Plan Review Details - Permit 07040043
Plan Review Stops For Permit 07040043
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-07-11 Cont ID  
Sent By amorse Date 2007-07-11 Time 16:26 Rev Time 0.00
Received By amorse Date 2007-07-11 Time 16:26 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-16 Cont ID  
Sent By amorse Date 2007-06-16 Time 11:42 Rev Time 0.00
Received By amorse Date 2007-06-16 Time 11:42 Sent To PC
Notes
2007-06-16 11:46:38 
  
 DENIED
  
 THE FOLLOWING COMMENTS FROM THE FIRST REVIEW WERE NOT
 COMPLETED
  
  
 3)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF
 THE FLORIDA STATUTES SHALL AFFIX THEIR OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS AND SPECIFICATIONS
 PER 106.1 FBC 2004. THE EXEMPTION FROM LICENSURE UNDER
 481.229 FS DOES NOT EXEMPT THE DESIGNER RESPONSIBLE FOR
 THE DRAWINGS FROM SIGNING AND DATING SAID DRAWINGS.
 ***** PRINT,SIGN AND DATE ALL COPIES INCLUDING THE
 PLUMBING, MECHANICAL AND ELECTRICAL PAGES*****
  
 8)IN AREAS OF QUESTIONABLE SOILS AS SHOWN IN THE
 OFFICIAL ZONING MAP OF THE CITY OF WEST PALM BEACH, 2
 COPIES OF A SOIL TEST REPORT SHALL BE SUBMITTED PER
 R401.4 FBC RES. ***** REQUIRES 2 SIGNED AND SEALED
 COPIES*****
  
 15)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD INCLUDE THE FLORIDA
 STATE APPROVAL COVER PAGES, AND THE PRODUCT NOA THAT
 LISTS THE SYSTEM COMPONENTS/ FASTENER LIST PAGES, THE
 PAGES WITH THE CHOSEN ASSEMBLY/ SYSTEM TO BE USED AND
 THE GENERAL LIMITATIONS PAGE. ALL CAN BE FOUND ON
 WWW.FLORIDABUILDING.ORG. ****PROVIDE PRODUCT APPROVALS
 FOR THE CASTCRETE LINTELS AND THE TS22 SIMPSON TIES
 USED ON THE VALLEY TRUSS SET*****
  
 16)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
 *****NO STATE OF FLORIDA PRODUCT APPROVALS WERE
 SUBMITTED, SEE APPROVAL NUMBERS AT THE TOP OF THE
 MIAMI-DADE NOA'S*****
  
 NEW REVIEW COMMENT
  
 1)PROVIDE LINTEL SCHEDULE THAT COMPLIES
 WITH 2104.1.5 FBC
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-28 Cont ID  
Sent By amorse Date 2007-04-28 Time 10:48 Rev Time 0.00
Received By amorse Date 2007-04-28 Time 10:48 Sent To PC
Notes
2007-04-28 10:46:18 
  
 DENIED
  
 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC* VALUE HAS BEEN INCREASED AND FEES ARE
 DUE THESE MUST BE PAID PRIOR TO FURTHER REVIEW
  
 2)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MOREINFORMATION.
  
 3)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF
 THE FLORIDA STATUTES SHALL AFFIX THEIR OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS AND SPECIFICATIONS
 PER 106.1 FBC 2004. THE EXEMPTION FROM LICENSURE UNDER
 481.229 FS DOES NOT EXEMPT THE DESIGNER RESPONSIBLE FOR
 THE DRAWINGS FROM SIGNING AND DATING SAID DRAWINGS.
  
 4)WORK ON EXISTING BUILDINGS IS COVERED UNDER THE FBC
 (EXISTING) AS SUCH A DESIGN PROFESSIONAL OR OWNERMUST
 ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION PER
 301.5 FBC (EXISTING)
  
 5)PROVIDE 2 COPIES OF SURVEY THAT SHOW THE PROPOSED
 ADDITION WITH SETBACK FROM PROPERTY LINES INDICATED
  
 6)PROVIDE A SITE PLAN THAT SHOWS CORRECT MEASUREMENTS
 THAT MATCH SURVEY.
  
 7)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES.
 SHOWDRAINAGE FROM BUILDINGAND AWAY FROM ADJOINING
 PROPERTIES
  
 8)IN AREAS OF QUESTIONABLE SOILS AS SHOWN IN THE
 OFFICIAL ZONING MAP OF THE CITY OF WEST PALM BEACH, 2
 COPIES OF A SOIL TEST REPORT SHALL BE SUBMITTED PER
 R401.4 FBC RES.
  
