| Plan Review Stops For Permit 07040043 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-07-11 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2007-07-11 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2007-07-11 |
Time |
16:26 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-06-16 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2007-06-16 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2007-06-16 |
Time |
11:42 |
Sent To |
PC |
|
| Notes |
| 2007-06-16 11:46:38 | | | | | | | DENIED | | | | | | THE FOLLOWING COMMENTS FROM THE FIRST REVIEW WERE NOT | | | COMPLETED | | | | | | | | | 3)A DESIGN PROFESSIONAL THAT IS REGISTERED TO | | | PRACTICE UNDER CHAPTER 481 OR 471 OF | | | THE FLORIDA STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, | | | SIGNATURE AND DATE TO SAID DRAWINGS AND SPECIFICATIONS | | | PER 106.1 FBC 2004. THE EXEMPTION FROM LICENSURE UNDER | | | 481.229 FS DOES NOT EXEMPT THE DESIGNER RESPONSIBLE FOR | | | THE DRAWINGS FROM SIGNING AND DATING SAID DRAWINGS. | | | ***** PRINT,SIGN AND DATE ALL COPIES INCLUDING THE | | | PLUMBING, MECHANICAL AND ELECTRICAL PAGES***** | | | | | | 8)IN AREAS OF QUESTIONABLE SOILS AS SHOWN IN THE | | | OFFICIAL ZONING MAP OF THE CITY OF WEST PALM BEACH, 2 | | | COPIES OF A SOIL TEST REPORT SHALL BE SUBMITTED PER | | | R401.4 FBC RES. ***** REQUIRES 2 SIGNED AND SEALED | | | COPIES***** | | | | | | 15)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF | | | EACH PRODUCT APPROVAL THAT | | | IS RELEVANT PER 9B-72. THESE SHOULD INCLUDE THE FLORIDA | | | STATE APPROVAL COVER PAGES, AND THE PRODUCT NOA THAT | | | LISTS THE SYSTEM COMPONENTS/ FASTENER LIST PAGES, THE | | | PAGES WITH THE CHOSEN ASSEMBLY/ SYSTEM TO BE USED AND | | | THE GENERAL LIMITATIONS PAGE. ALL CAN BE FOUND ON | | | WWW.FLORIDABUILDING.ORG. ****PROVIDE PRODUCT APPROVALS | | | FOR THE CASTCRETE LINTELS AND THE TS22 SIMPSON TIES | | | USED ON THE VALLEY TRUSS SET***** | | | | | | 16)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA | | | STATE PRODUCT APPROVAL COVER | | | SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON | | | WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT | | | SUBMITTED APPLICATIONS WILL BE DENIED | | | *****NO STATE OF FLORIDA PRODUCT APPROVALS WERE | | | SUBMITTED, SEE APPROVAL NUMBERS AT THE TOP OF THE | | | MIAMI-DADE NOA'S***** | | | | | | NEW REVIEW COMMENT | | | | | | 1)PROVIDE LINTEL SCHEDULE THAT COMPLIES | | | WITH 2104.1.5 FBC | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-04-28 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2007-04-28 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
amorse |
Date |
2007-04-28 |
Time |
10:48 |
Sent To |
PC |
|
| Notes |
| 2007-04-28 10:46:18 | | | | | | | DENIED | | | | | | 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST | | | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC | | | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES | | | PER 108.3 FBC* VALUE HAS BEEN INCREASED AND FEES ARE | | | DUE THESE MUST BE PAID PRIOR TO FURTHER REVIEW | | | | | | 2)BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SETS OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561) 233-5025 FOR MOREINFORMATION. | | | | | | 3)A DESIGN PROFESSIONAL THAT IS REGISTERED TO | | | PRACTICE UNDER CHAPTER 481 OR 471 OF | | | THE FLORIDA STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, | | | SIGNATURE AND DATE TO SAID DRAWINGS AND SPECIFICATIONS | | | PER 106.1 FBC 2004. THE EXEMPTION FROM LICENSURE UNDER | | | 481.229 FS DOES NOT EXEMPT THE DESIGNER RESPONSIBLE FOR | | | THE DRAWINGS FROM SIGNING AND DATING SAID DRAWINGS. | | | | | | 4)WORK ON EXISTING BUILDINGS IS COVERED UNDER THE FBC | | | (EXISTING) AS SUCH A DESIGN PROFESSIONAL OR OWNERMUST | | | ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION PER | | | 301.5 FBC (EXISTING) | | | | | | 5)PROVIDE 2 COPIES OF SURVEY THAT SHOW THE PROPOSED | | | ADDITION WITH SETBACK FROM PROPERTY LINES INDICATED | | | | | | 6)PROVIDE A SITE PLAN THAT SHOWS CORRECT MEASUREMENTS | | | THAT MATCH SURVEY. | | | | | | 7)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN | | | COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES. | | | SHOWDRAINAGE FROM BUILDINGAND AWAY FROM ADJOINING | | | PROPERTIES | | | | | | 8)IN AREAS OF QUESTIONABLE SOILS AS SHOWN IN THE | | | OFFICIAL ZONING MAP OF THE CITY OF WEST PALM BEACH, 2 | | | COPIES