Plan Review Details - Permit 07040087
Plan Review Stops For Permit 07040087
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-01 Cont ID  
Sent By jwitmer Date 2007-09-01 Time 13:00 Rev Time 2.00
Received By jwitmer Date 2007-09-01 Time 13:00 Sent To  
Notes
2007-09-01 13:15:14BUILDING PLAN REVIEW
 PERMIT: 07040087
 ADD: 4720 N DIXIE HWY
 CONT: NUNNO BUILDERS
 TEL: (954)961-0777
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE! WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3A)THE EDITION OF THE CODE UNDER WHICHTHE PERMIT
 WAS ISSUED. WHAT LEVEL OF ALTERATION WILL THIS BE ,
 2004 EXISTING BUILDING CODE? PLANS INDICATED LEVEL I
 PLESE SEE THE REMOVAL OF RESTROOM FACILITIES AND THE
 RECONFIGURATION MADE A LEVEL II ALTERATION. THE REMOVAL
 OF THE ROOF PARAPET,&MANSARD PLUS THE REST OF THE
 DESCRIBED WORK IN THE PROJECT WILL CLASSIFY THIS AS A
 LEVEL III ALTERATION.
  
 3B) COMPLIED.
  
 3C) PLANS INDICATE THIS BUILDING TO BE A TYPE III
 BUILDING PLEASE PROVIDE IF THIS IS A
 **A OR B**. IF THE DESIGNER WISHES TO CLASSIFY THIS AS
 A MORE RESTIVE IIA OR IIIB THE BUILDING WILL BE
 REQUIRED TO MEET THESE RATINGS. THE MINIMUM CODE
 CLASSIFIES THIS AS A VB.FOR THIS REVIEW THE REVIEWER
 WILL CONTINUE THE REVIEW AS A VB BUILDING, BUT THE NEXT
 ROUND OF COMMENTS WILL FOLLOW THE DESIGNERS DESIGNATION
 OF THE BUILDING.
  
 3D-F) COMPLIED.
  
 4) COMPLIED.
  
 5)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT
 TESTING REPORTS, MISSING REPORTS ARE AS FOLLOWS: A)
 EFIS WALL SYSTEMS MISSING THE FLORIDA COVER SHEET/
 DESIGNER OF RECORD APPROVAL
 WITH SHOP DRAWING STAMP.
 B) TRUSS ANCHORS NONE SUBMITTED WILL REQUIRE THE
 FLORIDA COVER SHEET/ DESIGNER OF
 RECORD APPROVAL WITH SHOP DRAWING STAMP.
  
 C) ROOFING ASSEMBLIES- THE FLORIDA COVER SHEET/
 DESIGNER OF RECORD APPROVAL
 WITH SHOP DRAWING STAMP. SUBSYSTEMS ARE NOT
 HIGHLIGHTED. WILL REQUIRE ENHANCED
 FASTENING IN ZONES 2 & 3. PROVIDE RAS 117
 CALCULATIONS PER LIMITATION# 7.
  
 D) FIXED/ STOREFRONT WINDOWS-NONE WERE SUPPLIED.
 PROVIDETHE FLORIDA COVER SHEET/ PRODUCT TESTING
 SHEETS & DESIGNER OF RECORD APPROVALWITH SHOP
 DRAWING STAMP.
  
  
 6)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA PRODUCT
 APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 7) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 8A) 2ND REQUEST, SHEET A-4.1 INDICATES THE FRAMING
 DETAIL FOR THE NEWLY DESIGNEDTOWER, SHEET A-4.1
 INDICATES THE NEW TOWER HAS THE CENTER OPEN AND THE
 INSIDE WALLS HAVE A MODIFIED BITUMEN ROOFING MEMBRANE,
 THERE APPEARS TO BE NO ROOF DRAIN NOR OVERFLOW SCUPPERS
 TO ALLOW THE RAIN WATER OUT OF THIS BOX LOOKING TOWER.
 HOW WILL RAIN WATER BE DRAINED?
  
 8B) SHEET A.4.0, A.4.1 & A5.0 ALL SHOW THE PARAPET
 DETAILS, BUT NONE INDICATE HOW THE
 PARAPET WILL BE ATTACHED TO THE EXISTING STRUCTURE?
 106.1.2*/ 1609 HOW WILL THE MOMENT OF OVERTURNING BE
 RESTRICTED?
  
