| 2007-05-02 09:10:09 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1.A GAS PERMIT CAN NOT BE ISSUED UNTIL |
| | A GEN/RES PERMIT APPLICATION HAS BEEN |
| | APPLIED FOR AND APPROVED BY ZONING FOR |
| | THE GENERATOR LOCATION. |
| | NOTE: PLEASE REVISE GAS DRAWINGS TO REFLECT ZONING |
| | REQUIREMENTS. |
| | |
| | 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC AND |
| | DOES NOT CLEARLY SHOW ALL CUT SECTIONS OF PIPE AND |
| | CORRESPONDING LEGTHS. THE ISOMETRIC MUST REFLECT BOTH |
| | THE ABOVE AND UNDERGROUND PIPING INCLUDING TANK, |
| | VALVES, SEDIMENT TRAPS, 1ST AND 2ND STAGE REGULATORS. |
| | |
| | 3. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | NOTE: PLEASE INCLUDE THIS INFORMATION ON THE |
| | RESUBMITTED ISOMETRIC DRAWING INCLUDING BOTH THE ABOVE |
| | AND UNDERGROUND PIPING. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER, LP TANK), TO THE MOST REMOTE OUTLET |
| | IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | NOTE: PLEASE SUBMIT MANUFACTURER SPECIFICATIONS ON 1ST |
| | AND 2ND STAGE REGULATORS WITH THE FOLLOWING |
| | INFORMATION, A}MANUFACTURER NAME B}SHOW LISTING FROM A |
| | NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL). |
| | |
| | 6. CLEARLY SHOW THE LOCATION AND CAPACITY |
| | OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | 7. IF THE TANK IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION 6.6.1, 6.6.16, |
| | 6.6.2.1. |
| | NOTE: PLEASE SUBMIT DETAIL ON HOW UNDERGROUND TANK IS |
| | TO BE ANCHORED. |
| | |
| | 8. PLEASE CLEARLY INDICATE ON TWO COPIES OF A SITE |
| | PLAN OR SURVEY THE LOCATION OF THE PROPOSED GENERATOR |
| | INDICATING ALL DIMENSIONS FROM PROPERTY LINES AND |
| | DISTANCES FROM ADJACENT DWELLING STRUCTURES. ALSO |
| | INDICATE THAT THE GENERATOR EXHAUST IS NOT CLOSER THAN |
| | TEN FEET FROM ANY OPENING INTO THE DWELLING STRUCTURE. |
| | THIS INCLUDES DOORS, WINDOWS AND ATTIC VENTILATION |
| | OPENINGS. |
| | |
| | 9. NOTE: GAS CONTRACTOR IS NOT IN THE CITY OF WEST |
| | PALM BEACH SYSTEM. CONTRACTOR MUST PROVIDE THE |
| | FOLLOWING INFORMATION. COPY OF CURRENT LICENSE, PROOF |
| | OF GENERAL LIABILITY AND WORKER'S COMP. |
| | |
| | 10. THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN |
| | MUST PRINT AND SIGN THEIR NAME TO SAME PER FBC-2004 |
| | CHAPTER 1, SECTION 106.3.4.3. IF AN ARCHITECT OR |
| | ENGINEER, COMPLY WITH 418 AND 417 FS, RESPECTIVELY. THE |
| | CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL IF |
| | EXEMPTIONS UNDER THOSE STATUTES ARE APPLICABLE. |
| | |
| | END OF COMMENTS: |
| | |