Plan Review Details - Permit 07031031
Plan Review Stops For Permit 07031031
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-10 Cont ID  
Sent By btrobaug Date 2007-04-10 Time 11:15 Rev Time 1.00
Received By btrobaug Date 2007-04-10 Time 07:37 Sent To I
Notes
2007-04-10 10:18:36 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} INDICATE COMPLIANCE WITH 250.112 NEC. THERE ARE NO
 EQUIPMENT GROUNDS RAN WITH ANY OF THE FEEDERS ON THE
 PLAN.
  
 2} THE SINGLE PHASE LOAD CALCULATION INCORRECTLY
 APPLIES 220.14(F) FOTR THE GENERAL LIGHTING LOAD. THAT
 LOAD SHOULD BE TAKEN FROM 220.12. ALSO@ 125 % PER
 215.2(A)(1).
  
 3} PROVIDE A SITE PLAN INDICATING THE LOCATION OF ALL
 SERVICE EQUIPMENT SO THAT THE INSPECTOR CAN LOCATE
 SAME.
  
 4} THE TITLE BLOCK FOR THE DESIGNER OF RECORD MUST
 CONTAIN A CERTIFICATE OF AUTHORIZATION PER F.A.C.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-10 Cont ID  
Sent By btrobaug Date 2007-04-10 Time 11:15 Rev Time 0.00
Received By btrobaug Date 2007-03-29 Time 18:37 Sent To PC
Notes
2007-03-29 18:37:49ELEC INBOX