEDULES.
  
 THIS SHOULD BE A THROUGH L, SEE THE PRODUCT APPROVAL
 ANCHOR SCHEDULES.SEE PAGE 14.YOU HAVE HIGHLIGHTED
 F, G, AND H.SPECIFY WHICH CONNECTION TYPE GOES WITH
 EACH OPENING, TOP AND BOTTOM.
  
 NEW COMMENT, 6TH REVIEW:
  
 YOU'VE HIGHLIGHTED THREE DIFFERENT CONNECTION TYPES.
 CONNECTION E REQUIRES 7" SPACING.
  
 INSTALLATION SCHEDULE STATES "WALL", BUT NONE OF THE
 WALL CONNECTION TYPES ON SHEET 13 ARE HIGHLIGHTED.
 WALL TYPES WILL BE A THROUGH E.IF YOU ARE USING E,
 WHICH IS HIGHLIGHTED, 7" ANCHOR SPACING REQUIRED.
 YOU'VE SPECIFIED 7.5".CODE COMPLIANCE CANNOT BE
 DETERMINED UNTIL YOU PROVIDE THIS INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-08-13 Cont ID  
Sent By shill Date 2007-08-13 Time 08:31 Rev Time 0.00
Received By shill Date 2007-08-13 Time 08:31 Sent To  
Notes
2007-08-13 08:34:18****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 FROM PREVIOUS LIST:
  
 4.)THE SHUTTER CONNECTION MOUNTING TYPE IS BLANK.
 THIS SHOULD BE A THROUGH L, SEE THE PRODUCT APPROVAL
 ANCHOR SCHEDULES.
  
 NEW COMMENT:NOW STATES "WALL SILL/CEILING/FLOOR".
 THIS SHOULD BE A THROUGH L, SEE THE PRODUCT APPROVAL
 ANCHOR SCHEDULES.SEE PAGE 14.YOU HAVE HIGHLIGHTED
 F, G, AND H.SPECIFY WHICH CONNECTION TYPE GOES WITH
 EACH OPENING, TOP AND BOTTOM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-07-30 Cont ID  
Sent By shill Date 2007-07-30 Time 15:43 Rev Time 0.00
Received By shill Date 2007-07-30 Time 15:43 Sent To  
Notes
2007-07-30 15:44:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 SHUTTER
 PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 FROM PREVIOUS LIST:
  
 _XX_4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.ALL INFORMATION IS REQUIRED.
  
  
 THE SHUTTER CONNECTION MOUNTING TYPE IS BLANK.THIS
 SHOULD BE A THROUGH L, SEE THE PRODUCT APPROVAL ANCHOR
 SCHEDULES.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-16 Cont ID  
Sent By shill Date 2007-07-16 Time 18:36 Rev Time 0.00
Received By shill Date 2007-07-16 Time 18:36 Sent To  
Notes
2007-07-16 18:37:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 FROM PREVIOUS LIST:
  
 _XX_4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.ALL INFORMATION IS REQUIRED.
  
  
 _XX_9.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2),
 FBC R301.2.1.4 OR PROVIDE JUSTIFICATION FOR EXPOSURE B
 PRESSURES (AERIALS OR SURVEY WITH DIMENSIONS).NOTE
 THAT THE DEFINITION FOR EXPOSURE C HAS CHANGED
 EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC R301.2.1.4.
  
 2ND REVIEW - YOU'VE SUPPLIED NEW WIND LOAD CALCS BUT
 THE DESIGN PRESSURE ON THE INSTALLATION SCHEDULE IS
 STILL FOR EXPOSURE B.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-19 Cont ID  
Sent By shill Date 2007-06-19 Time 10:10 Rev Time 0.00
Received By shill Date 2007-06-19 Time 10:10 Sent To  
Notes
2007-06-19 10:12:34****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 ____1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED,
 FS713.13.
  
 ____2.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A
 DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS FAC61G15-23.002.
  
 ____3.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.ALL INFORMATION IS REQUIRED.
  
 ____5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____6.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS
 APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A
 HIGHLIGHTER.
  
 ____7.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 ____8.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 4
 ABOVE.
  
 _XX_9.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2),
 FBC R301.2.1.4 OR PROVIDE JUSTIFICATION FOR EXPOSURE B
 PRESSURES (AERIALS OR SURVEY WITH DIMENSIONS).NOTE
 THAT THE DEFINITION FOR EXPOSURE C HAS CHANGED
 EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC R301.2.1.4.
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-09-18 Cont ID  
Sent By adarroug Date 2007-09-18 Time 12:26 Rev Time 0.00
Received By adarroug Date 2007-09-18 Time 12:26 Sent To B
Notes
2007-09-18 12:26:46TO "SHILL' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-28 Cont ID  
Sent By adarroug Date 2007-08-28 Time 13:37 Rev Time 0.00
Received By adarroug Date 2007-08-28 Time 13:37 Sent To B
Notes
2007-08-28 13:37:53TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-06 Cont ID  
Sent By adarroug Date 2007-08-06 Time 13:23 Rev Time 0.00
Received By adarroug Date 2007-08-06 Time 13:23 Sent To B
Notes
2007-08-06 13:23:30TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-27 Cont ID  
Sent By adarroug Date 2007-07-27 Time 10:33 Rev Time 0.00
Received By adarroug Date 2007-07-27 Time 10:33 Sent To B
Notes
2007-07-27 10:34:12TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-11 Cont ID  
Sent By adarroug Date 2007-07-11 Time 14:44 Rev Time 0.00
Received By adarroug Date 2007-07-11 Time 14:44 Sent To B
Notes
2007-07-11 14:44:54TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-19 Cont ID  
Sent By shill Date 2007-06-19 Time 10:12 Rev Time 0.00
Received By shill Date 2007-06-08 Time 10:28 Sent To  
Notes
2007-06-08 10:28:28TO "MISC' BOX#1