OF A SOIL TEST REPORT SHALL BE SUBMITTED PER | | | R401.4 FBC RES. | | | | | | 9)PROVIDE BEAM/LINTEL DETAIL. TOB = 8'-0" DOOR IS | | | 6'-8" IN ORDER TO FIT 8" BOND BEAM AND 8" LINTEL DOOR | | | WILL NOT FIT. IF POURED DROP DOWN BEAM IS USED SHOW | | | DETAIL. ALSO WILL BE REQUIRED FOR WINDOWS IF SAME | | | ELEVATION IS USED. | | | | | | 10)DRAWING DOES NOT SHOWACCESSIBLE BATHROOM THAT | | | COMPLIES WITH R322.1.1 FBC RES. W/C DOOR SIZE NOT | | | PROVIDED. | | | | | | 11)IDENTIFY SAFETY GLAZING FOR SHOWER DOOR THAT MEETS | | | PROVISIONS OF R308.4 FBC RES. | | | | | | 12)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS | | | REQUIRED PER R807.1 FBC RES. | | | | | | 13)SUBMIT ENGINEERED TRUSS DRAWINGS THAT | | | COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR | | | BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND | | | APPROVED BY THE DESIGNER OF RECORD | | | | | | 14)PROVIDE ENGINEERED SUBSTRATE ATTACHMENT FOR WOOD | | | BUCKS PER 1714.5.4.1 FBC | | | | | | 15)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF | | | EACH PRODUCT APPROVAL THAT | | | IS RELEVANT PER 9B-72. THESE SHOULD INCLUDE THE FLORIDA | | | STATE APPROVAL COVER PAGES, AND THE PRODUCT NOA THAT | | | LISTS THE SYSTEM COMPONENTS/ FASTENER LIST PAGES, THE | | | PAGES WITH THE CHOSEN ASSEMBLY/ SYSTEM TO BE USED AND | | | THE GENERAL LIMITATIONS PAGE. ALL CAN BE FOUND ON | | | WWW.FLORIDABUILDING.ORG | | | | | | 16)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA | | | STATE PRODUCT APPROVAL COVER | | | SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON | | | WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT | | | SUBMITTED APPLICATIONS WILL BE DENIED | | | | | | 17)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE | | | 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL PER 106.3.3 FBC* | | | | | | | | | 18)PLEASE PROVIDE (2) COPIES OF THE PRODUCT APPROVALS | | | THAT PERTAIN TO BUILDING (NO FIXED WINDOWS ARE SHOWN ON | | | THE DRAWINGS) | | | | | | 19)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT IS REQUIRED PRIOR TO | | | A PERMIT BEING ISSUED | | | | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-07-05 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-07-05 |
Time |
06:38 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-07-05 |
Time |
06:15 |
Sent To |
P |
|
| Notes |
| 2007-07-05 06:26:58 | | | | PROVISO | | | R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED IN | | | NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-05-30 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-05-30 |
Time |
16:51 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2007-05-30 |
Time |
16:29 |
Sent To |
M |
|
| Notes |
| 2007-05-30 16:51:18 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | | | | 2} THE BATH CIRCUIT MAY NOT FEED OTHER RECEPTACLES . | | | 210.11.(C)(3). | | | | | | 3} THE REFERENCED CODES ARE INCORRECT. NFPA-72 IS 2002 | | | EDITION, 101 IS 2003 EDITION. SEE REFERENCED MATERIAL | | | IN THE 2004 FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-04-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-04-12 |
Time |
14:45 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2007-04-12 |
Time |
13:49 |
Sent To |
P |
|
| Notes |
| 2007-04-12 14:06:07 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK | | | MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002 | | | FAC. | | | | | | 2} 240.24(D) OVERCURRENT DEVICES SHALL NOT BE LOCATED | | | IN THE VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS | | | IN CLOTHES CLOSETS.PANEL "A" CANNOT BE LOCATED IN THE | | | CLOSET. ALSO SEE 408.17 LOCATION RELATIVE TO EASILY | | | IGNITIBLE MATERIAL. | | | | | | 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), SEE CIRCUIT #2 AT 15 AMPS. | | | | | | 4} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1 | | | RESIDENTIAL FLORIDA BUILDING CODE. ALL 120-VOLT, SINGLE | | | PHASE, 15- AND 20-AMPERE BRANCH CIRCUITS SUPPLYING | | | OUTLETS INSTALLED IN DWELLING UNIT BEDROOMS SHALL BE | | | PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER, | | | COMBINATION TYPE INSTALLED TO PROVIDE PROTECTION OF THE | | | BRANCH CIRCUIT. | | | | | | 5} ALL 120-VOLT, SINGLE PHASE, 15- AND 20-AMPERE BRANCH | | | CIRCUITS SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT | | | BEDROOMS SHALL BE PROTECTED BY A LISTED ARC-FAULT | | | CIRCUIT INTERRUPTER, COMBINATION TYPE INSTALLED TO | | | PROVIDE PROTECTION OF THE BRANCH CIRCUIT. INDICATE SAME | | | IN PANEL SCHEDULE. | | | BRANCH/FEEDER AFCIS SHALL BE PERMITTED TO BE USED TO | | | MEET THE REQUIREMENTS OF 210.12(B) UNTIL JANUARY 1, | | | 2008. | | | | | | 6} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS | | | DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES | | | FOR CLARITY IN THE FIELD. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-11-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-28 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-28 |