 9) COMPLIED CANOPY AND AWNINGS TO BE UNDER A SEPARATE
 PERMIT.
  
 10)THE NEW RESTROOM LAYOUT HAS DISCREPANCIES, SEE THE
 MEN?S RESTROOM DOOR ON SHEET A1.0 VERSES E1.0. SHEET
 A1.0 THE IN SWING DOOR INTERFERES WITH THE CLEAR FLOOR
 SPACE REQUIRED FOR THE URINAL, 11-4-18-3.SHEET E1.0
 THE DOOR BLOCKS THE EGRESS ROUTE. SEE 1005.2.
  
 11) A SECOND DISCREPANCY IS D2 VERSES A.1.0 SHEET A.1.0
 INDICATES WINDOWS 4(A) & 4(B) ON THE DEMO PLAN ONE
 WINDOW STAYS AND ONE IS REPLACED. PLEASE CORRELATE.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-11 Cont ID  
Sent By jwitmer Date 2007-06-11 Time 17:13 Rev Time 3.44
Received By jwitmer Date 2007-06-11 Time 17:13 Sent To PC
Notes
2007-06-11 17:23:10BUILDING PLAN REVIEW
 PERMIT: 07040087
 ADD: 4720 N DIXIE HWY
 CONT: NUNNO BUILDERS
 TEL: (954)961-0777
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) P.E. EDUARDO CARCACHE HAS USED A SEAL WITH THE
 WORDING "CERTIFICATE":
 RULE 61G15-23.001(1) F.A.C.
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS HAS CLEANED UP THE APPEARANCE
 OF THE SEAL BY ELIMINATING OBSOLETE
 CONTENT AND CHANGING THE WORD
 "CERTIFICATE" TO "LICENSE". A GRACE
 PERIOD RAN THROUGH DEC. 31,2005.
  
 PURSUANT TO SECTION 471.025 F. S. , THE
 BOARD HEREBY ESTABLISHES AS INDICATED
 BELOW THE FORMS OF EMBOSSING IMPRESSION
 SEALS WHICH ARE ACCEPTABLE TO THE BOARD.
 SAID SEAL SHALL BE A MINIMUM OF 1 7/8"
 IN DIAMETER. ALL ENGINEERS MUST BE
 UTILIZING SEALS AS ILLUSTRATED IN THIS
 RUKE NO LATER THAN JANUARY 1, 2006.
  
 3)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 WHAT LEVEL OF ALTERATION WILL THIS BE ,
 2004 EXISTING BUILDING CODE?
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THEOCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 4) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EFIS WALL SYSTEMS
 B) TRUSS ANCHORS
 C) ROOFING ASSEMBLIES
  
 6)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 8) SHEET A-4.1 INDICATES THE FRAMING DETAIL FOR THE
 NEWLY DESIGNEDTOWER, SHEET A-4.1 INDICATES THE NEW
 TOWER HAS THE CENTER OPEN AND THE INSIDE WALLS HAVE A
 MODIFIED BITUMEN ROOFING MEMBRANE, THERE APPEARS TO BE
 NO ROOF DRAIN NOR OVERFLOW SCUPPERS TO ALLOW THE RAIN
 WATER OUT OF THIS BOX LOOKING TOWER. HOW WILL RAIN
 WATER
 BE DRAINED?
  
 SHEET A-3.0 INDICATES A STRIPED ILLUMINATED TOWER BY
 KFC/ VENDOR, IS THIS TO BE UNDER SEPERATE PERMIT? IS
 THIS TO KEEP OUT RAIN OR IS THIS ADVERTISEMENT
 PURPOSES?
 WILL THERE BE ENGINEERING SHOWING COMPLIANCE WITH 140
 MPH WIND LOADS?
  
 9) PLANS SHOW AWNINGS BUT NO INFORMATION HAS BEEN
 PROVIDED AS TO THE TYPE OF AWNING IF FIXED IN PLACE, IF
 CLOTH ETC, TO BE UNDER A SEPERATE PERMIT?
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-23 Cont ID  
Sent By dpalmer Date 2007-08-23 Time 07:12 Rev Time 0.00
Received By dpalmer Date 2007-08-22 Time 21:14 Sent To  
Notes
2007-08-23 07:18:432007-08-23 07:18:43
 *** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO
 CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED.
  
