| 2007-04-10 09:53:27 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | |
| | COMMENTS FROM FIRST REVIEW, NOT PROPERLY ADDRESSED: |
| | |
| | |
| | _XX_3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| | SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG |
| | |
| | THIS WAS ADDRESSED BUT ONLY ONE SET WAS SUBMITTED.TWO |
| | COMPLETE SETS OF PERMIT DOCUMENTS REQUIRED FOR |
| | PERMITTING, FBC*106.1. |
| | |
| | _XX_4.)1ST REVIEW - FOR THE FLAT DECK, SELECT THE |
| | APPROVED ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH |
| | FASTENER YOU ARE USING IF THE OPTIONS HAVE DIFFERENT |
| | PRESSURE LIMITATIONS. NOTE THAT THE ASSEMBLY YOU CHOSE |
| | IS LIMITED TO -45PSF, NO ENHANCED FASTENING ALLOWED, |
| | GENERAL LIMITATION #9. |
| | |
| | 2ND REVIEW - TWO DIFFERENT ASSEMBLIES ARE MARKED, ONE |
| | WITH GENERAL LIMITATION #9.THE ENGINEER SPECIFIES THE |
| | OTHER ASSEMBLY.DO NOT MARK MORE THAN ONE ASSEMBLY. |
| | |
| | _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES. |
| | |
| | 2ND REVIEW - THIS WAS DONE WITH ENGINEERING.HOWEVER, |
| | THE ENGINEER STATES THIS IS A RECOVER DECK, BUT YOUR |
| | APPLICATION STATES THAT THIS IS A REROOF. |
| | |
| | _XX_ 7.)PRODUCT APPROVAL IS FOR RECOVER DECK, |
| | APPLICATION IS FOR REROOF. |
| | |
| | 2ND REVIEW - APPLICATION IS NOT CONSISTENT WITH |
| | ENGINEERING AND PRODUCT APPROVAL SUBMITTED.PLEASE |
| | ADDRESS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |