| Plan Review Stops For Permit 07040128 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-09-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-09-28 |
Time |
06:45 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-09-28 |
Time |
06:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2007-05-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-05-29 |
Time |
07:22 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-05-29 |
Time |
06:58 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-04-13 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-13 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-13 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2007-04-13 11:50:18 | BUILDING PLAN REVIEW | | | PERMIT: 07040128 | | | ADD: 1617 N. FLAGLER DR. APT, 9A | | | CONT: RICKEY J. WILSON CONST. INC. | | | TEL: (561)###-#### | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)106.1IF THE DESIGN PROFESSIONAL IS AN ARCHITECT | | | OR ENGINEER LEGALLY REGISTERED UNDER THE LAWS OF THIS | | | STATE REGULATING THE PRACTICE OF ARCHITECTURE AS | | | PROVIDED FOR IN CHAPTER 481, FLORIDA STATUTES, PART 1, | | | OR ENGINEERING AS PROVIDED FOR IN CHAPTER471, FLORIDA | | | STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER | | | OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS. | | | | | | 3)108.3*THE CLAIMED VALUATION ON THE PERMIT | | | APPLICATION IS LOW. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT | | | COST EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS | | | ICC (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS | | | SERVICES. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-10-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-10-10 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-10-10 |
Time |
10:48 |
Sent To |
PC |
|
| Notes |
| 2007-10-10 11:02:27 | | | | | | | CANNOT FIND FILE COPY.PER LUIS, REVIEWED FOR CODE | | | COMPLIANCE AND CALLED FOR PICK UP./WRT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-05-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-05-10 |
Time |
16:31 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2007-05-10 |
Time |
16:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-04-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-04-16 |
Time |
17:02 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2007-04-16 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2007-04-16 17:02:30 | | | | | | | NONCOMPLIANT | | | | | | THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON THE | | | PLANS, MUST SIGN AND SEAL THE PLAN PER | | | 481.221(1)(B)FS. | | | | | | 1} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED | | | IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. | | | | | | 2} NFPA-72 REQUIRES ALARMS OR DETECTORS WITHIN 20 FEET | | | OF COOKING APPLIANCES BE SILENCING OR PHOTOELECTRIC. | | | SEE 11.8.3.5(4). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2007-05-16 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-05-16 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-05-16 |
Time |
15:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-04-13 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-04-13 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-04-13 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2007-04-13 14:08:15 | ***DENIED*** | | | | | | 1) PLANS ARE REQUIRED TO BE SIGNED, SEALED AND DATED BY | | | DESIGN PROFESSIONAL IN ACCORDANCE WITH FLORIDA | | | STATUTES. | | | | | | 2) PLEASE PROVIDE INFORMATION REGARDING HOW MANY FIRE | | | SPRINKLER HEADS WILL BE IMPACTED BY THIS WORK. SEPARATE | | | SHOP DRAWINGS AND PERMIT MAY BE REQUIRED. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-09-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-17 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-17 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2007-09-24 15:51:43 | TO "BOB"#7 | | 2007-09-17 11:53:26 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-05-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-03 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-03 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2007-05-07 13:19:24 | TO "BOB"#5 | | 2007-05-03 16:17:55 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2007-04-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-04-05 |
Time |
17:39 |
Sent To |
|
|
| Notes |
| 2007-04-05 17:39:58 | TO BOB # 8 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2007-05-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-05-14 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-05-14 |
Time |
09:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-04-09 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-04-09 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-04-09 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2007-04-09 09:22:00 | DENIED; | | | PLANS ARE REQUIRED TO BE SEALED SIGNED AND DATED BY THE | | | DESIGN PROFESSIONAL. SEE CHAPTER 481 FLORIDA STAUTES | | | PART 1. | | | PLUMBING PLAN REVIEW OK. WILL STAMP WHEN PLANS ARE | | | SIGNED AND SEALED. | | | PLUMBING PLAN REVIEW BY | | | JOHN LEECH | | | 805-6695 |
|
|