 1) NOTE:PLEASE COMPLETE ELECTRICAL PLANS WITH
 ELECTRICAL AS SHOWN ON REFLECTED CEILING PLANS. PLEASE
 SEE MISSING INFORMATION FOR EXTERIOR LIGHTING, LOAD,
 SIZE AND TYPE OF FIXTURES.
 ONLY SOME SHOWN.
 PLEASE SEE FBC CHAPTER 13, 13-415.2 FOR MAXIMUM
 LIGHTING DENSITIES. PLEASE PROVIDE THESE ON PLANS. FBC
 106.1.2
  
 2) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK
 SEEMS LOW. PLEASE KNOW THE VALUE FOR WORK MUST INCLUDE
 ALL LABOR, MATERIALS AND EQUIPMENT EVEN IF OWNER
 SUPPLIED. PLEASE SEE THIS INCLUDES DESIGN COST,
 EQUIPMENT, FIXTURES WHICH MAY BE OWNER/CORPORATE
 SUPPLIED AND ALL LABOR.
 THE VALUE WAS NOT ADJUSTED.
 FBC 108.3
  
 3) NOTE: PLEASE SEE THE AMOUNT AND LOCATION OF THE
 EXISTING SHOWN EMERGENCY LIGHTS DO NOT SEEM TO PROVIDE
 THE MINIMUM 1FT CANDLE OF LIGHTING UNDER EMERGENCY
 CONDITIONS. PLEASE SEE LS 101 7.8/7.9 AND ADJUST AS
 NEEDED.
 PLEASE SEE HALLWAY OUTSIDE BATHROOMS, KITCHEN AREA AND
 DINING AREA OUTSIDE BATHROOMS.
 PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G15-23.004
 WHICH REQUIRES MINIMUM LIGHTING LEVELS TO BE FIGURED
 FOR AREAS AS NOTED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-08-22 21:14:482007-08-22 21:14:48
 IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-15 Cont ID  
Sent By dpalmer Date 2007-04-15 Time 19:31 Rev Time 0.00
Received By dpalmer Date 2007-04-15 Time 19:31 Sent To  
Notes
2007-04-15 19:31:48** UNSAT **
  
 ** PLEASE SEE ANY REFERENCES IN PLAN REVIEW NOTES TO
 CHAPTER 1 OF THE FBC ARE THAT WHICH IS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLANS AT THIS TIME DO NOT INDICATE ANY CODES. PLEASE
 SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004
 FBC FOR ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW
 THERE ARE CHANGES IN THE FBC WHICH MAY AFFECT DESIGNS
 FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THE SEAL WHICH IS BEING USED BY THE
 ENGINEER IS NO LONGER VALID IN THE STATE OF FLORIDA.
 PLEASE SEE RULING FROM THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS IN FEB OF 04 WHICH REQUIRED ALL
 SEALS TO CONTAIN THE WORDING OF *LICENSE*. AN EXTENSION
 WAS GIVEN DECEMBER 31ST, 2005 HOWEVER ALL SEALS FOR
 ENGINEERS AFTER THAT DATE MUST USE NEW SEALS. PLEASE
 OBTAIN NEW SEAL.
 FAC 61G15-23.001
 ** THIS IS REQUIRED FOR ALL TRADES AND SHEETS WHETHER
 OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 3) NOTE: PLEASE SEE FS 471.025, AND FAC 61G15-23.002
 WHICH REQUIRES PLANS TO BE SIGNED, DATED AND SEALED BY
 THE ENGINEER.
 PLEASE SEE PLANS APPEAR TO BE SIGNED, WITH *INITIALS*,
 IF THIS IS INDEED THE LEGAL SIGNATURE OF SAID ENGINEER,
 PLEASE SUBMIT, SIGNED, DATED AND SEALED LETTER FOR
 LEGAL SIGNATURE VERIFICATION. THIS WILL BE PLACED IN
 OUR SIGNATURE FILE FOR ANY FUTURE REFERENCE.
 ** PLEASE KNOW THAT THE LETTER WILL BE REQUIRED TO BE
 NOTARIZED WITH CORRECT INFORMATION FOR NOTARY AND
 ORIGINAL SIGNATURE PER FS 117.05
 *THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 4) NOTE: PLEASE COMPLETE ELECTRICAL PLANS WITH
 ELECTRICAL AS SHOWN ON REFLECTED CEILING PLANS. PLEASE
 SEE MISSING INFORMATION FOR EXTERIOR LIGHTING, LOAD,
 SIZE AND TYPE OF FIXTURES.
 ONLY SOME SHOWN.
 PLEASE SEE FBC CHAPTER 13, 13-415.2 FOR MAXIMUM
 LIGHTING DENSITIES.
 FBC 106.1.2
  