 9)PROVIDE BEAM/LINTEL DETAIL. TOB = 8'-0" DOOR IS
 6'-8" IN ORDER TO FIT 8" BOND BEAM AND 8" LINTEL DOOR
 WILL NOT FIT. IF POURED DROP DOWN BEAM IS USED SHOW
 DETAIL. ALSO WILL BE REQUIRED FOR WINDOWS IF SAME
 ELEVATION IS USED.
  
 10)DRAWING DOES NOT SHOWACCESSIBLE BATHROOM THAT
 COMPLIES WITH R322.1.1 FBC RES. W/C DOOR SIZE NOT
 PROVIDED.
  
 11)IDENTIFY SAFETY GLAZING FOR SHOWER DOOR THAT MEETS
 PROVISIONS OF R308.4 FBC RES.
  
 12)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS
 REQUIRED PER R807.1 FBC RES.
  
 13)SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
  
 14)PROVIDE ENGINEERED SUBSTRATE ATTACHMENT FOR WOOD
 BUCKS PER 1714.5.4.1 FBC
  
 15)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD INCLUDE THE FLORIDA
 STATE APPROVAL COVER PAGES, AND THE PRODUCT NOA THAT
 LISTS THE SYSTEM COMPONENTS/ FASTENER LIST PAGES, THE
 PAGES WITH THE CHOSEN ASSEMBLY/ SYSTEM TO BE USED AND
 THE GENERAL LIMITATIONS PAGE. ALL CAN BE FOUND ON
 WWW.FLORIDABUILDING.ORG
  
 16)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 17)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
  
 18)PLEASE PROVIDE (2) COPIES OF THE PRODUCT APPROVALS
 THAT PERTAIN TO BUILDING (NO FIXED WINDOWS ARE SHOWN ON
 THE DRAWINGS)
  
 19)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-07-05 Cont ID  
Sent By btrobaug Date 2007-07-05 Time 06:38 Rev Time 0.00
Received By btrobaug Date 2007-07-05 Time 06:15 Sent To P
Notes
2007-07-05 06:26:58 
 PROVISO
 R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED IN
 NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-05-30 Cont ID  
Sent By btrobaug Date 2007-05-30 Time 16:51 Rev Time 0.50
Received By btrobaug Date 2007-05-30 Time 16:29 Sent To M
Notes
2007-05-30 16:51:18 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
  
 2} THE BATH CIRCUIT MAY NOT FEED OTHER RECEPTACLES .
 210.11.(C)(3).
  
 3} THE REFERENCED CODES ARE INCORRECT. NFPA-72 IS 2002
 EDITION, 101 IS 2003 EDITION. SEE REFERENCED MATERIAL
 IN THE 2004 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-12 Cont ID  
Sent By btrobaug Date 2007-04-12 Time 14:45 Rev Time 1.00
Received By btrobaug Date 2007-04-12 Time 13:49 Sent To P
Notes
2007-04-12 14:06:07 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 2} 240.24(D) OVERCURRENT DEVICES SHALL NOT BE LOCATED
 IN THE VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS
 IN CLOTHES CLOSETS.PANEL "A" CANNOT BE LOCATED IN THE
 CLOSET. ALSO SEE 408.17 LOCATION RELATIVE TO EASILY
 IGNITIBLE MATERIAL.
  
 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), SEE CIRCUIT #2 AT 15 AMPS.
  
 4} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE. ALL 120-VOLT, SINGLE
 PHASE, 15- AND 20-AMPERE BRANCH CIRCUITS SUPPLYING
 OUTLETS INSTALLED IN DWELLING UNIT BEDROOMS SHALL BE
 PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER,
 COMBINATION TYPE INSTALLED TO PROVIDE PROTECTION OF THE
 BRANCH CIRCUIT.
  
 5} ALL 120-VOLT, SINGLE PHASE, 15- AND 20-AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT
 BEDROOMS SHALL BE PROTECTED BY A LISTED ARC-FAULT
 CIRCUIT INTERRUPTER, COMBINATION TYPE INSTALLED TO
 PROVIDE PROTECTION OF THE BRANCH CIRCUIT. INDICATE SAME
 IN PANEL SCHEDULE.
 BRANCH/FEEDER AFCIS SHALL BE PERMITTED TO BE USED TO
 MEET THE REQUIREMENTS OF 210.12(B) UNTIL JANUARY 1,
 2008.
  
