Plan Review Details - Permit 07040066
Plan Review Stops For Permit 07040066
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-28 Cont ID  
Sent By amorse Date 2007-04-28 Time 14:05 Rev Time 0.00
Received By amorse Date 2007-04-28 Time 14:05 Sent To PC
Notes
2007-04-28 14:03:51 
  
 DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MOREINFORMATION.
  
 2)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES (DUE $ 5.42)
  
 3)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF
 THE FLORIDA STATUTES SHALL AFFIX THEIR OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS AND SPECIFICATIONS
 PER 106.1 FBC 2004
  
 4)PHOTO COPIED, STAMPED OR REPRODUCED
 SIGNATURES ARE NOT ACCEPTABLE PER
 471.025 F.S.
  
 5)WORK ON EXISTING BUILDINGS IS COVERED UNDER THE FBC
 (EXISTING) AS SUCH A DESIGN PROFESSIONAL OR OWNERMUST
 ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION PER
 301.5 FBC (EXISTING)
  
 6)PROVIDE 2 COPIES OF RECENT SURVEY THAT SHOWS THE
 PROPOSED ADDITION AND ALL SETBACKS
  
 7)PROVIDE ROOF PITCH ON DRAWINGS
  
 8)PROVIDE ATTIC ACCESS PER R807 AND SHOW COMPLIANCE
 WITH ROOF VENTILATION PER R806
  
 9)PROVIDE LEGEND/SCHEDULE FOR DOOR AND WINDOWS ON A.8
 STATING TYPE OF UNIT. PRODUCT APPROVALS CONTAIN 3 TYPES
 ? IF HALF CIRCLE ARE NOT INTEGRAL TO THE WINDOW PRODUCT
 APPROVALS ARE REQUIRED FOR MULLIONS
  
 10)SUBMIT PRODUCT APPROVALS FOR ROOF TILE
  
 11)FIRST FLOOR FOUNDATION PLAN SHOWS SAME DETAIL #
 FOR F2 AND F3 FOUNDATIONS (3/S.2)
  
 12)SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 13)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
  
 14)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD INCLUDE THE FLORIDA
 STATE APPROVAL COVER PAGES, AND THE PRODUCT NOA THAT
 LISTS THE SYSTEM COMPONENTS/ FASTENER LIST PAGES, THE
 PAGES WITH THE CHOSEN ASSEMBLY/ SYSTEM TO BE USED AND
 THE GENERAL LIMITATIONS PAGE. ALL CAN BE FOUND ON
 WWW.FLORIDABUILDING.ORG
  
 15)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 16)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 17)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 18)LICENCES FOR DESIGN PROFESSIONALS ARE EITHER
 DELINQUENT OR NULL & VOID AT DBPR PLEASE RECTIFY BEFORE
 RESUBMITAL
  
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-19 Cont ID  
Sent By btrobaug Date 2007-04-19 Time 07:32 Rev Time 1.00
Received By btrobaug Date 2007-04-19 Time 06:40 Sent To M
Notes
2007-04-19 07:32:50 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON
 THE PLANS, MUST SIGN AND SEAL THE PLAN PER
 481.221(1)(B)FS. ONLY 1 SET SEALED.
  
 2} THE AREA OF THE KITCHEN THAT IS BEING EXTENDED MUST
 INCLUDE SMALL APPLIANCE CIRCUITS, PLEASE SEE
 210.52(B)(ALL) FOR REQUIREMENTS. PLACE SAME ON PLANS.
  
 3} THE NOTE ON SHEET E.1 DOES NOT ADDRESS CIRCUITING
 FOR THE NEW BATHROOM. SINCE NO PANEL SCHEDULE HAS BEEN
 PROVIDED, PLEASE INCLUDE VERBAGE FROM 210.11(C)(3) IN
 THE NOTE, ALSO 210.52(B), CLEAR ENOUGH TO CONVEY THOSE
 REQUIREMENTS TO THE CONTRACTOR.
  
 4} IF THERE IS WORK TO BE DONE IN THE PANTRY, IT MUST
 COMPLY WITH 210.52(B). INDICATE ADDED DEVICES.
  
 5} THE DISCONNECTING MEANS /RECEPTACLE FOR THE
 WASHER/DRYER IS NOT SHOWN.
  
 6} SHEET E.2 IS INCORRECTLY LABLED"1ST FLOOR
 LIGHTING".
  
 7} INDICATE IF THE PANEL SHOWN IN THE PANTRY IS BEING
 ADDED. IF SO PROVIDE A RISER DIAGRAM OF THE SERVICE.
  
 NOTE:PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL
 BE BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 13:45 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 13:45 Sent To E
Notes
2007-04-16 13:45:45TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-04-28 Time   Rev Time 0.00
Received By spalmer Date 2007-04-03 Time 18:21 Sent To  
Notes
2007-04-03 18:21:36TO ZONING

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-19 Cont ID  
Sent By tgordon Date 2007-04-19 Time 11:56 Rev Time 1.00
Received By tgordon Date 2007-04-19 Time 11:56 Sent To E
Notes
2007-04-19 12:12:54*** DENIED ***
 1) MECHANICAL PERMIT #07040071 HAS BEEN APPLIED FOR BUT
 NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE
 SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC CITY
 OF WPB AMEND. 106.3.5.4 (10). SHOW ON MECHANICAL PLANS
 ALL NEW DUCT WORK TO BE INSTALLED, BATHROOM EXHAUST
 FANS, CLOTH DRYER VENT AND NOTE WERE IT WILL TERMINATE
 AT, AND ANY GAS APPLIANCES, ETC.
  
 2) PLEASE SUBMIT ENERGY CALCULATIONS FORM 600C-04R
 (SHORT FORM), PER 2004 FBC 13-600.3.C (12-8-06
 REVISION)
  
 3) PLEASE SUBMIT TWO SIGNED AND SEALED SETS OF PLANS,
 AS ONE SET SUBMITTED IS A PHOTO-COPY OF A SIGNATURE AND
 NOT SEALED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-25 Cont ID  
Sent By jleech Date 2007-04-25 Time 09:22 Rev Time 0.00
Received By jleech Date 2007-04-25 Time 09:10 Sent To B
Notes
2007-04-25 09:26:06DENIED;
 ONLY ONE SET OF DRAWINGS SEALED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-13 Cont ID  
Sent By adavila Date 2007-04-13 Time 11:49 Rev Time 0.00
Received By adavila Date 2007-04-09 Time 17:03 Sent To I
Notes
2007-04-13 11:50:11PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE SIDE SETBACK DIMENSIONS FROM PROPERTY LINE
 TO PROPOSED ADDITION.
  
 2. PROVIDE EITHER REAR SETBACK DIMENSIONS FROM PROPERTY
 LINE TO PROPOSED ADDITION OR DIMENSIONS OF STRUCTURE ON
 BOTH COPIES OF SITE PLAN.
  
 3. PROVIDE SETBACK DIMENSIONS FROM EXISTING ACCESSORY
 STRUCTURE TO PROPOSED ADDITION.
  
 4. PROVIDE BUILDING HEIGHT DIMENSIONS FROM GRADE TO THE
 HIGHEST POINT OF THE ROOF.
  
 5. PROVIDE BUILDING HEIGHT DIMENSIONS FROM GRADE TO THE
 MIDPOINT BETWEEN THE ROOF RIDGE AND EVE OF THE PROPOSED
 ADDITION.
  
 6. PER THE HISTORIC PRESERVATION DIVISION, EXISTING
 WINDOWS SHALL REMAIN ALONG THE NORTH FA?ADE,
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.