 5) NOTE: PLEASE INDICATE IN BATHROOMS WITH MULTIPLE
 STALLS AN EMERGENCY BATTERY BACK UP TYPE FIXTURE W/
 BATTERY BACK UP WIRED PER 700.12E.
 LS 101 7.8, 7.9
  
 6) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK
 SEEMS LOW. PLEASE KNOW THE VALUE FOR WORK MUST INCLUDE
 ALL LABOR, MATERIALS AND EQUIPMENT EVEN IF OWNER
 SUPPLIED.
 FBC 108.3
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-09-11 Cont ID  
Sent By mawillia Date 2007-09-11 Time 15:58 Rev Time 0.00
Received By mawillia Date 2007-09-11 Time 15:31 Sent To  
Notes
2007-09-11 15:51:28*****APPROVED*****
  
 THE PREVIOUS FIRE PLAN REVIEW COMMENTS HAVE BEEN
 ADDRESSED;PLAN SHEETS A-1.0, A-3.1, AND E-1.0 WERE
 STAMPED, INITIALED, AND DATED.
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-05-30 Cont ID  
Sent By mawillia Date 2007-05-30 Time 17:19 Rev Time 0.00
Received By mawillia Date 2007-05-30 Time 16:41 Sent To  
Notes
2007-05-30 17:17:34*****DENIED*****
  
  
 1.THE 2003 EDITION OF NFPA 101 SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, AND
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO THE
 SAID PROPERTY OR VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5. THE BUILDING OR PORTIONS OF THE BUILDING WILL BE
 PERMITTED TO BE OCCUPIED DURING THE SCOPE OF WORK ONLY
 WHERE THE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE
 PROTECTION ARE IN PLACE AND MAINTAINED.
  
 6.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 BROADWAY AVENUE,POST THE NUMERICAL ADDRESS.AS PER
 WEST PALM BEACH CODE , THOSE NUMBERS SHALL BE NO LESS
 THAN 6" IN HEIGHT AND NO LESS THAN 1"IN WIDTH.IN
 ADDITION THESE ADDRESS NUMBERS SHALL NOT BE BLOCKED BY
 THE INSTALLATION OF SECURITY BARRICADES AND/OR
 HURRICANE SHUTTERS.
  
 7.PLEASE SHOW THE LOCATION OF EXIT LIGHTS, EMERGENCY
 LIGHTS, AND FIRE EXTINGUISHER(S) FOR THE STRUCTURE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-04 Cont ID  
Sent By adarroug Date 2008-04-04 Time 11:17 Rev Time 0.00
Received By adarroug Date 2008-04-04 Time 11:17 Sent To  
Notes
2008-04-04 11:17:36TO "COMM" BD#42

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-27 Cont ID  
Sent By adarroug Date 2007-07-27 Time 13:16 Rev Time 0.00
Received By adarroug Date 2007-07-27 Time 13:16 Sent To  
Notes
2007-08-07 20:18:36TO COMM BOARD SPACE #51
2007-07-27 13:18:07WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-11 Cont ID  
Sent By jwitmer Date 2007-06-11 Time 17:13 Rev Time 0.00
Received By jwitmer Date 2007-04-03 Time 18:11 Sent To  
Notes
2007-04-04 18:02:32TO COMM BOARD # 14
2007-04-03 18:11:35WAITING FOR COMM BOARD

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-09-08 Cont ID  
Sent By kstevens Date 2007-09-08 Time 15:59 Rev Time 0.00
Received By kstevens Date 2007-09-08 Time 15:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-17 Cont ID  
Sent By kstevens Date 2007-05-17 Time 16:49 Rev Time 0.00
Received By kstevens Date 2007-05-17 Time 16:49 Sent To  
Notes
2007-05-17 17:08:01DENIED
 REFEREINC: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS. THE SEAL OF THE PROFESSIONAL ENGINEER IS
 NOT VALID. THE FLORIDA BOARD OF ENGINEERS MANDATED A
 CHANGE FROM THE "CERTIFICATE" TO "LICENSE" BY FEB. 05,
 2004, THEN AMENDED ITS RULING TO ALLOW A GRACE PERIOD
 UNTILL DEC 31 2005. (SEE ATTACHED SHEET). PLEASE USE
 REQUIRED SEAL.
  