 6} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-11-28 Cont ID  
Sent By adarroug Date 2007-11-28 Time 16:19 Rev Time 0.00
Received By adarroug Date 2007-11-28 Time 16:19 Sent To M
Notes
2007-11-28 16:19:47TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-10-17 Cont ID  
Sent By adarroug Date 2007-10-17 Time 16:39 Rev Time 0.00
Received By adarroug Date 2007-10-17 Time 16:39 Sent To M
Notes
2007-10-17 16:40:12TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-07-02 Cont ID  
Sent By adarroug Date 2007-07-02 Time 15:47 Rev Time 0.00
Received By adarroug Date 2007-07-02 Time 15:47 Sent To E
Notes
2007-07-02 15:48:13TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-25 Cont ID  
Sent By adarroug Date 2007-05-25 Time 16:54 Rev Time 0.00
Received By adarroug Date 2007-05-25 Time 16:54 Sent To E
Notes
2007-05-25 16:54:48TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-23 Cont ID  
Sent By adarroug Date 2007-05-23 Time 08:49 Rev Time 0.00
Received By adarroug Date 2007-05-23 Time 08:49 Sent To Z
Notes
2007-05-23 08:49:51TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-10 Cont ID  
Sent By adarroug Date 2007-04-10 Time 10:24 Rev Time 0.00
Received By adarroug Date 2007-04-10 Time 10:24 Sent To E
Notes
2007-04-10 10:25:22TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-04-28 Time   Rev Time 0.00
Received By spalmer Date 2007-04-03 Time 17:21 Sent To Z
Notes
2007-04-03 17:21:33TO ZONING

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-12-04 Cont ID  
Sent By tgordon Date 2007-12-04 Time 11:14 Rev Time 0.30
Received By tgordon Date 2007-12-04 Time 11:14 Sent To  
Notes
2007-12-04 11:15:27REVISION TO MECH. PLAN, SHEET MP-1.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-10-23 Cont ID  
Sent By tgordon Date 2007-10-23 Time 08:40 Rev Time 0.30
Received By tgordon Date 2007-10-23 Time 08:40 Sent To  
Notes
2007-10-23 08:59:42PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) MECHANICAL PLAN NEEDS TO BE SIGNED AND SEALED BY THE
 ENGINEER ON RECORD (EVERETT C. FENNELL) SEE FAC
 61G15-23.002.
  
 2) CONDENSER UNIT MODEL NUMBER SHOWING IN THE EQUIPMENT
 NOTES IS FOR A 4 TON CONDENSER UNIT PLANS STATE ONLY A
 1.5 TON SYSTEM IS TO BE INSTALLED, PLEASE CORRECT, SEE
 FBC 13-607.1.ABC.1.1.
  
 3) AIR HANDLER UNIT MODEL NUMBER SHOWING IN THE
 EQUIPMENT NOTES CAN NOT BE FOUND ON THE ARI DIRECTORY
 WEB SITE, PLEASE CORRECT MODEL NUMBER AND SUBMIT THE
 ARI REFERENCE NUMBER FOR THE A/C SYSTEM, SEE FBC
 13-607.1.ABC.3.1.1.
  
 4) SANITARY RISER S/1 ON SHEET MP-1 HAD BEEN RED LINED
 BY PLUMBING REVIEWER LAST TIME BUT REVISED PLANS MUST
 SHOW THESE CORRECTIONS WHEN BEING REVISED, PLEASE
 CORRECT, SEE FBC 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-07-09 Cont ID  
Sent By tgordon Date 2007-07-09 Time 11:02 Rev Time 0.30
Received By tgordon Date 2007-07-09 Time 11:02 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-05-31 Cont ID  
Sent By tgordon Date 2007-05-31 Time 09:05 Rev Time 0.30
Received By tgordon Date 2007-05-31 Time 09:05 Sent To P
Notes
2007-05-31 09:19:48*** DENIED ***
 1) PROVIDE RETURN AIR TO MASTER SUITE, SEE 2004 FBC/R
 M1602.4.
  
 2) THE 12X6" RETURN AIR GRILL APPEARS TO BE TOO SMALL
 FOR A 1.5 TON A/C SYSTEM PLEASE ENLARGE, OR YOU MAY
 SUBMIT MANUFACTURER'S SPECIFICATION'S SHOWING THE
 PRESSURE LOSS FOR THE RETURN AIR GRILL AND MANUAL D
 CALCULATIONS FOR RESIDENTIAL DUCT DESIGN, SEE 2004
 FBC/R M1601.1.
  