Time |
16:19 |
Sent To |
M |
|
| Notes |
| 2007-11-28 16:19:47 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-10-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-17 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-17 |
Time |
16:39 |
Sent To |
M |
|
| Notes |
| 2007-10-17 16:40:12 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-07-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-02 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-02 |
Time |
15:47 |
Sent To |
E |
|
| Notes |
| 2007-07-02 15:48:13 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-05-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-25 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-25 |
Time |
16:54 |
Sent To |
E |
|
| Notes |
| 2007-05-25 16:54:48 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-05-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-23 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-23 |
Time |
08:49 |
Sent To |
Z |
|
| Notes |
| 2007-05-23 08:49:51 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-04-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-10 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-10 |
Time |
10:24 |
Sent To |
E |
|
| Notes |
| 2007-04-10 10:25:22 | TO "SFR" "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2007-04-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-04-03 |
Time |
17:21 |
Sent To |
Z |
|
| Notes |
| 2007-04-03 17:21:33 | TO ZONING |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2007-12-04 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-12-04 |
Time |
11:14 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-12-04 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2007-12-04 11:15:27 | REVISION TO MECH. PLAN, SHEET MP-1. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2007-10-23 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-10-23 |
Time |
08:40 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-10-23 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2007-10-23 08:59:42 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) MECHANICAL PLAN NEEDS TO BE SIGNED AND SEALED BY THE | | | ENGINEER ON RECORD (EVERETT C. FENNELL) SEE FAC | | | 61G15-23.002. | | | | | | 2) CONDENSER UNIT MODEL NUMBER SHOWING IN THE EQUIPMENT | | | NOTES IS FOR A 4 TON CONDENSER UNIT PLANS STATE ONLY A | | | 1.5 TON SYSTEM IS TO BE INSTALLED, PLEASE CORRECT, SEE | | | FBC 13-607.1.ABC.1.1. | | | | | | 3) AIR HANDLER UNIT MODEL NUMBER SHOWING IN THE | | | EQUIPMENT NOTES CAN NOT BE FOUND ON THE ARI DIRECTORY | | | WEB SITE, PLEASE CORRECT MODEL NUMBER AND SUBMIT THE | | | ARI REFERENCE NUMBER FOR THE A/C SYSTEM, SEE FBC | | | 13-607.1.ABC.3.1.1. | | | | | | 4) SANITARY RISER S/1 ON SHEET MP-1 HAD BEEN RED LINED | | | BY PLUMBING REVIEWER LAST TIME BUT REVISED PLANS MUST | | | SHOW THESE CORRECTIONS WHEN BEING REVISED, PLEASE | | | CORRECT, SEE FBC 106.1.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-07-09 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-07-09 |
Time |
11:02 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-07-09 |
Time |
11:02 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-05-31 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-05-31 |
Time |
09:05 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-05-31 |
Time |
09:05 |
Sent To |
P |
|
| Notes |