 2. ALL SHEETS. PER 61G15-23.002(1)(2) THE SIGNATURE OF
 THE PROFESSIONAL IS REQUIRED ON EACH SHEET. IT APPEARS
 THAT INITIALS HAVE BEEN USED. IF THIS IS INDEED YOUR
 LEGAL SIGNATURE, PLEASE SUBMIT A SIGNED, SEALED,
 NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE OF THE
 ENGINEER OF RECORD FOR OUR FILES.
  
 3. SHT P-1.0 SANITARY RISER DIAGRAM. THE FITTING
 CONNECTING THE FLOOR DRAIN, (MEN'S ROOM), TO THE BRANCH
 LINE SHALL BE INSTALLED TO GUIDE THE WASTE IN THE
 DIRECTION OF FLOW. SECTION 706.3.
  
 4. SHT ADA-1.0 SHOW COMPLIANCE WITH THE FOLLOWING:
 ___W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 C. 11-4.16.6 DISPENSERS
 ___LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.5 FAUCETS
  
 SHOW THE W/C'S 18" OFF THE WALL TO THE CENTERLINE OF
 THE FIXTURE. FIG. 11-29.
 SHOW THE LAV'S MINIMUM OF 15" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE
 SET OF THEM LOOSELY ON TOP OF THE COLLATED
 PLANS TO BE REVIEWED. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2007-08-13 Cont ID  
Sent By adavila Date 2007-08-13 Time 14:45 Rev Time 0.00
Received By adavila Date 2007-08-10 Time 14:39 Sent To  
Notes
2007-08-13 14:45:50PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. PER SECTION 94-219(D)(9)(A) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS), ALL PROPERTIES SHALL
 BE BROUGHT INTO COMPLIANCE WITH THE LANDSCAPE
 REGULATIONS IN ARTICLE XIV, CONCURRENTLY WITH EXTERIOR
 BUILDING IMPROVEMENTS EXCEEDING $10,000.00.AS THE
 PROPOSED EXTERIOR RENOVATIONS EXCEED $10,000.00, A
 LANDSCAPE PLAN PREPARED, SIGNED AND SEALED BY A
 REGISTERED LANDSCAPE ARCHITECT, AND MEETING THE
 LANDSCAPE PROVISIONS SET OUT IN ARTICLE XIV OF THE
 ZLDRS, SHALL BE PROVIDED.
 A. PLEASE PROVIDE A DATA TABLE STATING THE REQUIRED AND
 PROVIDED LANDSCAPE.
 B. PROVIDE TREE PLANTING PLAN DETAILS MEETING THE
 CITY?S ZLDRS.PLEASE SEE THE ATTACHED DIAGRAM FOR
 REFERENCE.
 C. PURSUANT TO SECTION 94-219(D)(9)(B), ALL EXISTING
 SURFACE PARKING LOTS SHALL BE LANDSCAPED WITH A 36-INCH
 HIGH PERIMETER HEDGE AND SHADE TREES AT EVERY THIRD
 PARKING SPACE.SHRUBS SHALL BE PLANTED AT TWO-FOOT
 INTERVALS.
 D. PURSUANT TO SECTION 94-443(A) OF THE ZLDRS, THE
 OWNER OF THE PROPERTY LOCATED ADJACENT TO A RESIDENTIAL
 ZONING DISTRICT SHALL INSTALL AND MAINTAIN ALONG THE
 ENTIRE PROPERTY LINE A LANDSCAPE BUFFER.LANDSCAPE
 BUFFER SHALL BE A MINIMUM OF FIVE (5) FEET IN WIDTH AT
 MATURITY.AT LEAST ONE SHADE OR FLOWERING TREE SHALL
 BE PLANTED FOR EACH 30 LINEAR FEET OR PORTION THEREOF.
 E. PURSUANT TO SECTION 94-443(B), THE OWNER OF THE
 PROPERTY SHALL INSTALL AND MAINTAIN A LANDSCAPE BUFFER
 STRIP ALONG THE ENTIRE EDGE OF THE PROPERTY ADJACENT TO
 A PUBLIC THOROUGHFARE AND OTHER NONRESIDENTIAL ZONING
 DISTRICTS. THE BUFFER STRIP SHALL BE AT LEAST FIVE (5)
 FEET WIDE.AT LEAST ONE SHADE OR FLOWERING TREE SHALL
 BE PLANTED FOR EACH 30 LINEAR FEET OR PORTION THEREOF.
 THE BUFFER STRIP MAY NOT BE INTERRUPTED BY MORE THAN
 25% OF ITS REQUIRED LENGTH TO PROVIDE FOR SIGNS OR
 VEHICULAR INGRESS AND EGRESS.
 F. PURSUANT TO SECTION 94-443(C)(2), VEHICULAR USE
 AREAS SHALL BE SCREENED FROM THOROUGHFARES AND
 RESIDENTIAL USES AND DISTRICTS BY A LANDSCAPE BUFFER OF
 AT LEAST FIVE (5) FEET IN WIDTH.
 G. PURSUANT TO SECTION 94-443(C)(5)(A), LANDSCAPE AREAS
 SHALL BE SEPARATED FROM VEHICULAR USE AREAS BY
 NONMOUNTABLE, CONCRETE CURBING OF THE TYPE CATEGORIZED
 AS ?TYPE D.?LABEL THE TYPE OF CURB WHEREVER
 APPLICABLE.
 H. PLEASE CONTACT THE PLANNER REVIEWER TO DISCUSS
 LANDSCAPE OPTIONS.
  