 *** 2004 FBC/R M1602.4 BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-11 Cont ID  
Sent By tgordon Date 2007-04-11 Time 14:19 Rev Time 0.45
Received By tgordon Date 2007-04-11 Time 14:19 Sent To E
Notes
2007-04-11 14:58:47*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, PER
 2004 FBC 13-600.3.A, (12-8-06 REVISION).
  
 2) REVISED ENERGY CALCULATIONS WILL NEED TO BE SIGNED
 BY OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) THE MINIMUM SEER FOR A/C UNITS IS NOW 13 SEER, SEE
 2004 FBC 13-607.1.ABC.3.2.1, PLEASE CORRECT.
  
 4) SEE ENERGY CAL'S LINE 6 IS SHOWING 890 CONDITIONED
 FLOOR AREA, PLANS SHOW ONLY 631 SQUARE FEET, PLEASE
 CORRECT.
  
 5) SEE MECHANICAL PLANS PAGE MP-1, PLEASE PROVIDE FOR
 RETURN AIR BACK TO THE AIR HANDLER UNIT, PLEASE BE
 ADVISED RETURN AIR MAY NOT COME FROM THE BATHROOM, SEE
 2004 FBC/R M1602.2 (4).
  
 6) PLEASE SHOW THE SIZE OF ALL SUPPLY AIR GRILL ON
 MECHANICAL PLANS.
  
 7) MECHANICAL PLANS SHOW A 10 SEER A/C SYSTEM, SEE NOTE
 #3 AND PLEASE CORRECT.
  
 8) PLEASE SEE MECHANICAL PLANS YELLOW HIGH LIGHTED
 SUPPLY AIR DUCTS (FLEX ?) NEED TO SHOW THE SIZE OF THE
 DUCTS.
  
 9) THE PLANS NEED TO BE SIGNED AND SEALED BY THE
 ENGINEER EVERETT C. FENNELL AS HIS INFORMATION IS IN
 THE TITLE BLOCK.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-07-09 Cont ID  
Sent By jleech Date 2007-07-09 Time 10:12 Rev Time 0.00
Received By jleech Date 2007-07-09 Time 10:09 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-06-14 Cont ID  
Sent By jleech Date 2007-06-14 Time 10:17 Rev Time 0.00
Received By jleech Date 2007-06-14 Time 10:09 Sent To B
Notes
2007-06-14 10:29:50DENIED;
 1. SANITARY RISER DIAGRAM FOR AUTOMATIC CLOTHES WASHER
 SHOULD BE 3" THE WASHER AND LAUNDRY TUB CAN BE ON SAME
 STACK. ACLEANOUT IS REQUIRED AT 48" ABOVE FINISH FLOOR.
 SEE FBC-2004 PLUMBING SECTION 406.3. (ONE SET OF PLANS
 MARKED IN RED)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-24 Cont ID  
Sent By jleech Date 2007-04-24 Time 09:56 Rev Time 0.00
Received By jleech Date 2007-04-24 Time 09:51 Sent To B
Notes
2007-04-24 10:02:48DENIED;
 A SANITARY RISER DIAGRAM IS REQUIRED SHOWING ALL
 PLUMBING FIXTURES TO BE INSTALLED IN THE NEW ADDITION.
 SIZE ALL PIPES AND SHOW VENT LOCATIONS AND ALL
 CLEANOUTS REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2007-05-23 Cont ID  
Sent By jroach Date 2007-05-23 Time 14:06 Rev Time 0.00
Received By jroach Date 2007-05-23 Time 14:06 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-09 Cont ID  
Sent By jroach Date 2007-04-09 Time 20:26 Rev Time 0.00
Received By jroach Date 2007-04-09 Time 20:26 Sent To I
Notes
2007-04-09 20:31:37***FAILED***
  
 1) PROPOSED ADDITION SHALL BE SHOWN ON TWO (2) COPIES
 OF THE SURVEY AND SHALL INDICATE THE DISTANCE FROM THE
 PROPOSED ADDITION TO ALL PROPERTY LINES.
  
 2) SITE PLAN DIMENSIONS DO NO NECESSARILY CORRESPOND
 WITH WHAT IS SHOWN ON THE SURVEY...ENSURE THAT ALL
 PLANS ARE CONSISTENT.
  
 3) BUILDING HEIGHT SHALL BE PROVIDED ON THE ELEVATIONS
 AS MEASURED FROM GRADE TO THE MEAN POINT OF THE ROOF
 PITCH.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.