| 2007-05-31 09:19:48 | *** DENIED *** | | | 1) PROVIDE RETURN AIR TO MASTER SUITE, SEE 2004 FBC/R | | | M1602.4. | | | | | | 2) THE 12X6" RETURN AIR GRILL APPEARS TO BE TOO SMALL | | | FOR A 1.5 TON A/C SYSTEM PLEASE ENLARGE, OR YOU MAY | | | SUBMIT MANUFACTURER'S SPECIFICATION'S SHOWING THE | | | PRESSURE LOSS FOR THE RETURN AIR GRILL AND MANUAL D | | | CALCULATIONS FOR RESIDENTIAL DUCT DESIGN, SEE 2004 | | | FBC/R M1601.1. | | | | | | *** 2004 FBC/R M1602.4 BALANCED RETURN AIR MAY BE | | | ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE | | | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS | | | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR | | | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO | | | ACHIEVE PROPER RETURN AIR BALANCE. | | | (B)TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF | | | GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING | | | THROUGH-THE-WALL TRANSFER GRILLES AND USING AN | | | UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE | | | PROPER RETURN AIR BALANCE | | | (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET | | | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR | | | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY | | | ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE | | | SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-04-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-04-11 |
Time |
14:19 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2007-04-11 |
Time |
14:19 |
Sent To |
E |
|
| Notes |
| 2007-04-11 14:58:47 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, PER | | | 2004 FBC 13-600.3.A, (12-8-06 REVISION). | | | | | | 2) REVISED ENERGY CALCULATIONS WILL NEED TO BE SIGNED | | | BY OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 3) THE MINIMUM SEER FOR A/C UNITS IS NOW 13 SEER, SEE | | | 2004 FBC 13-607.1.ABC.3.2.1, PLEASE CORRECT. | | | | | | 4) SEE ENERGY CAL'S LINE 6 IS SHOWING 890 CONDITIONED | | | FLOOR AREA, PLANS SHOW ONLY 631 SQUARE FEET, PLEASE | | | CORRECT. | | | | | | 5) SEE MECHANICAL PLANS PAGE MP-1, PLEASE PROVIDE FOR | | | RETURN AIR BACK TO THE AIR HANDLER UNIT, PLEASE BE | | | ADVISED RETURN AIR MAY NOT COME FROM THE BATHROOM, SEE | | | 2004 FBC/R M1602.2 (4). | | | | | | 6) PLEASE SHOW THE SIZE OF ALL SUPPLY AIR GRILL ON | | | MECHANICAL PLANS. | | | | | | 7) MECHANICAL PLANS SHOW A 10 SEER A/C SYSTEM, SEE NOTE | | | #3 AND PLEASE CORRECT. | | | | | | 8) PLEASE SEE MECHANICAL PLANS YELLOW HIGH LIGHTED | | | SUPPLY AIR DUCTS (FLEX ?) NEED TO SHOW THE SIZE OF THE | | | DUCTS. | | | | | | 9) THE PLANS NEED TO BE SIGNED AND SEALED BY THE | | | ENGINEER EVERETT C. FENNELL AS HIS INFORMATION IS IN | | | THE TITLE BLOCK. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-07-09 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-07-09 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-07-09 |
Time |
10:09 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-06-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-06-14 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-06-14 |
Time |
10:09 |
Sent To |
B |
|
| Notes |
| 2007-06-14 10:29:50 | DENIED; | | | 1. SANITARY RISER DIAGRAM FOR AUTOMATIC CLOTHES WASHER | | | SHOULD BE 3" THE WASHER AND LAUNDRY TUB CAN BE ON SAME | | | STACK. ACLEANOUT IS REQUIRED AT 48" ABOVE FINISH FLOOR. | | | SEE FBC-2004 PLUMBING SECTION 406.3. (ONE SET OF PLANS | | | MARKED IN RED) | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-04-24 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-04-24 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-04-24 |
Time |
09:51 |
Sent To |
B |
|
| Notes |
| 2007-04-24 10:02:48 | DENIED; | | | A SANITARY RISER DIAGRAM IS REQUIRED SHOWING ALL | | | PLUMBING FIXTURES TO BE INSTALLED IN THE NEW ADDITION. | | | SIZE ALL PIPES AND SHOW VENT LOCATIONS AND ALL | | | CLEANOUTS REQUIRED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2007-05-23 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-05-23 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2007-05-23 |
Time |
14:06 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-04-09 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-04-09 |
Time |
20:26 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2007-04-09 |
Time |
20:26 |
Sent To |
I |
|
| Notes |
| 2007-04-09 20:31:37 | ***FAILED*** | | | | | | 1) PROPOSED ADDITION SHALL BE SHOWN ON TWO (2) COPIES | | | OF THE SURVEY AND SHALL INDICATE THE DISTANCE FROM THE | | | PROPOSED ADDITION TO ALL PROPERTY LINES. | | | | | | 2) SITE PLAN DIMENSIONS DO NO NECESSARILY CORRESPOND | | | WITH WHAT IS SHOWN ON THE SURVEY...ENSURE THAT ALL | | | PLANS ARE CONSISTENT. | | | | | | 3) BUILDING HEIGHT SHALL BE PROVIDED ON THE ELEVATIONS | | | AS MEASURED FROM GRADE TO THE MEAN POINT OF THE ROOF | | | PITCH. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | | AT (561) 822-1435. |
|
|