 3. PER SECTION 94-221(D)(10) OF THE ZLDRS, FLAT ROOFS
 SHALL BE ENCLOSED BY A PARAPET NO LESS THAN 42 INCHES
 IN HEIGHT.
  
 4. (REPEAT COMMENT) IDENTIFY/LABEL OBJECTS ON TOP OF
 THE ROOF ON SHEET A-3.0.
 A. THERE ARE 3 OBJECTS PROJECTING OVER THE ROOF THAT
 ARE NOT IDENTIFIED.SHEET D-2.0 REFERS TO 2 OBJECTS
 IDENTIFIED AS ?LIGHTS TO BE REUSED.?IF THESE LIGHTS
 ARE 2 OF THE 3 OBJECTS SHOWN ON THE PROPOSED
 ELEVATIONS, THAN THEY SHOULD BE LABELED AS SUCH.IF
 NOT, PLEASE CLARIFY WHAT THE OBJECTS ARE AND HOW THE
 LIGHTS WILL BE REUSED.THE THIRD OBJECT IS AT THE WEST
 CORNER OF THE ROOF ON THE NORTH ELEVATION.
 B. IF THE OBJECTS ARE LIGHTING FIXTURES, PROVIDE A
 PHOTOMETRIC PLAN SHOWING LIGHTING DETAILS.PLEASE NOTE
 THAT GLARE MAY NOT EXCEED 0.5 FOOT CANDLE AT OR BEYOND
 THE EAST BOUNDARY, AND 1 FOOT CANDLE AT OR BEYOND THE
 NORTH AND WEST BOUNDARIES.
  
 5. THERE SHALL BE 12 INCHES BETWEEN THE DOUBLE STRIPING
 OF THE PARKING STALLS.PLEASE REFER TO THE ATTACHED
 DIAGRAM FOR REFERENCE.
  
 6. (REPEAT COMMENT) WHEEL STOPS SHALL BE 2 FEET FROM
 THE CURB TO THE BACK OF THE WHEEL STOP.THE DETAILS
 PROVIDED IN SHEET C-1 SHOWS 2 FEET FROM THE CURB TO THE
 FRONT OF THE WHEEL STOP.
  
 7. HANDICAP SYMBOL SHALL BE 2 FEET FROM THE OPEN END OF
 THE PARKING SPACE, AND SHALL BE 3 FEET OR 5 FEET IN
 HEIGHT.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-10 Cont ID  
Sent By adavila Date 2007-04-10 Time 14:05 Rev Time 0.00
Received By adavila Date 2007-04-09 Time 12:15 Sent To  
Notes
2007-04-10 14:06:31PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. PROVIDE TWO (2) SIGNED AND SEALED SURVEYS.SURVEY
 SHALL BE LESS THAN A YEAR OLD.
  
