Plan Review Details - Permit 07040009
Plan Review Stops For Permit 07040009
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-05-24 Cont ID  
Sent By shill Date 2007-05-24 Time 13:38 Rev Time 0.00
Received By shill Date 2007-05-24 Time 13:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-27 Cont ID  
Sent By btrobaug Date 2007-04-27 Time 13:30 Rev Time 0.33
Received By btrobaug Date 2007-04-27 Time 13:06 Sent To P
Notes
2007-04-27 13:30:00 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY. THE CONTRACTOR OF RECORD MAY BE THE
 DESIGN PROFESSIONAL IF EXEMPTIONS UNDER THOSE STATUTES
 ARE APPLICABLE.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3
 FBC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-05-02 Cont ID  
Sent By mperson Date 2007-05-02 Time 08:10 Rev Time 0.45
Received By mperson Date 2007-05-02 Time 08:10 Sent To B
Notes
2007-05-02 09:10:09DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1.A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPLIED FOR AND APPROVED BY ZONING FOR
 THE GENERATOR LOCATION.
 NOTE: PLEASE REVISE GAS DRAWINGS TO REFLECT ZONING
 REQUIREMENTS.
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC AND
 DOES NOT CLEARLY SHOW ALL CUT SECTIONS OF PIPE AND
 CORRESPONDING LEGTHS. THE ISOMETRIC MUST REFLECT BOTH
 THE ABOVE AND UNDERGROUND PIPING INCLUDING TANK,
 VALVES, SEDIMENT TRAPS, 1ST AND 2ND STAGE REGULATORS.
  
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: PLEASE INCLUDE THIS INFORMATION ON THE
 RESUBMITTED ISOMETRIC DRAWING INCLUDING BOTH THE ABOVE
 AND UNDERGROUND PIPING.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER, LP TANK), TO THE MOST REMOTE OUTLET
 IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: PLEASE SUBMIT MANUFACTURER SPECIFICATIONS ON 1ST
 AND 2ND STAGE REGULATORS WITH THE FOLLOWING
 INFORMATION, A}MANUFACTURER NAME B}SHOW LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL).
  
 6. CLEARLY SHOW THE LOCATION AND CAPACITY
 OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 7. IF THE TANK IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION 6.6.1, 6.6.16,
 6.6.2.1.
 NOTE: PLEASE SUBMIT DETAIL ON HOW UNDERGROUND TANK IS
 TO BE ANCHORED.
  
 8. PLEASE CLEARLY INDICATE ON TWO COPIES OF A SITE
 PLAN OR SURVEY THE LOCATION OF THE PROPOSED GENERATOR
 INDICATING ALL DIMENSIONS FROM PROPERTY LINES AND
 DISTANCES FROM ADJACENT DWELLING STRUCTURES. ALSO
 INDICATE THAT THE GENERATOR EXHAUST IS NOT CLOSER THAN
 TEN FEET FROM ANY OPENING INTO THE DWELLING STRUCTURE.
 THIS INCLUDES DOORS, WINDOWS AND ATTIC VENTILATION
 OPENINGS.
  
 9. NOTE: GAS CONTRACTOR IS NOT IN THE CITY OF WEST
 PALM BEACH SYSTEM. CONTRACTOR MUST PROVIDE THE
 FOLLOWING INFORMATION. COPY OF CURRENT LICENSE, PROOF
 OF GENERAL LIABILITY AND WORKER'S COMP.
  
 10. THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN
 MUST PRINT AND SIGN THEIR NAME TO SAME PER FBC-2004
 CHAPTER 1, SECTION 106.3.4.3. IF AN ARCHITECT OR
 ENGINEER, COMPLY WITH 418 AND 417 FS, RESPECTIVELY. THE
 CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL IF
 EXEMPTIONS UNDER THOSE STATUTES ARE APPLICABLE.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 11:01 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 11:01 Sent To E
Notes
2007-04-12 11:01:43TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-24 Cont ID  
Sent By shill Date 2007-05-24 Time 13:38 Rev Time 0.00
Received By shill Date 2007-04-03 Time 17:45 Sent To  
Notes
2007-04-03 17:45:39TO ZONING

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-16 Cont ID  
Sent By tgordon Date 2007-04-16 Time 12:21 Rev Time 0.20
Received By tgordon Date 2007-04-16 Time 12:21 Sent To E
Notes
2007-04-16 12:23:22*** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-10 Cont ID  
Sent By kdfreema Date 2007-04-10 Time 14:58 Rev Time 0.00
Received By kdfreema Date 2007-04-10 Time 14:58 Sent To I
Notes
2007-04-10 15:05:30***FAILED***
  
 THE GENERATOR MUST BE INSTALLED NO FURTHER THAN FOUR
 (4) FEET INTO A REQUIRED SETBACK.
  
 PLEASE CALL KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH ANY QUESTIONS.