 3. PLEASE PROVIDE TOTAL VALUE OF EXTERIOR RENOVATIONS.
  
 4. A DIFFERENT PERMIT SHALL BE SUBMITTED FOR ALL NEW
 SIGNS.
 A. PLEASE NOTE THAT PER SECTION 94-221(E)(1) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS, THE SIGN AREA
 SHALL NOT EXCEED 36 INCHES IN HEIGHT BY 60 PERCENT OF
 THE WIDTH OF EACH SIDE OF THE BUILDING.
 B. PLEASE NOTE THAT PER SECTION 94-221(E)(2) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS, A SIGN BAND
 LOCATED ON THE REAR OF THE BUILDING AND FACING A
 RESIDENTIAL ZONING DISTRICT SHALL NOT EXCEED ONE AND
 ONE HALF (1.5) FEET IN VERTICAL DISTANCE BY 30 PERCENT
 OF THE WIDTH OF THE FA?ADE.
 C. PLEASE INDICATE ON THE ELEVATIONS THAT ALL SIGNS
 WILL NOT BE PART OF THIS PERMIT APPLICATION.
  
 5. EXISTING CURB CUT ALONG THE WEST PROPERTY LINE SHALL
 BE SHOWN ON BOTH COPIES OF SITE PLAN.
  
 6. PROVIDE CLEAR GLAZING CALCULATIONS, EXISTING VS.
 PROPOSED, BETWEEN TWO (2) AND EIGHT (8) FEET ABOVE THE
 GROUND ALONG ALL FRONTAGE LINES.
 A. PLEASE NOTE THAT THE PERCENTAGE OF CLEAR GLAZING MAY
 NOT BE REDUCED FROM WHAT EXISTS.
  
 7. PER SECTION 94-221(D)(7)(B) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, AWNINGS AT THE SIDEWALK LEVEL
 SHALL NOT HAVE A BOTTOM SOFFIT OR SIDE PANELS.
  
 8. PROVIDE DEPTH DIMENSIONS FROM WALL TO END OF
 AWNING.
  
 A. PLEASE NOTE THAT PER SECTION 94-221(D)(7)(C) OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS, AWNINGS AT THE
 SIDEWALK LEVEL SHALL PROJECT A MINIMUM OF FOUR FEET
 FROM THE BUILDING FA?ADE.
  
 9. PROVIDE OVERALL HEIGHT OF NEW PARAPET.
  
 10. IDENTIFY/LABEL OBJECTS ON TOP OF THE ROOF ON SHEET
 A-3.0.
  
 11. PLEASE PROVIDE THE INTENT OF PROVIDING "EIFS SCORED
 8"" EACH WAY AT THE BOTTOM OF THE BUILDING.
  
 12. PURSUANT TO SECTION 94-485(G) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS, TRAFFIC CONTROL SIGNS AND
 PAVEMENT MARKINGS SHALL BE USED AS NECESSARY TO ENSURE
 SAFE AND EFFICIENT TRAFFIC OPERATIONS WITHIN ALL
 PARKING AND LOADING AREAS.AN ?ENTRY ONLY? SIGN SHALL
 BE PLACED ON THE ENTRANCE ON THE WEST SIDE OF THE
 PROPERTY.
  
 13. PURSUANT TO SECTION 94-485(G) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS, REQUIRED OFF-STREET
 PARKING SPACES SHALL BE DELINEATED BY FOUR INCH WHITE
 DOUBLE STRIPED LINES.
  
 14. PURSUANT TO FIGURE XIV-2 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, WHEEL STOPS SHALL BE TWO (2)
 FEET FROM THE END OF THE CURB TO THE BACK OF THE WHEEL
 STOP.
  
 15. PURSUANT TO SECTION 94-443(C)(5)(B) OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, ONLY ONE WHEEL STOP
 MAY BE USED FOR ONE PARKING STALL.SECOND WHEEL STOP
 ON THE HANDICAPPED PARKING SPACE SHALL BE REMOVED.
  
 16. EXISTING TREE STUMPS SHALL BE REMOVED AND REPLACED
 BY TREES.
  
 17. MISSING HEDGES ALONG THE SOUTH PROPERTY LINE, AT
 THE EAST END, SHALL BE REPLACED.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.